| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.5 CrAccepted-AOC | ₹6.5 Cr | L1 | Accepted-AOC Award of Work Eligible L1 bidder recommended by Tender Committee and duly approved |
| 2 | L2₹6.8 Cr+₹29.2 L (4.49%)Rejected-Finance | ₹6.8 Cr+₹29.2 L (4.49%) | L2 | Rejected-Finance Rejected as not being L1 bidder |
| 3 | L3₹7.4 Cr+₹94.3 L (14.5%)Rejected-Finance | ₹7.4 Cr+₹94.3 L (14.5%) | L3 | Rejected-Finance Rejected as not being L1 bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Rejected under one sub head of Work Experience as per Cl 8A,9e1 of NIT and duly approved |
Tender Value
₹8.6 Cr
EMD Value
₹10.7 L
Closing Date
14 Sept 2023, 5:00 pmClosed
GM(CMC), SECL HQ
Office of the GM(CMC), SECL HQ, Bilaspur
2 x 1000KVA, 33/3.3KV Substation on turnkey basis at Jhiria West, Hasdeo Area as detailed in NIT, TENDER DOCUMENTS and BoQ.
2023_SECL_284913_1
SECL/BSP/CMC/e-Ten/Turnkey/589 dt 2.8.23
Turnkey
Electrical and Maintenance Works
Item Rate
2190 days
JHIRIA WEST OCP, HASDEO AREA, SECL
Please refer Tender documents.
6 documents required · 6 mandatory
₹10.7 L
Office of the GM(CMC), SECL HQ, Bilaspur
6 Mar 2024
3 Aug 2023
16 Sept 2023
3 Aug 2023
14 Sept 2023
13 Aug 2023
3 Aug 2023 - 7 Sept 2023
10 Aug 2023
Amount
DESIGN AND ENGINEERING COST (for 2X1000kVA,33/3.3kV S/S)
Design and Engg on PLANT & MACHINERY ( P&M - Electrical) to be supplied by bidder inlcusive of Overhead constuction cost, Contigencices, but excluding GST
Design and Engg on Civil and structural work
CIVIL CONSTRUCTION AND STRUCTURAL WORKS for 2X1000kVA,33/3.3kV S/S on Turnkey Basis at Jhiria West OCP inclusive of Insurance,Contingencie but excluding GST
Sub-Station Building
Outdoor Steel Structures
Foundation of outdoor structures including Transformer foundation
Cable Trench
Barbed wire fencing
Boundary wall
Surface dressing
Stone laying
Anti weed treatment
Bore well with submersible pump
Path way
Security Room
RCC sump and Pump House
Shed for DG & oil filter unit
Drain along boundary wall
Parking Shed
Oil Overflow Chamber
Oil Drain Pipe
Survey & Soil testing
SUPPLY OF PLANT & MACHINERY inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST for substation (2 X 1000 KVA, 33/3.3 KV Substation )
Isolator,33kV, 3 poles, 1250Amps, 25 kA, arrangement for interlocking with vacuum circuit breakers (Min 06 nos)
Isolator,33kV, 3 poles, 1250Amps, 25 kA, arrangement for interlocking with vacuum circuit breakers with earthing switch (Min 04 nos.)
Isolator,33kV, 3 poles, 1250Amps, 25 kA, with DO fuse (Min 04 nos)
Lightning arrester, station class, 30 kV, 25kA, suitable for 33 kV supply, effectively earthed(each set consists of 3 Nos.) with counters/surge monitors (Min 08 nos)
Vacuum Circuit breaker, outdoor type, 33kV,1250 A, 25 kA, including Indoor type remote control and relay panel (Min 05 nos)
Current transformer (CT), single phase, out door type, 33 kV, 3 cores, CTR as required (each set consists of 3 nos.) (Min 05 nos)
Potential transformer (PT), outdoor type, 33 kV /110V, 3 cores, 100 VA each for 33 kV, 3 phase system, (each set consists of 3 nos.) (Min 02 Sets)
Transformer outdoor type conforming to IS:2026 (current) having OFF-LOAD tap changer on HV side with all accessories as per IS:3639 (Current) with the rating asgiven below Rated kVA: 1000 Rated Voltage(primary):33000V Rated Voltage(secondary):3300V Connection and vector group:Dy11 (Min 02 nos)
Earth Fault protection system for NGR consisting of CT , instantaneous earth fault relay etc (Min 02 nos)
3.3 kV switch board panel, indoor type with VCB,14 panel (Min 01 No.)
3.3 kV capacitor banks , 200 kVAr WITH APFC (Min 02 nos.)
Station Transformer, 160 kVA, 3.3/0.415 kV, DYn11, Cu wound (Min 01 no.)
Lighting Transformer, 63 kVA, 33/0.230(L-L) kV, Cu wound (Min 01 no.)
415 V, 3Ph - neutral , Power distribution board, Indoor type (Min 01 no.)
Main Lighting Distribution Board,230V, Indoor type (Min 01 no.)
Battery and battery charging (with one stand bye battery charging unit) equipment and control panels etc. (Min 01 no.)
Insulators, strung bus, ACSR conductors, steel hardware etc for 33 kV sides in the out door yard.
Earthing system including earth pits, chemicals ,required galvanised strips/flats for inter connection etc.
Lightning protection system consisting of spikes, earth pits, galvanised strips /flats, shield conductors etc.
Lighting System
Decorative, 1x15 W and 2x15/18 W LED light fittings for lighting of substation building
Tubular steel poles, 9m height along with required) LED lamps with fittings
Lighting masts, 11m height along with required no of LED lamps with fittings.
90 W (min) LED lamps (complete) fitted on substation building(4 Nos) along with two nos post top lantern with 40W LED on the main entrance of substation Building.
Accessories such as sub distribution board, junction boxes, individual control cables, PVC conduits/ casings, back up fuses, switches, sockets, ceiling roses, single core PVC cable with copper conductors, flexible wire etc.
Emergency lighting system suitable for operation on 110 V DC supply in substation building
DG Set , 63 kVA , with 415 V Power Distribution Board , cables , change over switch etc. (Min 01 no.)
2 pole structure fitted with gang operated AB switch, lightning arrester etc for outgoing feeders (As per Requirement)
(i) Fire Fighting System - Supply of Diesel Pump , Jockey Pump and Electric Pump for hydrant type fire fighting ,associated change over switch, 415 V panel with protection, cables and electricals, hoses, nozzles, hydrant valves, electricals for submersible pump etc as per design , (ii) Fire detection, Alarm and Protection system in the substation building and pump house etc. (iii)Portable fire extinguisher with sand Buckets
Cable and accessories
HT power cable, 3300 V grade, XLPE, FRLS, stranded Aluminium conductor
LT Power cable, 1100V grade, PVCSWA, 10 sq. mm.(minimum),3/4 core copper stranded conductors
Outdoor Lighting cable, 1100V, PVCSWA , 2 cores, 10 sq mm (minimum) stranded copper conductors
Outdoor Control cables, 660V/1100V grade, PVCSWA, not less than 2.5 sq mm , copper conductors of with required number of cores
Wires for internal wiring of 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor cable of 660 /1100V grade
Cables for internal control wiring of illumination, ceiling fans, power sockets etc. 1.5 sq mm and 6 sq mm size, PVC insulated copper conductor of 660 /1100V grade
Cable trays, cable racks, binding materials, cable glands/lugs, cable jointing kit, bolts, nuts, washers, termination kit etc.
Miscellaneous items
Room air conditioners, 1.5 t capacity including servo stabilizer
Exhaust fans, 600 mm sweep (Min 03 nos.)
Ceiling fan ,1200 mm sweep along with electronic regulator
Water cooler with water purifier
Vacuum Cleaner,Domestic type
Erection and commissioning of Plant and Machinary for substation to be suplied by bidder as above inclusive of Overhead Construction cost, Insurance, Contingencies , but excluding GST
Training of O&M staff
Store cost for maintenance of P&M during Defect Liability Period (DLP) of five years.
Cost of Maintenace during during Defect Liability Period (DLP) of five years.
Total impact of GST for the purpose of CTC
SRISHTI CONSTRUCTIONS (J.V)
RESILIENT BEPL JV
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .