Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹75.0 LAdmitted-Finance | L1 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s MANISH ENTERPRISES L1 |
|---|---|---|---|---|
| 1.00Solar Power Plants | ||||
| 2.00SITC of Grid interactive Solar Photovoltaic Power Plant of required capacity having specifications as per A, B, C, D, E, F and G | ||||
| 3.00A. Solar Photovoltaic module : MNRE approved and ALMM listed, SPV module of capacity 580 Wp or above, Anodized Aluminium Alloy Framed Topcon N- type Bifacial, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. , 2 mm Low Iron ARC semi-tempered glass, IP-68 PPL Junction box, 4.0 sq.mm cable with MC4 solar connector, conversion efficiency shall not be less than 21.0 % on STC, performance warranty for their output peak watt capacity > 90 % at the end of 10 years and > 80% at the end of 25 years. | ||||
| 4.00B. Inverter / PCU : MPPT integrated, IGBT/MOSFET based and microprocessor/ DSP controlled Power Conditioning Unit (PCU) of AC nominal power output rating equal or greater than the required KWp of the module in IP-65 Enclosure, of 250-1500 V DC Input voltage range and 400 V AC, TPN, 50Hz +/- 2.5 Hz, Efficiency > 97%, THD < 3%, Overloading capacity > / = 10%, remote monitoring facility and PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. | ||||
| 5.00C. Module mounting structure : MMS Steel shall be as per latest IS 2062:2011 and galvanization of the mounting structure shall be in compliance of latest IS 4759, All bolts, nuts, fasteners shall be hot dip galvanized, MMS shall be designed and installed to withstand the speed for the wind zone of the location with factor of safety >1.5, STAAD report of structure to be submitted | ||||
| 6.00D. Array Junction Box / DCDB : IP 65 AJB / Enclosure mounted on MMS with Polyamide glands and MC4 Connectors and cable ferrules for identification. DC fuses with SPD type-II/MOV type surge arrester to be provided. | ||||
| 7.00E. ACDB : IP 65 ACDB / Enclosure mounted on MMS with Polyamide glands and MC4 Connectors and cable ferrules for identification. MCB/MCCB with SPD type-II/MOV type surge arrester to be provided. | ||||
| 8.00F. Earthing and Lightning protection: The entire space occupying the SPV array shall be suitably protected against Lightning by deploying required number of Lightning Arrestors (LAs). as per NFC17-102:2011/IEC 62305 standard and three no. of Earthing with suitable size earth conductor | ||||
| 9.00G. Solar meter and Cable : Laying of array cables to PCU/ DCDB unit along with supplying & fixing of necessary GI raceways/MS conduit lugs and suitable size aluminium armoured cable from ACDB to Electrical panel (up to 50 Mtr.) Discom approved solar meter (Direct or CT operated) with suitable size IP65 enclosure or MIP Box with CT | ||||
| 10.00 | 20 KWp | 1 | Set | 10,40,000 ₹10,40,000 Lowest |
Tender Value
₹76.9 L
EMD Value
₹1.5 L
Closing Date
20 Aug 2026, 6:00 pmClosed
Executive Engineer Medical and Health Div Churu
Executive Engineer Medical and Health Div Churu
SITC of 20 KWp Solar Power System, Air conditioning and external electrical work DG Set, FFW and FDW and other miss work in construction of new CHC building at Tibbi, Distt. Hanumangarh S No.7
2026_MEDIC_589393_1
NIT 07/2026-27 EE MH Churu
Open Tender
Electrical Works
Percentage
90 days
Hanumangarh
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
Executive Engineer Medical and Health Div Churu
₹1.5 L
22 Sept 2026
17 Aug 2026
21 Aug 2026
17 Aug 2026
20 Aug 2026
17 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Fire Detection System | - | - | - | - |
| 2 | SITC of UL 10th edition / EN54 / VDS certified Automatic Floating Sensitivity type Analog addressable Multi criteria (two optical/Smoke sensor to reduce false alarm) detector with mounting base & LED etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 130 | Each | 3,104 | ₹4,03,520 |
| 3 | SITC of UL 10th edition / EN54 / VDS certified Addessable Manual Call point (MCP) with LED / FIRE Indication Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 10 | Each | 3,509 | ₹35,090 |
| 4 | SITC of UL 10th edition / EN54 / VDS certified Addressable sounder with strobe light, Loop Powered / Direct powered from FACP with sound level 90 dB and programmable from the panel etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | 10 | Each | 8,128 | ₹81,280 |
| 5 | SITC of UL 10th edition / EN54 / VDS certified Microprocessor based inteligent, Analogue addressable,modular, expandable networkable loop Fire Alarm Control Panel with each loop capacity of min 125 detectors per loop with total of 125 detectors & devices with Loop length up to 1 KM as per NFPA 72 approval. The Panel shall be able to give pin point location of addressable units via the address code for each unit. The Panel shall also be able to automatically switch off all control switches when-ever any Alarm is triggered. . The panel shall have 230 + 5 % volts power supply, Automatic battery charger 24V, sealed lead acid maintanence free battries sufficient for 24 hours normal working and then be capable of operating the system for 30 minutes during emergency condtion. Loop interface cards, communication module, LCD/LED unit to indicate Fire / Fault Signal of individual unit, inbuilt networking port(both RS485&Ethernet),Serial port for printer,two supervisory inputs,two position key switch and USB port for programming.including the cost of all accessories Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
| 6 | 2 - Loop Panel | 1 | Each | 2,96,858 | ₹2,96,858 |
| 7 | Add Extra for per Loop expansion beyond Two Loop | 2 | per Loop | 67,462 | ₹1,34,924 |
| 8 | Supplying and drawing Fire Resistant flexible / stranded bare copper conductor, PVC / XLPE insulated, overall aluminium mylar tape shielded ATC drain wire and outer PVC sheathed industrial Instrumentation (shielded)cables voltage grade 300/500 V as per BS /EN 50288-7 in existing surface or recessed PVC/ MS conduit/casing capping / Cable tray / Open Duct making connections, testing etc. as required. OEM Must have its own in house NABL lab setup for all testing facilities for cables. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
| 9 | 2 x 1.5 Sq.mm Unarmoured With Outer Sheath in Red Color | 2,270 | Mtr | 94 | ₹2,13,380 |
| 10 | SITC of PA system Operator Console of following wattage to be installed with Conventional fire alarm system complete with following capacity , channel mixing amplifier , 1 no cardioids goose neck microphone , 1 no professional grade cassette deck/ CD Player , 16 zone floor selector console , equipment rack complete in all respects. PA system shall be coupled to the Fire Alarm System. Etc. as required. All as per pre approved by Engineer in charge. For additional technical parameters of products/ work , refer Annexure "A" attached with this BSR . | - | - | - | - |
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 13.05 MB
Tendernotice_2.pdf
PDF • 30.02 MB
Tendernotice_3.pdf
PDF • 0.45 MB
Tendernotice_4.pdf
PDF • 22.59 MB
Tendernotice_5.pdf
PDF • 0.05 MB
Tendernotice_6.pdf
PDF • 0.11 MB
BOQ_1046697.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .