| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAccepted-AOC PI NO 13 S NO 81 82 BEHIND 132 33 KVA MSEB SUBSTATION MIDC AREA AMBAD NASHIK 422 010 | NASHIK | NASHIK | MAHARASHTRA | 422010 | ₹1.2 Cr Quoted ₹1.4 Cr | L1 | Accepted-AOC Lowest bid |
| 2 | L2₹1.4 Cr+₹3.9 L (2.91%)Rejected-Finance 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | ₹1.4 Cr+₹3.9 L (2.91%) | L2 | Rejected-Finance REJECTED BEING OTHER THAN L1 |
| 3 | L3₹1.4 Cr+₹7.8 L (5.73%)Rejected-Finance SHOP NO 259 LOHOGAON ROAD KALWAD KHANDVE NAGAR PUNE 411032 | PUNE | MAHARASHTRA | 411032 | ₹1.4 Cr+₹7.8 L (5.73%) | L3 | Rejected-Finance REJECTED BEING OTHER THAN L1 |
| 4 | L4₹1.6 Cr+₹23.7 L (17.5%)Rejected-Finance 9 EZRA STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | ₹1.6 Cr+₹23.7 L (17.5%) | L4 | Rejected-Finance REJECTED BEING OTHER THAN L1 |
Tender Value
₹1.2 Cr
EMD Value
₹1.9 L
Closing Date
8 Jul 2023, 6:00 pmClosed
COL VIKAS KESARWANI
CWE (AF) LOHEGAON, PUNE - 411032
UPGRADATION OF ELECTRIC NETWORK IN DOMESTIC AREA AT AIRFORCE STATION PUNE (PH-I) UNDER GE (AF) LOHEGAON
2023_MES_601253_1
81876/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
GE (AF) LOHEGAON
As per NIT
6 documents required · 6 mandatory
₹500
Yes
GE (AF) LOHEGAON
₹1.9 L
Yes
31 Aug 2023
5 Jun 2023
15 Jul 2023
5 Jun 2023
8 Jul 2023
26 Jun 2023
Amount
Supply and Installation of 22 KV, 630 Amps/3 Sec, 3 Way outdoor, Extensible motorized SCADA compatibile RMU as per MSEDCL RAPDRP specification consisting of 2 Nos feeder with motorized Load Break Switch and 1 No feeder with motorized VCB including connection testing and commissioning complete all as specified and directed confirming to following specifications.
Incomer feeder Shall confirm to following specification: 1. Motorized 630A load breaker switch with built-in earth switch with full making capacity - 2 No. 2. Mechanical position indicator. Switch ON/OFF/EARTHED -2 No. 3. Live Cable Indication. - 2 No. 4. Cable compartment cover interlocked with earth switch. -2 No. 5. Cable termination bushings suitable for 1 no. 3CX300mm2 XLPE cable - 2 Set. 6. 22kV touch proof Cable termination kit with boots - 2 Set. 7. NO/NC contact for: - 2 set Isolator ON/OFF Earth Switch ON/OFF Fault Indicator Operated 8. Command Output for: - 2 set Isolator Close Isolator Open FPI reset Outgoing VCB feeder consists of: 1. Motorized 630A Vacuum Circuit Breaker with motorized spring charging arrangement and manual close & open push buttons, ON /OFF indication and series trip coil for self-powered relay & shunt trip coil for external tripping - 01 No
2. Self-powered Numerical O/C & E/F relay type CSDPR with CTs of ratio 100-50/1A, 2.5VA, 5P10 for 100/1 and 10P10 for 50/1(Protection core) & 100-50/1A, 2.5VA, Cl 0.5 for 100/1 and Cl 1for 50/1 (Metering core) - 1 Set 3. Manually operated 630A load breaker switch with built-in earth switch with full making capacity - 1 No. 4. Mechanical position indicator. Switch ON/OFF/EARTHED - 1 No. 5. Live Cable Indication. 1 No. 6. Cable compartment cover interlocked with earth switch. 1 No. 7. Cable termination bushings suitable for 1no. 3CX300mm2 XLPE cable - 1 Set. 8. 22kV Screened touch proof Cable termination kit with boots - 1 Set. 9. NO/NC contact for: - 1 Set. Breaker ON/OFF Relay operated. 1No. Metering Module as Bus PT (i) 1 Set of 03nos. Single Phase Potential Transformers having ratio 22kV/rt3:110V/rt3, 50VA, Class 0. (ii) 1 Provision for installation of Multifunction Meters for energy reading in breaker functions.
Common Items per RMU SF6 Gas Pressure indicator with auxiliary contacts. 1 No. Handles for RMU 2 Nos. FPI. Battery&BatteryCharger. (i) PCC for foundation and paltform including excevation, PCC block Mansonary , mooram filling, plastring, compaction of mooram/earth is deemed to be inclusive of the quoted rate, Modification suggested by MSEDCL Note: (i) The RMU shall be got inspected and tested at site by the SEI and the records of the testing shall be signed by the rep of A.O., GE, Engr-in-Charge and the contractor. (ii) Factory inspection of RMU shall be carried out by rep of accepting officer, contractor shall give 45 days notice period for the same (iii) Contractor shall submit detailed specification, line diagram and layout diagram for approval of Accepting Officer (iv) The contractor shall arrange all T&P required for testing / inspection of RMU and cost of the same is deemed to be inclusive in quoted rates.
S&F in repairs cable end joint 300 Sqmm 3 core XLPE 22 kV HT Cable heat shrinkable indoor type complete all as specified and directed
S & F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 Core XLPE armoured Al conductor cable of size 120 sqmm complete all as specified and directed
S & F Cable jointing kit for 11 KV (Earthed) grade cable for in- door termination heat shrink type joint complete with jointing material & accessories suitable for 3 Core XLPE armoured Al conductor cable of size 120 sqmm complete all as specified and directed
Supply, installing, commissioning and testing of outdoor type, HT 11 KV, 3 phase 50 cycles, oil immersed, naturally air cooled, core type. LT, 433 volts, step down, copper wound 630 KVA capacity transformer in accordance with vector group Dyn ll with neutral brought out on LV side as per IS 1180, including all fittings and consisting of the following acessories complete all as specified and directed:- a) Rating plate and terminal marking plate. b) Two earthing terminlas for body earthing and two additional for neutral brought out on a bushing. c) Lifting lugs. d) Drain valve with plug or cover plate. e) Dehydrating breather. f) Oil level indicator with minimum and maximum Marking. g) Cooling Radiator. h) Thermometer pocket. j) Conservator k) Oil filling hole with cover. l) Air release device with conservators. m) Filter valves n) Rollers as per manufacturer's design. o) Thermometer dial type.
p) First fill of transformer oil q) Explosion vent. r) LV Cable terminating box. s) LV neutral bushing brought outside for direct earthing. t) HT bushing u) Manual Tap Changer with tapping on HT side t) Any other fittings as recommended by the manufacturer and as directed by the GE.
Note: (i) Brickwork and PCC for foundation and platform of size (3mtr x 3mtr x 1mtr) including excavation, PCC block Mansonary , moorum filling, plastering, compaction of mooram/earth is deemed to be inclusive of the quoted rate, (ii) The Transformer shall be got inspected and tested at site by the SEI and the records of the testing shall be signed by the rep of A.O., GE, Engr-in-Charge and the contractor. (iii) All the arrangements and testing equipments etc, for testing as per note above shall be provided by the contractor and cost of the same shall be deemed to be included in the contractor's quoted rates. (iv) Factory inspection of transformers shall be carried out by rep of Accepting Officer, contractor shall be given 45 days for the same. (v) Contractor shall submit detailed specifications, diagram for approval of Accepting Officer.
S & F Steel tubular swaged poles complete with cast iron plate, finial taper plug, bolt, nuts & screws as specified type 410 SP-55 (11 mtr long) including one coat of red oxide primer and two coats of aluminium paint and making 30 cm wide strips (total -05 Nos) with yellow and black paint alternately on external surface above column/PCC benching including numbering with black paint and painting with bitumenou paint internally and externally for portion embedded in PCC complete all as specified and directed.
S & F Air break gang operated switch with 12 Nos insulators outdoor type, triple pole, mechanically operated, suitable for vertical installation, single break, provided with locking arrangement consisting of MS chanel HT post type insulator copper alloy, high pressure assembly drop out fuses operating rod of 20 mm dia GI pipe (medium grade) for operating from 1.2 m above GL complete including drop out fuses conforming to IS-9921 Part-I to V (1982 to 1985) of 1972 rated voltage 11 KV and for current rating 200 Amp complete all as specified and directed
S & F Lighting arrestor (set of three) HT metal oxide surge arrestor polymetic type complete with all fittings rated voltage 12 KV continuous operating voltage. 11 KV, normal discharge current 10 KA max residual voltage at 8/20 impalse 75 KV etc complete all specified and confirming to IEC-600994-2001.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e M.S. channel or angle sections etc. including new nuts, bolts, washers as reqd dia/length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of aluminium paint (1st quality ) as required complete all as specified and directed
S & F APFC Panel of 200 KVAR capacity outdoor type with canopy protection class IP-55 double door, dust and vermin proof made out of 3.15mm thick CRCA sheet of CPRI approved make, mounting on suitable size foundation with 150 mm thick PCC (1:3:6) type C2 with 100 mm offsets, opening and locking arrangement compete including two coat of finishing powder coated paint of approved shade over one coat of red oxide primer including MS Angle iron 50mm x 50mm x 6mm frame suitable including the following accessories:-
M & L For Dismantling from insulators and taking down copper conductor any size from LT over head lines complete all as specified and directed
M & L For Dismantling earth wire any size from eye hooks /insulators etc from HT/LT over head lines complete all as specified and directed
M & L For Dismantling insulator any type and any size from LT over head lines complete all as specified and directed
M & L For Dismantling, cross arms, clamps, supports made of channels or angle section etc including nuts and bolts and setting aside all as required at site complete all as specified and directed
M & L For Dismantling stay assy complete including excavation for taking out PCC block breaking of PCC block for taking out MS plate complete all as specified and directed
M & L For Taking Down of old UG Cable including taking down from wall/trenches etc complete all as specified and directed
Supplying laying & testing of XLPE cable insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminum conductor, 22000 volts grade, earthed system of size 3 core 300 sq mm complete all as specified and directed
Supplying laying & testing of XLPE cable insulated screened PVC bedded, galvanized steel strip armoured, electric power cables (heavy duty) with stranded aluminum conductor, 11000 volts grade, earthed system of size 3 core 120 sq mm complete all as specified and directed
Supply and laying in trenches or fixing to wall/pole or passing through pipe XLPE insulated, armoured heavy duty electric cable with multi stranded aluminium conductor 1100 volts grade cross sectional area 500 Sqmm 3.5 core all as directed including lugs, cable glands, LT heat shrinkable end termination kit of suitable size at cable connection ends, nut bolts etc all as directed by engineer in charge
Ditto all as per srl item No 19.00 above but cable of size 400 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 240 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 185 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 120 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 95 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 70 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 50 Sqmm 3.5 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 16 Sqmm 4 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 10 Sqmm 4 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 6 Sqmm 4 core complete all as specified and directed
Ditto all as per srl item No 19.00 above but cable of size 6 Sqmm 2 core complete all as specified and directed
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in soft/loose soil etc complete all as specified and directed by Engr-in-Charge.
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole in soft disintegrated rock complete all as specified and directed by Engr-in-Charge. Note - Excavation shall be done manually by deploying manpower
Ditto all as per Ser Item No 33.00 above but depth exc 1.5 mtr but not exc 3.00 mtr complete all as specified and directed
Returning, filling in, including spreading, leveling watering, and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed by Engr-in-Charge.
Removing excavated material n.exc 50m and depositing where directed at a level exc. 1.5 cm above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for crushed stone sand cushioning to UG cable, provide with the layer 8 cm before and 15 cm after laying and punning down and testing the cable complete all as specified and directed by Engr-in-Charge. Note :- Thickness of sand after punning will be measured and paid.
Supplying and laying ISI Marked un-reinforced precast concrete cable cover, HV, Type 1, flat, size 300mmx 180mm x 40mm complete all as specified and directed
Supplying and laying un-reinforced ISI marked precast concrete cable cover, class I, flat, size 250mm x 150mm x 40mm for LT cable protection complete all as specified and directed
M&L for PCC 1:2:4 type B-1 using 20 mm graded stone agrregates as in pedestal of pole/ strut and in copping including necessary form work and finishing exposed faces of concrete even and smooth using extra cement all as directed by engineer in charge .
M & L for PCC 1:4:8 type D2 using 40mm graded stone agreegates for foundation of stay assembly , pole , struts etc all as directed by engineer in charge.
Supply install, test and commissioning LT Feeder Pillar / Panel board cubical type outdoor, free floor standing factory fabricated made out of 3 mm thick CRCA sheet & suitable size to accomodate all accessories/fittings, compartmentalized in construction to accommodate incoming and outgoing MCCB, MCB and TPN aluminium bus bars of rating not less 1.5 times the rated cap of incomer MCCB / ACB. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator. The incoming as well as outgoing MCCBs shall have copper extension links of current carrying cap not less than 1.5 times the rated capacity of individual feeders alongwith aluminium bus bar on incoming and outgoing end for MCCB rating 63 Amps and above. The cubicle shall have a detachable bottom stand made out of equal angle 50mmx50 mmX6mm . A detachable predrilled gland plateof thickness not less than 3 mm thick should be used at the bottom for entry of armoured cable of adequate size with glands.The above panel shall be front and back openable lockable /openable by key from both side, The Panel shal be manucatured from CPRI approved manufacturerof makes stipulated. The cost is inclusive of taking down of existing panel, disconnecting existing cables, reconnecting the cables with lugs & glands, Excavation, PCC Foundation complete all as specified and directed
(i) Main Incoming Manual spring charging Draw out type ACB of Rating 1000 Amps Four Pole 50 kA without releae , Manual Drawout - 01 No (ii) Outgoing MCCB FP 415 Volt 315 Amps 36 kA - 01 Nos (iii) Outgoing MCCB FP 415 Volt 250 Amps 36 kA - 01 Nos (iv) Outgoing MCCB FP 415 Volt 200 Amps 36 kA - 01 Nos (v) Outgoing MCCB FP 415 Volt 160 Amps 36 kA - 02 Nos (vi) Outgoing MCCB FP 415 Volt 125 Amps 36 kA - 01 Nos (vii) Outgoing MCCB FP 415 Volt 100 Amps 36 kA - 01 Nos (viii) Outgoing MCB TP 415 Volt 40 Amps 16 kA - 01 Nos (ix) Street light timer switch up to 16 Amp single phase with astonomical on off in sheet poly carbonate/MS sheet enclosure (x) LED Type RYB Phase Indicator -01 Set (xi) Digital VAFPF Meter -01 Nos (xii) CTs - 01 Set (xiii) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Main Incoming manual spring charging draw out type ACB of Rating 800 Amps Four Pole 50 kA without releae , Manual Drawout - 01 No (ii) Outgoing MCCB FP 415 Volt 500 Amps 36 kA - 01 Nos (iii) Outgoing MCCB FP 415 Volt 400 Amps 36 kA - 01 Nos (iv) Outgoing MCCB FP 415 Volt 250 Amps 36 kA - 01 Nos (v) Outgoing MCCB FP 415 Volt 100 Amps 25 kA - 02 Nos (vi) LED Type RYB Phase Indicator -01 Set (vii) Digital VAFPF Meter -01 Nos (viii) CTs - 01 Set (ix) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 160 Amps 25 kA - 01 Nos (ii) Outgoing MCCB TP 415 Volt 63 Amps 16 kA - 04 Nos (iii) TPN Aluminum bus bar with colour code 200 Amps (iv) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 125 Amps 25 kA - 01 Nos (ii) Outgoing MCCB TP 415 Volt 63 Amps 16 kA - 03 Nos (iii) TPN Aluminum bus bar with colour code 200 Amps (iv) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 100 Amps 25 kA - 01 Nos (ii) Outgoing MCCB TP 415 Volt 63 Amps 16 kA - 02 Nos (iii) TPN Aluminum bus bar with colour code 200 Amps (iv) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 125 Amps 25 kA - 01 Nos (ii) Outgoing MCB TP 415 Volt 40 Amps 10 kA - 02 Nos (iii) TPN Aluminum bus bar with colour code 200 Amps (iv) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 160 Amps 25 kA - 01 Nos (ii) Outgoing MCCB TP 415 Volt 63 Amps 16 kA - 02 Nos (iii) Outgoing MCB TP 415 Volt 40 Amps 16 kA - 03 Nos (iv) TPN Aluminum bus bar with colour code 200 Amps (v) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
Ditto all as per ser item No 42.00 above and comprising the following :- (i) Incoming MCCB FP 415 Volt 200 Amps 25 kA - 01 Nos (ii) Outgoing MCCB TP 415 Volt 100 Amps 16 kA - 02 Nos (iii) TPN Aluminum bus bar with colour code 200 Amps (iv) The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
M&L earthing complete with galvanised steel earth plate eletrode 60 cm x 60 cm and 6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top prjgc, of the plate not less than 1.5m below normal ground level, connected to the Galvanised Iron earth lead 32 mm x 6 mm (GI Strip) size, by means of bolts, nuts, check buts and washers of galvanised iron and 32 mm x 6 mm earth lead protected by provision of GI medium grade pipe 40 mm bore including provision of aggregates with 40 mm thick cover of RCC (1:2:4) , reinforced with XPM (weight not less than 4 kg per sqmm) and frame of angle iron 40mmx40mmx3mm and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe of suitable length for watering perforated at bottom placed on top edged of earth plate, common salt and charcoal filling, funnel, wire mesh and earth work in hard/dense soil, returning filling in distance not exceeding 50 mtr and removal of surplas soil to plate No 3 of SSR 2009 Part-I and connecting to feeder pillers and Transformer all as specified including testing on completion complete all as specified and directed.
M&L earthing complete with copper earth plate eletrode 60 cm x 60 cm and 3.15 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top prjgc, of the plate not less than 1.5m below normal ground level, connected to the copper lead 20 mm x 3 mm size, by means of bolts, nuts, check buts and washers, earth lead protected by provision of GI medium grade pipe 40 mm bore including provision of aggregates with 40 mm thick cover of RCC (1:2:4) , reinforced with XPM (weight not less than 4 kg per sqmm) and frame of angle iron 40mmx40mmx3mm and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe of suitable length for watering perforated at bottom placed on top edged of earth plate, common salt and charcoal filling, funnel, wire mesh and earth work in hard/dense soil, returning filling in distance not exceeding 50 mtr and removal of surplas soil to plate No 3 of SSR 2009 Part-I and connecting to feeder pillers and Transformer all as specified including testing on completion complete all as specified and directed.
M&L earthing complete with galvanised steel earth plate eletrode 60 cm x 60 cm and 6mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top prjgc, of the plate not less than 1.5m below normal ground level, connected to the Galvanise Iron earth wire 4.0 mm, by means of bolts, nuts, check buts and washers of galvanised iron and 4.00 mm earth lead protected by provision of GI medium grade pipe 25 mm bore including provision of aggregates with 40 mm thick cover of RCC (1:2:4) , reinforced with XPM (weight not less than 4 kg per sqmm) and frame of angle iron 40mmx40mmx3mm and with 6 mm dia MS bar handle made to shape, GI light grade 20mm bore pipe of suitable length for watering perforated at bottom placed on top edged of earth plate, common salt and charcoal filling, funnel, wire mesh and earth work in hard/dense soil, returning filling in distance not exceeding 50 mtr and removal of surplas soil to plate No 3 of SSR 2009 Part-I and connecting to DB & Poles all as specified including testing on completion complete all as specified and directed.
S & F cable route marker of size 100 mm x 100 mm x 5 mm thick GI plate with insertion there on bolted welded to 35 mm x 35 mm x 6 mm angle iron 60 cm long and frounting the sae in ground with PCC as required for LT calbe incl necessery earth work complete all as specified and directed.
M & L for LT Cable junction box shall be made out of Polycarbonate with glass fiber reinforced and size should be not less than 255 mm x 355 mm x 122 mm suitable for Cable Size 16 to 50 sqmm. The Junction Box shall be rated for Protection IP 65 including one No. 4 pole connector and 2 Nos 06 Amp MCB, clamps and nut bolts complete all as per manufacturer’s instructions
Ditto all as per Ser item No 54.00 above but size should be not less than 255 mm x 295 mm x 122 mm(Cable Size 16 to 35 sqmm) complete all as specified and directed.
Ditto all as per ser item No 54.00 above but size should be not less than 130 mm x 180 mm x 77 mm(Cable Size 2.5 to 6 sqmm) complete all as specified and directed.
Material and labour for brick work with sub class 'B' bricks, straight or curved on plan exc or curved on plan exc 6 m radius built in cement mortar 1:4 in two pole /4 pole electrical substation area complete all as specified and directed.
Material and labour for cement plaster work 10 mm thick in 1:4 rendering on fair faces on brick work or concrete surfaces including 5 mm thick finishing to be carried out one even and smooth surfaces including 5 mm thick finishing to be carried out one even and smooth surface (without using extra lime or cement)
Fixing only chain link fencing including line wires any mesh size and type of standards, rails, straining bolts, etc including provision of binding wire complete all as specified and directed by Engr-in-Charge
Supply only chain link MS galvanised fencing any size of type 2.10 meter high complete all as specified and directd by Engr-in - charge
Supply and fix angle iron as in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, painting by applying two coat of red oxide primer, two coat of enamel paint etc., and similar work conforming to Fe-290 Gde E-165
M & L for Coarse aggregates (Granite, Trap or Basalt), grading l, grading 3, 50 to 20 mm size around Transformer/2 Pole structure) complete all as specified and directed.
Material and labour for Pre-cast cement concrete block masonry with solid blocks,Type B1 1:2:4 20 mm graded aggregrate exc. 10 cm in width and setting in mortar complete all as specified and directed.
Material and labour for broken stone of boulders hardcore of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rammed to a true surface complete all as specified and directed.
M&L for cement concrete (1:4:8) type D2 in foundation filling and mass concrete using 40mm graded stone aggregate for pole/stay foundation etc complete all as specified and directed.
M&L for cement concrete (1:2:4) type B2 in foundation filling and mass concrete using 40mm graded stone agg for pole/stay foundation etc complete all as specified and directed.
Supply and fix distribution board iron clad, double door with IP-43 1K-09 protection suitable for MCCB as incomer and MCB as outgoing 415 Volts 3 phase 50 C/s 4 way, complete with appropriate size copper bus bar and neutral link, including one MCCB 3 pole 415 Volts 63 Amps rating with rupturing cap 16 KA, size making connection with thimbles & including fixing DB on wall and making good the disturbed wall surface all as required at site complete all as specified and directed. Note : The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
S & F MCB Single Pole 40 Amps, 230 Volts including connecting up complete all as specified and directed.
M & L for Disconnect the existing cable of Bldg from LT pole and connect the same in new Feeder Pillar Box incl replacing of Lugs, Cable glands, Nut, Bolt, Washers, including Ecxavation, Returning filiing, Removal etc. complete all as specified and directed.
Supply and fixing copper cable multistrand PVC insulated PVC seathead 1.5 Sqmm 3 core for street light connection, including PVC conduit along with GI clamps, nut bolts etc from Pole junction box complete all as specified and directed.
M & L for GI steel tubing light grade of size 100 mm dia as cable protection across road/along wall/pole etc complete all as specified and directed.
M & L for GI steel tubing light grade of size 80 mm dia as cable protection across road/along wall/pole etc complete all as specified and directed.
M & L for GI steel tubing light grade of size 50 mm dia as cable protection across road/along wall/pole etc complete all as specified and directed.
M & L for GI steel tubing light grade of size 40 mm dia as cable protection across road/along wall/pole etc complete all as specified and directed.
M & L for cutting existing road to depth up to 60 Cm for laying of pipe/cables etc and refilling, making good the road by PCC 1:2:4 watering, curing, well ramming complete all as specified and directed.
Supply and installation, connecting eclectically & commissioning of LT feeder pillar box outdoor type of size 0.90 x 0.60 x 0.50 Mtr size factory fabricated made out of MS sheet of thickness 3.00 mm front door openable with locking arrangement mounted on angle iron legs made out of angle iron of size 40x40x6mm, 1.5 mtr long, 1.0 mtr above ground level and 0.50 mtr embedded in PCC blocks of size 0.30x0.30x0.50 mtr- 04 Nos duly painted with two coats of synthetic enamel paint over a coat of red oxide complete with 400 amps rated aluminium bus bar suitable for 3 phase 4 wire supply system duly drilled holes and making all cable connection with proper thimbles mounted on epoxy based post insulators complete all as required at site. Note : The layout diagram alongwith rating of busbar and switchgear of the panel shall be submitted by the contractor and shall be got approved by GE.
sapana enterprises
Rama Electricals
Prasur Electricals & Engineering Co.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .