Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹16,800
Closing Date
18 Jul 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
(1) Installation of electric poles cemented 8 mtr. and wire in different Pyts. (2) Procurement of transformer 63 KVA
2023_PDD_220949_1
ED/Udh/35 of 2023-24 dt. 11-07-2023
Open Tender
Electrical Works
Turn-key
60 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹600
Executive Engineer Electric Division UdhampurJPDCL
₹16,800
5 Aug 2023
11 Jul 2023
19 Jul 2023
11 Jul 2023
18 Jul 2023
11 Jul 2023
11 Jul 2023 - 14 Jul 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 0.6 Km 1 Phase 2 Wire LT line on 8 mtr. Long PCC poles with 30mm², ACSR Weasel conductor at DDC Constituency UDHAMPUR-1
8 mtr. Long PCC poles (PCC-WL-360 Kg)
GI M Clamps for shackle insulator
30mm² ACSR Conductor
Shackle insualtor
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 20mm 2.5 mtr. Long through GI Strip
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 0.5 Km 11 KV line on 9 mtr. PCC poles, 30mm² ACSR Weasel Conductor with minimum span of 52 mtrs. at DDC Constituency Udhampur-1.
9 mtr. Long PCC Pole (PCC-WL-360 KG)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30mm² ACSR Conductor
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm
Galvanized Nuts and Bolts
Danger Plates with Clamps
Anti Climbing Device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip.
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Installation of 63 KVA Sub station on 9 mtr. PCC poles at DDC Constituency Udhampur-I
11/0.433 KV, 3-phase distribution Transformer 63 KVA with Bimetallic Terminal Connectors Energy Level-2 Aluminium Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
120mm² (1ckt) 1.1 KV Grade,single core PVC insulated stranded conductor FRLS Type
9 mtr. Long ST pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
LT distribution box for 63 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI standed wire complete
PG Clamps
Danger Plates with Clamps
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
VEENA CONSTRUCTION CO.
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .