Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹3,000
Closing Date
25 Mar 2022, 11:15 amClosed
EE EnM M-6
DELHI JAL BOARD MU BLOCK PITAMPURA DELHI-34
Internal and External Electrification of QU Block BPS
2022_DJB_219003_25
NIT NO.6 (M-6)
Open Tender
Miscellaneous Works
Item Rate
15 days
EE EnM M-6
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Account No 50448339804
₹3,000
Yes
28 Apr 2022
16 Mar 2022
25 Mar 2022
16 Mar 2022
25 Mar 2022
16 Mar 2022
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel. SOR 31.15
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required. SOR 31.31
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. SOR 31.32
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. SOR 31.12
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. SOR 31.44
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required. SOR 31.41
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire. Make : - Havells / Gloster / Grandley / Approved By DJB SOR 31.14.2
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required, Single pole, make L&T / Havells / C&S / Approved by DJB SOR 32.10.1
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (2 + 16), Double door. SOR 32.3.4
Supply of PVC/XLPE insulated(HEAVY DUTY), electrical cable for working voltage up to and including 1100vpolts to IS :1554(part-I) 1988/7088/7098(part-I) 1988 with Copper conductor, Armoured of 2X10 Sq MM Make: - Gloster, Grandlay, Havels, Polycab SOR 18.9.5
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. SOR 35.1.4
S/o ceiling fan, 1200 mm sweep make: Havells / Crompton SOR 20.1.1
New generation energy saving and environmental friendly long life LED street light made up of pressure die cast aluminum housing with high efficient LED as lighting source and PC cover having TOP Opening separate driver compartment with IP66 protection and impact resistance of IK07.. 45 watt Make: Bajaj / Havells / Philips / Approved by DJB SOR 19.10.5
RISHABH ENGINEERS
HARI ELECTRICAL CO.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .