Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹9.4 LAccepted-AOC A 93 SECTOR 36 GREATER NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201308 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201308 | ₹9.4 L Quoted ₹9.6 L | 1 | Accepted-AOC Lowest bidder |
| 2 | 2₹11.0 L+₹1.5 L (15.3%)Rejected-AOC | ₹11.0 L+₹1.5 L (15.3%) | 2 | Rejected-AOC 2nd |
| 3 | 3₹12.1 L+₹2.6 L (26.8%)Rejected-AOC | ₹12.1 L+₹2.6 L (26.8%) | 3 | Rejected-AOC 3rd |
| 4 | 4₹13.6 L+₹4.1 L (42.6%)Rejected-AOC | ₹13.6 L+₹4.1 L (42.6%) | 4 | Rejected-AOC 4th |
| 5 | 5₹13.7 L+₹4.1 L (43.1%)Rejected-AOC | ₹13.7 L+₹4.1 L (43.1%) | 5 | Rejected-AOC 5th |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
1 Dec 2021, 6:00 pmClosed
GE AF TUGHLAKABAD
GE AF TUGHLAKABAD SANGAM VIHAR PO NEW DELHI 110080
ANNUAL MAINTENANCE CONTRACT (AMC) FOR EARTHING INFRASTRUCTURE AND MISC E/M REPAIR / REPLACEMENT OF OLD UNSERVICEABLE EARTHING, LA SYSTEM, EARTHING STRIP AND EARTH PIT AT 7BRD, AF UNDER GE (AF) TUGHLAKABAD
2021_MES_486228_1
GE/TKD/TOKEN-44/2021-22
Open Tender
Civil Works - Others
Item Rate
270 days
GE AF TUGHLAKABAD
MES contractor enlisted having deposited Standing Security with dept. Contractors not enlisted in MES should meet the MES enlistment criteria corresponding to appropriate class and category
8 documents required · 8 mandatory
₹500
GE AF TUGHLAKABAD
₹30,000
Yes
29 Mar 2022
3 Nov 2021
3 Dec 2021
10 Nov 2021
1 Dec 2021
17 Nov 2021
Amount
M&L for dismantling the strip from earth pit and testing of earth pit to be done as per fall of potential method mentioned in IS-3043 with digital earth resistance tester to check the healthiness of earthing system in and including replacement earth pit nut bolts with brass nut bolts as per required size and record should be kept on ledger duly signed by user representative, JE concerned and contractor and the same shall be submitted to Engr in charge for counter signature complete all as specified and directed by Engineer-in-Charge. Note: Testing of earth pit shall be done as and when required basis as directed by Engineer-in-Charge from time to time.
Labour for physical inspection for earthing health and to check the healthiness of earthing system whether the resistance under safe limits of resistance IF higher than the permissible then recharging of earthing should be done immediately with carbon based low resistivity compound 0.001 ohm meter recharging of existing earth pit by excavating soil up to electrode depth approx 10 feet by manual drilling (post hole) method and filling with backfill compound maintenance free earthing compound to achieve desired resistance value less than 1 ohms in and including water up to top of the excavated bore, backfilling of earth pit, measuring the value after refilling pit and testing of earthing after recharging, reconnecting grounding electrode conductor and earth grid applying petroleum jelly etc. to bolted joints to minimise corrosion for the pipe earthing or plate earthing then gel should be used to lower down the resistance complete all as specified and as directed by Engr-in-charge.
Notes for sl item No 2: (i) In case of satisfactory results not found or results degraded during one year of recharging of the earthing, the same shall be made good/recharged again in order to have required test results within contract/Defect liability period without any extra cost to the department. (ii) Contractor will mark each earthing with CA No., date of recharging of earthing on MS sheet size 18"x12" x 1/8" with suitable mounting arrangement on wall or on ground duly painting blue over a coat of Red Oxide primer and letter/figures of words written with white colour. Quoted rate will be deemed to have been included the cost of the same. (iii) Necessary compound required for recharging shall be measured and paid separately under item No 3 here-in-after.
Supply only carbon based low resistivity compound 0.001 ohm meter, backfill compound complete all as specified and directed by Engr-in-charge.
Supply and fixing in replacement 32x6 mm Copper strip in short pieces on surface or in recess for all interconnecting, in and including taking out worn out and damaged strip complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement 25x4 mm GI strip in short pieces on surface or in recess for all interconnecting, in and including taking out worn out and damaged strip complete all as specified and directed by Engineer-in-Charge.
M&L for copper brazing (welding) at site to connect loop copper earthing strip of any size after tightening by nut, bolt, washer, check nuts of brass complete all as specified and as directed by Engr-in-charge. Note: Copper brazing shall be done upto 20 mtr height. Necessary tool/plant and ladder required for working upto 20 mtr height shall be deemed to be included in the rate quoted for above item.
M&L for GI brazing (welding) at site to connect loop GI earthing strip of any size after tighten by nut, bolt, washer, check nuts, complete all as specified and as directed by Engr-in-charge. Note: GI brazing shall be done upto 20 mtr height. Necessary tool/plant and ladder required for working upto 20 mtr height shall be deemed to be included in the rate quoted for above item.
M&L for dismantling of old existing earthing PCC earthing pit with cover and S&F new polyplastic earth pit cover heavy duty with sign board triangular shape, making connection of earth strip including minor adjustment, construction of rectangular of size 0.75X0.75X0.50 (LXBXH) brick boundary alongwith necessary plastering work with specified colour coding around poly plastic earth pit cover, complete all as specified and directed by Engineer-in-Charge.
M&L for earthing complete with electrode shall be 2 Nos copper plate of size 90 cm x 60 cm x 5mm inter connected with 50x6 copper strip of length 1.5 mtrs and in centre shall be rod electrode as per UL 467:16mm dia solid rod with 250 microns copper coating of length 3 mtr with suitable connector for lower resistance. Alternate layers of soil & curec+ or equivalent (03 kgs bag x 2), make as per IEEE 80: 2000, Clause 14.5D, maintenance free earthing system to give earthing resistance value of < 1Ω . The soil shall be mixed with backfill compound as per IEEE 80: 2000 Clause 14.5 (b). Copper electrode's should be solid rod and surrounded with highly conductive and non corrosive nature (pH value certified) and covered with Poly plastic earth pit cover. Further electrodes of GI pipe at least 30mm dia shall be interconnected in paralled fashion in case low ohmage is not achievable, polyplastic pit cover enclosure shall be provided in and including boundary for poly plastic pit cover of size 1.25x1.25x0.3 mtrs of brick work duly plaster and painted as per colour coding. All certificates should be NABL LAB and CPRI certified, complete all as specified and directed by Engineer-in-Charge.
Note for Srl Item No. 9.00: The contractor will render a guarantee of 24 years for satisfactory working/effectivness of earthing from the certified date of completion from manufacturer firm/executing agency. The guarantee amount towards effectiveness of earthing equal to 5% of cost of item in BOQ in the form of FDR in favour of GE (AF) Tughlakabad shall be furnished by the contractor. The matured amount after period of 10 years (which is maximum period of FDR) again will be guarantee amount for next 10 years and thereafter i.e. after 20 years matured amount will be guarantee amount for next 04 years. Matured amount after 20 years will be given as guarantee amount for next 04 years to meet cost of inflation for time to time which will be released after satisfactory expiry of guarantee period.
Supply and fixing in replacement only single phase rolling shutter gate motor powerful with a maximum gate weight capacity 200-250 kg, power source- 230 V-1 phase electromechanical gear motor rolling shutter for industrial hangers complete with encoder, control Unit 230V, rolling shutter tube 60 mm, dia winding flange 200 mm, power 0-450 W, amperage-2A, frequency 50 Hz, insulation class F, Capacitor - mF, RPM -9, Torque - 142 N-M , Max rising height- 7 meter, short team rotation- -8 Min, T with automatically by button or controller manually & limit switches, environmental temperature -25°C to +50°C, with inbuilt control box and infrared photo cell sensor including remote, highest relative humidity: 95 % (25°C) with 10 minutes continuous operation at most in and including dismantling of unserviceable rolling shutter motor from the shaft of shutter for carrying out necessary cleaning and replacement of unserviceable parts, complete all as specified and directed by Engineer-in-Charge. Make/Model: UNIKO-1 M EVOLUTION/ELCOMA/ELERO
Supply and fixing in replacement only single phase rolling shutter gate motor powerful with a maximum gate weight capacity 500 kg, power source- 220 V-1 phase electromechanical gear motor rolling shutter for industrial hangers up to 500 kg complete with encoder, control Unit 220V, rated power-370 W, rated current-3.5A, lifting force-500 KG, output torque- 345 N-M, output rotate speed 6.2 r/min, max rising height- 7 Metre, short team rotation- -8 Min, own weight dropping torque ≤ 10 KG, standard drum diameter- 5 inch, sprocket specification (GB1243.1-81)- 10A-1*68, sprocket gear ratio - 9 T/47 T with automatically by button or controller manually & limit switches, environmental temperature -25°C to +50°C, Highest relative humidity: 95 %(25°C) with 10 minutes continuous operation at most in and including dismantling of unserviceable rolling shutter motor from the shaft of shutter for carrying out necessary cleaning and replacement of unserviceable parts, complete all as specified and directed by Engineer-in-Charge. Make: Tianxing made in TRC JMJ345/6.2-1P- (500 Kg) /TELCOMA/ELERO
LAIQ RAM VERMA
IK ONKAR ENGINEER AND CONTRACTOR
M/S Delhi Engineering Co.
RUHI ASSOCIATES
Deep Contractor
stage.html
html • 0.06 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .