CWE (AF) Gurgaon
HQ CWE (AF) Gurgaon, Old Palam Road, Delhi Cantt-110010
REPAIR AND MAINT OF EXTERNAL ELECTRIFICATION, HT/LT EQUIPMENT, DG SET STREET LIGHT/FIRE FIGHTING AND CONNECTED WORKS AT IMAC STN AT NTS GURGAON
2021_MES_472728_1
CA NO CWE/GGN/GT-13/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Gurgaon
As per NIT
9 documents required · 9 mandatory
₹500
GE (AF) Gurgaon
₹76,400
Yes
3 Dec 2021
3 Sept 2021
11 Oct 2021
3 Sept 2021
9 Oct 2021
25 Sept 2021
Amount
M&L for Carry out 'C' check from authorised rep or service engineer from the manufacturer of DG set of 2X750 KVA,capacity Make : Cummins (excluding the cost of the following spares all as per OEM instructions and directed by Engineer in Charge .
S & F in replacement of Element Lub oil filter (cat part No.3238204)
S & F in replacement of Kit fuel filter and Ring. (cat part No.3238493)
S & F in replacement of Kit super by pass filter element (cat part No.3879488)
S & F in replacement of SEAL 'O' Ring (cat part No.3010937)
S & F in replacement INHIBITOR CORROSION 2/ 10 Ltrs (cat part No.3167222)
S & F in replacement STRIP TEST (cat part No.4912590)
S&F in replacement of Engine oil, VALVOLINE PREMIUM BLUE 7800 PLUS 2/20 Ltr (Cat Part no. 505441)
S&F in replacement of Engine oil, VALVOLINE PREMIUM BLUE 7800 PLUS1/55 Ltr (Cat Part no. 506655)
S&F in replacement of Engine oil, VALVOLINE PREMIUM BLUE 7800 PLUS1/210 Ltr (Cat Part no. 504626)
S & F in replacement of air cleaner element . (Cat part no. 4020551)
S & F in replacement of air cleaner element . (Cat part no. 4020552)
S&F replacement of Seal O Ring (Cat part No. 3042542)
S&F replacement of Seal O Ring (Cat part No. 3066914)
S&F replacement of Gasket Rocker Lever Cover (Cat part No. 4920076)
S&F in replacement of existing batteries (maintenance free) 12 V, 160 AH for 750 KVA DG Set complete All as specified & directed by engr-in-charge Make: PULSE ULTRA
Supply and fixing in replacement of AVR S/F VARIABLE SPEED DCDG suitable for DG set with input voltage range 415 Volt AC with neutral & Out put DC voltage suitable for DG set of 750 KVA complete all as specified and directed by Engineer -in-charge.
M&L for disconnecting and opening of self starter assemlly 12/24 volt for repair from DG set of 750 KVA & replacement of unserveceable part of self starter suitable size as required on site complete all as specified and directed. Note :- Supply of Spares shall be measured & paid seperatly.
Supply only Armature.
Supply only Solenoied switch
Supply only Bush gear
Supply only 'O' Ring assy.
Supply only Bush set.
Supply only FIELD Coil
Supply only Sealing kit.
Supply only Brush Set
S&F only the following items of DG Set of various capacity :-
Battery terminal, lug, bolts type suitable for heavy duty battery.
Battery leads of copper conductor multiwired 70 Sqmm Single Core.
Hinges for DG set door of any size, any type as required on site.
V belt for fan pulley for DG set of 750 KVA DG Set complete all as specified.
Fuel hose pipe from fuel filter to fuel pump for DG set of 750 KVA, complete all as specified.
Fuel pipe from fuel tank to fuel filter for DG set of 750 KVA, complete all as specified.
Material & labour for carrying out complete servicing of DG set (750 KVA), PCC3.3 digital panel (power command) including checking and rewiring faulty electrical circuit using 1.5 sqmm FRLSH copper conductor, repairing of PCC3.3 card, making all electric connections and testing for smooth operation complete all as directed.
M&L for complete descaling of cooling system of 750 KVA by radiwash with two times circulation of radiwash by means of running of engine & cleaning of fan blades, crankcase breather, radiator and its fins by means of high pressure air, or water.
Repair/ comprehensive maintenance/ testing of Fire alarm system (Make: Honeywell) smoke detectors (77 Nos), Heat detectors (6 Nos), Hooters (15 Nos), MCP (15 nos) including Smoke Detector Continuity Report, checking of all fire detectors are in working condition and the LED is working,carry out smoke test and detector fitness test once in every month and submit the report,Check all fire Panels and repeater panels.,Check all cables and ensure that there is no short circuit/break in the circuit, Carry out cleaning of all the external components, All faulty detectors, if noticed to be replaced with call log no, all false fire alarms would be investigated and to resolved including replacement of non-servicabe smoke sensor, heat sensor, remote panel , monthly inspection report all as per instruction, specified and directed by Engr-in-charge.The tenderer shall have to replace the U/s material with OEM material only. The cost of replaced spare parts are included in comprehensive maintenance of schedule item. Old material will be contractor property .
Repair/comprehensive maintenance/hydro testing of FM 200 (Fire suppression system-o4 cylinder, 80 KG Each) (Make: RAVEL FIRE) including Regular monthly Maintenance, Checking of proper pressure, Maintenance chart for each cylinder, Filling of gas if required due to any reason (Need extra charge with cost approval), including maintenace cost of VESDA LASER FOCUS 250 monthly inspection report all as per instruction ,specified and directd by Engr-in-charge.The tenderer shall have to replace the U/s material with OEM material only. The cost of replaced spare parts included in comprehensive maintenance of schedule item.Old material will be contractor property .
Repair/ comprehensive aintenance/testing of water leak detection system (Make: STAR ELECTRONICS CONCEPTS) including regular monthly Maintenance, check all water leakage sensors, control panel, check insulation breakdown due to soaked leading cable leading to signal breakdown, check LED dispaly ststus for all zones including all maintenace cost of WLD System monthly inspection report all as per instruction, specified and directd by Engr-in-charge. The tenderer shall have to replace the U/s material with OEM material only. The cost of replaced spare parts are included in comprehensive maintenance of schedule item. Old material will be contractor property .
M&L for Dehydration including filtration and cleaning of Transformer oil by dehydrating machine incl testing of sample before and after dehydration and filtration all as specified and directed NOTE:- Contractor has to arrange the dehydration machine and testing kit without any extra cost to the dept. Test report to be submitted after completion of job. (Transformer 2x750 KVA)
Supply & Filling /pouring of up to the appropriate level Transformer oil of low viscosity having dielectric strength not less than 60 KV complete all as specified and as directed . NOTE:- Dielectric strength test shall be carried out at site before poring/filling in transformers in the presence of Engr-in-Charge on the site
Repar/ maintenance of transformer by isolating ,disconnecting of input/output ,supply cable, opening of top of transformer, detecting of fault ,u/s component, cleaning of serviceable parts/ component ,including replacement of worn out spare parts, finding of oil leakage & sealing it by oil seal or gas welding etc if any all as specified and directed. (Transformer 750 KVA)
Material and labour for preparation of old painted surfaces of floor mounted indoor type transformer of 750 KVA capacity by cleaning/rubbing with course cloth wire brushes to remove dust deposits oil grease and repainting by applying one coat of spray paint with synthetic enamel paint of approved colour without disturbing/damaging the electrical net work system/equipment including making of capacity /rating /incoming outgoing details in capital english alphabet of size all as specified and directed.
Taking down defective unserviceable LT bush porcelain insulator and supply and fix new LT bush porcelain insulator with oil seal for transformer outdoor/indoor of 750KVA all as specified and directed
Taking down defective unserviceable HT bush porcelain insulator and supply and fix new HT bush porcelain insulator for transformer outdoor/indoor of 750 KVA all as specified and directed
Taking down the HT vacuum circuit breaker/Oil Circuit breaker of any capacity 11 KV, 630 amp 25 KA,Make: joyti Ltd. for servicing, repairs, replacement of defective/worn out components and re-assembling complete comprising of the following including testing and commissioning to the entire satisfaction of Engineer-in-Charge complete all as specified and directed.
(a) Dismantling the HT VCB from the enclosure consisting of interuper assembly, socket contacts, checking the serviceability of the following parts carefully including cleaning, adjustments, replacement of defective/worn out parts and re-assembling the unit complete. (i) Cleaning the external surface of bushings with CTC or Liquid ammonia to remove the accumulation of dirt or any other deposits. Inspection of bushings and make sure that vibration due to breaker operation have not caused the bushings to move resulting misallignment of contacts. (ii) Checking the interrupter assembly and contacts. Checking the allignment of contacts and setting the contact surfaces to bare firm and uniform pressure and adjust the gap as per manufacterurs tolerance. Badly potted contacts needs to be replaced. Note: Contacts shall be ordered separately. (iii) Checking the breaker bushing of bus bar and circuit side inspecting the interval surface carefully for any charging/trackings,replacement of bushings.
(b) Dismantling the spring charging mechanism of the HT VCB, checking the operations of the closing/tripping through closing/tripping coils electrically as well as manual charging including cleaning adjustments and replacement of defective /worn out parts re-assembly complete for the following. (i) Checking the condition of the spring charging motor along with gear box including servicing to the motor bushes, lubrication of bearing surfaces etc. (ii) Checking the ratchet wheel assembly, driving and charging parts including replacement of defective ratchet wheel and parts. (iii) Checking the type and release prop and dash pot assembly making necessary adjustment including replacement of defective/worn out components. (iv) Checking the operating mechanism of the breaker and ensure its operation freely through entire stroke. Parts which shows excessive wear and tear to be replaced or adjusted as per manufacterurs tolerance. (v) Checking of operating voltage at mechanism terminals and tripping arrangement for positive tripping. Contacts to be examined for their condition and operation. Dress the pitted contacts and replace if necessary. (vi) Review the adjustment of all pressure switches and lockout devices. (vii) Inspecting all bolts, nuts, pins and coller pins are in place and they are tight and opened properly. (viii) Inspection, cleaning and relubrication of circuit earthing truck with Aseol Molite or Moliday 47. Note:- (I) Cost of additional hardware like, bolts, nuts , washers and spring washers, petroliumjelly CTC, to put the breaker in serviceable condition is deemed to be included in the rates quoted.
Supply of the following material for VCBs complete all as specified and directed :-
Power Pack with 12 V
Isolating Contact 2 Pair Finger Type
Isolating Contact 2 Pair Flat Type
Vaccum Interrupter
Flexible connection
Shutter for racking Shaft
Closing Coil 110V AC/DC
Shunt Trip Coil 24V DC/110V DC
Ratchet Wheel
Motor cut off switch
Bus bar Spout 800A
Circuit Spout 800A
Shutter for bus bar spout
Shutter operating Link
Draw out type 3 Phase PT 11KV/110V 200 VA class 1.0 cast resin wound type, 3Core with enclosure, wheels, HT bushings and HT fuses mounted on with drawable truck of existing make and model.
HT Epoxy CT 200-100/5-5A with 15 VA class 1.0 for metering and 5 P 10 for protection.
HT Epoxy CT 100-50/5-5A with 15 VA class 1.0 for metering and 5 P 10 for protection.
LED indication Lamp
Service/Test position Limit Switch
Space heater
Thermostat for Space heater
HT Tape roll 16.6 M
Spring Motor with gear box
Bus bar supporting insulator
HRC Fuse suitable for HT CBs 2A to 16A
Auxialary contact Male&Female
Taking down the LT air circuit breakers of various capacities form 630 amps to 1600 amps for repairs, servicing comprising the following and refixing the same, re-orientation and labour for taking down the defective parts and refixing the same spare parts (including spare parts cost ) all as specified and directed (a) Checking/repair of mechanical system of ACB. (b) Checking/repair of the manual closing/tripping of breaker.
Supply & Fixing in repalcement of 1250A, Electrically operated Draw-out type ACB 4 pole fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch all as specified and directed. Make: Cat No.SL96074 of L&T/or equivalent in Schnider .
Supply & Fixingin repalcement of 1600A, Electrically operated Draw-out type ACB 4 pole fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw/ for protection against common outgoing of change over switch all as specified and directed. Make: Cat No.SL96075 of L&T/or equivalent in Schnider .
Supply & Fixing in repalcement of 630A, Electrically operated Draw-out type ACB 3 pole fixed type with Microprocessor basedSR18G relay with protection aganist over current, earth fault and short circuit, 50KA=Icu=Ics=Icw for protection against common outgoing of change over switch all as specified and directed. Make: Cat No.SL96051 of L&T/or equivalent in Schnider .
Taking down the old deterioted/damaged rubber mats from the sub stations, supply & lay synthetic insulating rubber matsof size: 2m x 1mx 19 mm for up to 11 KV all as specified & directed MAKE: Jyothi/Electromat
Supply and fix silica gel breather assembly complete with breather unit and silica gel including connecting with proper rubberised gasket and necessary fittings GI fittings for fixing/assembling for 750 KVA transformer complete by removing the unserviceable silica gel breather assembly all as specified and directed by Engr-in-chrage.
Repair/maintenance of 2000 Amp, 433 V, TPN, 3 phase, 1.1 KV sandwitch type bus bar including physical inspection and checking of clearance, insulation resistance measurement, high voltage test with 2.5 KV for one minute, Milli volt drop test for all joints,and test report for all test to be submitted all as specified and directed by Engr-in-charge.
M&L for maintenace/testing of RTCC panel, PLC panelVRV LT panel, PAC LT panel, MDB panel,by isolating, disconnecting of input/output , supply cable, detecting of fault, ,u/s component in panel ,cleaning of serviceable parts/ component ,including replacement of worn out auto/manual switches LED indicator, cost of spare parts all as specified and directed by Engr-in-Charge. (repacement of spare parts not to be paid separately .
M&L for earthling complete with galvanised iron earth plate electrode of the size 600 mm x 600 mm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip 32 x 6 mm by means of bolts ,nuts.chuck nuts and washers of galvanised iron or .steel watering pipe of 20 mm bore , galvanised iron medium grade of 40 mm bore galvanised iron light grade of earth wire protection including all excavation earth work in any type of soil ,PCC pit with RCC pit cover , charcoal,salt,funnel complete all as shown in electrical plate No-3 of SSR Part-I & Testing on completion. Note: Quoted rates shall be including for earth strip with protection pipe upto 7.5 mtr length.
M & L for GI earth strip of size 32 x 6 mm laying in trench, fix to pole with necessary clamp and nut, bolt etc including taking out of unsv earth wire.
Excavation in trenches not exceeding 1.5 mtr and n.exc 1.5 mtr depth in any type of soil.
S & F Bricks sub class ‘B’ old size having compressive strength 75 Kg /Sq cm laid in trenches for cable protection complete all as specified and directed.
Returning filling in including spreading, levelling watering and well ramming in layers n.exc 25cm thick with available and approved soil/earth complete all as directed
Removal of excavated material to a distance n exc 50 mtr and depositing where directed at a level n.exc 1.5m above the starting point.
Supply, laying, jointing and commissioning in replacement of HT cable XLPE insulated PVC bedded GI strip or wire armoured electric power cable heavey duty with aluminium multi stranded conductor 11 KV grade of size 300 Sqmm 3 core laid in trenches /duct passing through pipe/ duct fixed in pole and connecting and testing complete.
Supply, jointing and testing, Outdoor type, Heat shrinkable end termination cable joint including all material and accessories suitable for 3 core 300 Sqmm XLPE cable of 11KV (E) grade complete all as specified and directed. Note : Cost of cutting of existing end termination joint deemed to be included in unit rate.
Supply, jointing and testing, Outdoor type, Straight through cable joint Heat shrinkable including all material and accessories suitable for 3 core X 300 Sqmm XLPE cable of 11000 volts (E) grade complete all as specified and directed. Note : Cost of Prepration of existing end deemed to be included in unit rate.
Supply, laying, jointing and testing XLPE insulated, PVC outer sheathed, galvanised steel strips armoured, heavy duty power cable with aluminium conductor suitable for rated voltage of 1100 Volts grade earthed system and conforming to IS : 7098 of 1995 and of size 3.5 core X 300 Sqmm and laid in trenches/ducts/pipe or on poles complete all as specified and directed.
Same as item No 36.00 but size 3.5 core X 150 sqmm
Same as item No 36.00 but size 3.5 core X 50 sqmm
Same as item No 36.00 but size 3.5 core X 25sqmm
Same as item No 36.00 but size 4 core X 16 sqmm
Same as item No 36.00 but size 4 core X 10 sqmm
Supply, jointing and testing,Outdoor type, straight through, heat shrinkable joint kit suitable for PVC/ XLPE insulated heavy duty armoured with aluminium multi stranded conductor 1100 volt grade of size 16 sq mm 4 core and including taking out from faulty portion in any situation /position complete all as specified and directed.
All as serial item No- 42.00 here in before but of size 25 to 35 Sqmm 3.5 core.
All as serial item No- 42.00 here in before but of size 50 to 95 Sqmm 3.5 core.
All as serial item No- 42.00 here in before but of size 120 to 150 Sqmm 3.5 core.
All as serial item No- 42.00 here in before but of size 300 to 400 Sqmm 3.5 core.
Arranging fault locating machine to pin point the fault in any size of HT/LT under ground cable in any situation , taking out the fault portion of HT/LT Cable of any length from trench , jointing with cable jointing kit and testing for satisfactory serviceability of the HT/LT cable in trench after jointing . Including excavation and earth work in any type of soil complete all as specified and directed. Cable jointing kit shall be measured sepereatly under respective item of Sch 'A'. Retrived old servicable bricks /cable cover willbe relaid in trenches on the cable
S & F Frequeny meter flush type 3 phase 415 volts AC including removing old meter. . Make: AE/AEE/Enercon.
S & F Volt meter of 0-500 Volt, 415 Volt Ac connecting testing including removing of unserviceable meter.Make : AE/AEE/ Enercon/ RE
S & F Ammeter 0 -3000 A with CT Coil,415 Volt Ac connecting testing including removing of unserviceable meter.Make : AE/AEE/ Enercon/ RE
Disconnecting the existing unservicable /burnt MCCB from the LT panel /stand by DG set panel & Supply & fixing new MCCB ,3 pole ,630 Amp(DN3-630N),50 KA,415 volt,50 Hz, 3 phase,Ics=100% of Icu with thermal magenatic release,installation of MCCB and connecting with existing cable including nut,bolt and washer etc complete.Make: L&T/Havelles/Standard
All as serial item No 51.00 here in before but of size 400 Amp(DN3-400 N).
All as serial item No 51.00 here in before but of size 200 Amp, 36 KA
All as serial item No 51.00 here in before but of size 160 Amp, 25 KA.
All as serial item No 51.00 here in before but of size 63 Amp, 25 KA .
All as serial item No 51.00 here in before but of size 100 Amp,25 KA,4 pole.
S & F in replacement of MCB SP 10 Amp, 10KA, 'C' series.
S & F in replacement of MCB TP 63 Amp, 10KA, 'C' series
S & F in replacement of MCB TP 32-40 Amp, 10KA, 'C' series
S & F in replacement of MCB DP 63 Amp, 10KA, 'C' series
Disconnecting the existing unservicable /burnt ATS from the PAC panel & Supply & fixing new ATS ,400 Amp, 3/4 pole ,415 volt,50 Hz, 3 phase with automatic /manual with inbuilt time delay and connecting with existing cable including nut,bolt and washer etc complete.Make:Socomec/Standard
Supply and fixing in replacement of new generation energy saving& enviroment friendly with die cast aluminium spigot, spun aluminium powder coated top cover, aluminium PDC heat sink, opal PC diffuserand clear acrylic LED Post top Lantern of wattage 70 Watts of IP65,class I protection integral driver operation at 170-270VAC 50Hz supply including , brackets for fixing on the pole/buildings/walls complete by removing the old unserviceable light fittings and making connection from existing electric net work system complete all as specified and directed. Make:Halonix cat No. HLPT-04- 70-CW LED or equivalent in Philips/Bajaj, Crompton.
Supply and fixing in replacement of new generation energy saving& enviroment friendly higly efficient LED street light made of pressure die cast aluminium housing with high power LEDs lens & toughened glass of wattage 45 Watts of IP66,class I protection integral driver operation at 170-270VAC 50Hz supply including , brackets for fixing on the pole/buildings/walls complete by removing the old unserviceable light fittings and making connection from existing electric net work system complete all as specified and directed. Make:Halonix cat No. HLSLD-10-45-WWL-I LED or equivalent in Philips/Bajaj, Crompton.
M&L for painting on MS Tabulor pole of length 6ft-8ft -30 Nos garden light fitting, street light pole- 4 Nos including GI pipe /brackets fixed on pole, by applying alluminum two coats of aluminum paint after cleaning the surface properly with sand paper, making strip with synthetic enamel paint with yellow/black/white colour as directed complete of all as directed by Engineer-in charge.
Supply and fix sand in trenches including spreading & levelling for cushioning of LT/HT UG cable complete all as specified and directed.
Supply and laying of PCC cable cover class HV type-1, with flat of size 300mm x 180mm x 40mm complete all as specified and directed.
S&F following parts of PCC 3.3 digital panel of 750 KVA DG Set (Make : Cummins)
PCC 3.3 control card (Cat part No. A054J968)
Display control (Cat part No. 0300-6315-02)
AVR Aux card (Cat part No. A028T766)
PCB assy Governor card (Cat part No. 0327-1507)
Net Contract Sum will be after deducting Sch of Credit of Rs 72,917.00
J B Electricals
D P ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .