Loading…
Loading…
Tender Value
₹51.1 L
EMD Value
₹1.0 L
Closing Date
20 Feb 2026, 11:00 amClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Above/Below/Par
TENDER
16 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
Work experience certificate from private individual shall not be considered. However, in addition to work experience certificates issued by any Govt. Organization, work experience certificate issued by Public listed company having average annual turnover of Rs 500 crore and above in last 3 financial years excluding the current financial year, listed on National Stock Exchange or Bombay Stock Exchange, incorporated/registered at least 5 years prior to the date of closing of tender, shall also be considered provided the work experience certificate has been issued by a person authorized by the Public listed company to issue such certificates. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final/last bill paid by company in support of above work experience certificate.
The work experience certificate shall be issued by an officer or Bill passing Officer in Railways and Bill passing Officer /Executive In-Charge of work in other Govt. / Govt. bodies / PSUs. The certificate should bear the signature and seal of the Issuing Officer, Name of the department etc,. In case tenderer submits work experience certificate issued by public listed company, the tenderer shall also submit along with work experience certificate, the relevant copy of work order, bill of quantities, bill wise details of payment received duly certified by Chartered Accountant, TDS certificates for all payments received and copy of final / last bill paid by company in support of above work experience certificate. (Note: Mandatory for whom it is applicable).
56 conditions · 11 needing a document upload
The tenderer(s) shall enclose the attested copies of the constitution of their concern, and copy of PAN Card along with their tender. Tender Documents in such cases are to be signed by such persons as may be legally competent to sign them on behalf of the firm, company, association, trust or society, as the case may be. . Necessary documents to this effect as applicable,
Electrical License as per tender conditions.
In case of other than company/proprietary firm , annexure V (A) shall also be submitted by each member of a partnership firm/ Joint Venture(JV)/Hindu United Family (HUF)/ Limited liability partnership(LLP) etc., as the case maybe. Non submission of above certificate(s) by the bidder shall result in summarily rejection of his/their bid. It shall be mandatorily incumbent upon the tenderer to identify, state and submit the supporting documents duly self attested/digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document
Power of attorney duly stamped and authenticated by a Notary Public or by Magistrate as per Tender conditions.
The tenderers are advised to download and carefully read the Tender Document attached with this Notice Inviting tender.
Tenderers are advised to submit all the documents required to be uploaded by them in Kannada/Hindi/English. Documents uploaded in any other language shall be translated to Kannada/Hindi/English and attested copy may be uploaded for better appreciation of the tender.
Mandatory documents that are to be uploaded without which the bid will be summarily rejected are mentioned in Chapter II of the Tender Document attached with this Notice Inviting Tender
CORRIGENDUM NOTICE ON IREPS: Railway may modify the tender document by issuing online corrigendum through "www.ireps.gov.in" 15 days prior to the tender closing date. For the purpose of CORRIGENDUM in the tender, NIT period is split as under: (a) ADVERTISEMENT PERIOD: The time during which all information pertaining to tender shall be available but offers cannot be submitted (b) OFFER SUBMISSION PERIOD: 15 days prior to closing of tender, during which tenderers can submit their offer
The tenderers are advised to carefully read this tender Document (Chapter I to IV) in conjunction with Indian Railways Standard General Conditions of Contract- April 2022 with latest amendments and correction slips before participating in this Tender.
The rates quoted for the relevant supply items of work shall include the cost of materials and their accessories. Similarly, for fixing/installation/erection/ Testing and Commissioning item of work shall include the cost of labour, together with the cost of providing the necessary tools and tackles etc., so as to ensure that the work carried out forms a complete supply, installation,Testing, commissioning of item work to the satisfaction of the Engineer-in-charge.
The prices quoted shall be net including all taxes and duties etc.
Documents to be Submitted Along with Tender (i)The tenderer shall clearly specify whether the tender is submitted on his own (Proprietary Firm) or on behalf of a Partnership Firm / Company / Joint Venture (JV) / Registered Society / Registered Trust / HUF etc. The tenderer(s) shall enclose the attested copies of the constitution of their concern, and copy of PAN Card along with their tender. Tender Documents in such cases are to be signed by such persons as may be legally competent to sign them on behalf of the firm, company, association, trust or society, as the case maybe. (ii)Following documents shall be submitted by the tenderer: (a)Sole Proprietorship Firm:
Following documents shall be submitted by the tenderer: if HUF: (i) A copy of notarized affidavit on Stamp Paper declaring that he who is submitting the tender on behalf of HUF is in the position of 'Karta' of Hindu Undivided Family (HUF) and he has the authority, power and consent given by other members to act on behalf of HUF.
Following documents shall be submitted by the tenderer: if Company registered under Companies Act2013: (i) The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company (ii) A copy of Certificate of Incorporation (iii) A copy of Authorization/Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company.
Following documents shall be submitted by the tenderer: if LLP (Limited Liability Partnership): (i) A copy of LLP Agreement (ii) A copy of Certificate of Incorporation (iii) A copy of Power of Attorney/Authorization issued by the LLP in favour of the individual to sign the tender on behalf of the LLP and create liability against the LLP. (iv) An undertaking by all partners of the LLP that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP or JV in which they were / are partners/members. concealment / wrong information in regard to above shall make the contract liable for determination under Clause 62 of the Standard General Conditions of Contract.
Following documents shall be submitted by the tenderer: if Registered Society & Registered Trust: The tenderer shall submit: (i) A copy of Certificate of Registration (ii) A copy of Memorandum of Association of Society/Trust Deed (iii) A copy of Power of Attorney in favour of the individual to sign the tender documents and create liability against the Society/Trust. (iv) A copy of Rules & Regulations of the Society
The following documents shall be submitted by the partnership firm, with the tender: (i) A notarized copy of the Partnership Deed or a copy of the Partnership deed registered with the Registrar. (ii) A notarized or registered copy of Power of Attorney in favour of the individual to tender for the work, sign the agreement etc. and create liability against the firm. (iii) An undertaking by all partners of the partnership firm that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP in which they were / are partners/members. Any Concealment / wrong information in regard to above shall make the bid ineligible or the contract shall be determined under Clause 62 of the Standard General Conditions of Contract.
The tenderers are advised to upload all required documents mentioned in this Notice Inviting Tender as well as in the Tender Document (Tender forms)(Chapter I to IV) along with the bid.
The schedule given in this NIT shall be read in conjunction with technical specifications/ explanatory notes and drawings given in the Tender document attached with this Tender
Upload duly filled & signed copy of "NEFT Declaration form". (please download the format from attached documents)
Partnership Deeds, Power Of Attorney Etc.: The tenderer shall clearly specify whether the tender is submitted on his/her own or on behalf of a partnership concern. If the tender is submitted on behalf of a partnership concern, he/she should upload the certified copy of partnership deed along with the tender and authorization to sign the tender documents on behalf of partnership firm. The Railway will not be bound by any power of attorney granted by the tenderer or by changes in the composition of the firm made subsequent to the execution of the contract. It may, however, recognize such power of attorney and changes after obtaining proper legal advice, the cost of which will be chargeable to the contractor. Note: Mandatory only for whom it is applicable.
The tenderer whether sole proprietor, a limited company or a partnership firm if they want to act through agent or individual partner s should submit along with the tender , a power of attorney duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/she/they be partner(s) of the firm or any other person specifically authorizing him/her/them to submit the tender and other tender related activities till completion of the work including signing No Claim Certificate and refer all or any disputes to arbitration. Note: Mandatory only for whom it is applicable.
The tenderer whether sole proprietor, a limited company or a partnership firm if they want to act through agent or individual partner s shall submit a power of attorney at a later stage duly stamped and authenticated by a Notary Public or by Magistrate in favour of the specific person whether he/they be partner s of the firm or any other person specifically authorizing him/them to sign the agreement, witness measurements, sign measurement books, to sign contract correspondence, signing the bills etc. the GPA shall be accepted after obtaining Legal advise from LAW branch/ Hubballi division. Note: Mandatory only for whom it is applicable. Note: Mandatory only for whom it is applicable.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Upload the CLEAR COPY of GST Registration particulars
Electrical arrangements to Modernization of signaling system by provision of Electronic Interlocking System at KGW & PKL Stations under SSE/Sig/HPT section.
HE-24-2025-26SL03
HE-24-2025-26SL03
Open
Works - General
6 Months
Dharwad, Karnataka
₹0
₹1.0 L
20 Feb 2026
28 Jan 2026
89 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 51,08,761.8 | ||
| — | 960.00 | — | — | ||
| Excavation in trenches in any kind of soil of required width for LT/HT UG cables, foundations, including excavation for joints, and dressing of sides, ramming of bottoms, depth up to 1.5 m as directed at site, including getting out the excavated soil, and then returning the soil as required in layers not exceeding 20 cm in depth, including consolidating each deposited layer by ramming, watering, etc. and disposing off surplus excavated soil as directed, within a lead of 50 mtrs from the starting point. | — | — | — | 1,93,804.8 | |
| — | 3200.00 | — | — | ||
| Supply of high density polyethylene pipe (HDPE pipe) of size 50 mm nominal dia, category of PE-80, PN-6 along with accessories (T joint / straight coupler etc.), ISI marked and drawing LT cables all as per specification. | — | — | — | 1,75,904 | |
| — | 3200.00 | — | — | ||
| Laying of high density polyethylene pipe (HDPE pipe) of size 50 mm (nominal bore) category of PE-80, PN-6 along with accessories (T joint / straight coupler etc.), ISI marked and drawing LT cables all as per specification. | — | — | — | 19,520 | |
| — | 3200.00 | — | — | ||
| Transportation, Laying, testing and commissioning of LTUG cable 4cx16 / 4cx25 / 4cx35 / 4cx50 sqmm as per specification. Note:- LT UG cable will be issued by Railways. The contractor will be responsible for collection of cables from the Elect Maintenance / Works Depot including loading, unloading, transportation and return of un-used cables back at Depot. Costs of these provisions are deemed to be included in the quoted rates. | — | — | — | 55,360 | |
| — | 330.00 | — | — | ||
| Material and labour for Trenchless cutting to lay the LTUG/HTUG cable for crossing the track/road duly drawing 160 mm (nominal bore) size PE80, PN.6 HDPE pipe, ISI marked as per instruction of Engr-In- Charge (Scope includes cost for horizontal drilling, cost of pipe and laying of pipe etc. but charge for laying of cable is not included). | — | — | — | 5,66,445 | |
| — | 16.00 | — | — | ||
| Fabrication, assembling, supply and erection of hot dip galvanized octagonal pole 5.5 Mtr long made of 3 mm thick sheet, top 70 mm A/F and bottom 130 mm A/F double arm bracket 350 mm long to fix street light luminary with foundation bolt, base plate 250 x250 x 12 mm and inbuilt junction box with strip connector, cut out and all accessories for street light pole/platform pole (Excluding PCC foundation). Note: conforming to BSEN 10025 grade S355 JO steel plate for shaft, IS 2062 for base plate | — | — | — | 1,70,352 | |
| — | 96.00 | — | — | ||
| Supply and drawing 3 x 1.5 sq mm size of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required. | — | — | — | 9,120 | |
| — | 4.00 | — | — | ||
| Providing and making steel pole foundation / collar with cement concrete (1:3:6) with stone aggregate 20 mm nominal size in foundations of specified size and shape including form work, plastering if required, curing etc as required. (Volume of pole /pipe not to be deducted). | — | — | — | 32,540 | |
| — | 30.00 | — | — | ||
| Supply and embedding 40 mm dia GI pipe, medium class, in pole collar / foundation (During casting) for cable entry including bending the pipe to the required shape complete as required. | — | — | — | 17,670 | |
| — | 32.00 | — | — | ||
| Supply of 70 W, LED Street light fitting with IP -66 protection as per detailed tender / SWR specifications. | — | — | — | 1,71,504 | |
| — | 32.00 | — | — | ||
| Fixing of 70 W, LED Street light fitting with IP -66 protection as per detailed specification. Note: The scope of work includes provision of fixing arrangements such as suitable clamps, nuts, bolts, washers, twisted twin core copper cables of 1 sqmm size, connector terminals etc. | — | — | — | 19,056 | |
| — | 5.00 | — | — | ||
| Cutting of cement concrete (PCC) surface, any type for laying of UG cables in trenches and disposing off the excavated material as directed including barricading, danger lighting and refilling the trenches in layers and consolidating complete all as specified and directed. | — | — | — | 5,390 | |
| — | 4.00 | — | — | ||
| Demolishing R.C.C work manually /by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 meters lead as per direction of Engineer-in- charge. | — | — | — | 9,252 | |
| — | 12.00 | — | — | ||
| Supply and making end termination with water / moisture proof brass compression gland with double check nuts and aluminium lugs for 4 x 50 Sqmm of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 KV grade as specified and directed. | — | — | — | 5,016 | |
| — | 30.00 | — | — | ||
| Supply and making end termination with water / moisture proof brass compression gland with double check nuts and aluminium lugs for 4 x 16 Sqmm of PVC insulated and PVC sheathed /XLPE aluminium conductor cable of 1.1 KV grade as specified and directed. | — | — | — | 9,270 | |
| — | 2.00 | — | — | ||
| Design, fabrication, supply, fixing, connecting, testing and commissioning of LT Control Panel, out door type, cubical type, 100 A, 3 phase 4 wire system, insulated copper bus bars of size 35 x 6 mm, opening from front side, separate compartments for each control gear and energy meters, separate cable alley and provision of knock out type entry plates suitable up to 120 sqmm size cables, panel made out of 2 mm thick CRCA sheet, epoxy powder coated with grey matt finish, including base frame made out of 40 x 40 x 4 mm angle iron sections with 60 cms long legs, embedded in PCC 1:3:6 foundation or mounted on walls as directed, consisting of the following switchgears and accessories:- i) MCCB 100 A, 4 pole, 415 V, 36 KA with microprocessor based, for I/C - 01 No ii) MCB 63 A, TPN, 415 V, 10 KA - 4 Nos, iii) MCB 5-32A, DP, 10 KA- 6 Nos. iv) Phase indicating lamps - RYB. v) Multi function 3 Phase meter - 01 No including integral wiring and all connecting materials and works. | — | — | — | 1,37,542 | |
| — | 6.00 | — | — | ||
| Supply and fixing 4 way (4 + 12), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. | — | — | — | 24,546 | |
| — | 6.00 | — | — | ||
| Supply and fixing 63 A rating, 415 V, 10 kA, "B" curve, miniature circuit breaker suitable for inductive load of Triple pole and neutral in the existing MCB DB complete with connections, testing and commissioning etc. as required. | — | — | — | 18,528 | |
| — | 36.00 | — | — | ||
| Supply and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "B" curve, Double pole miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. | — | — | — | 23,616 | |
| — | 12.00 | — | — | ||
| Supply and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "B" curve, Single pole miniature circuit breaker suitable for inductive load in the existing MCB DB complete with connections, testing and commissioning etc. as required. | — | — | — | 3,072 | |
| — | 12.00 | — | — | ||
| Material and labour for earthing with G.I earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing mansory enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with Charcoal/coke and salt as required and as specified in the tender documents. | — | — | — | 89,664 | |
| — | 80.00 | — | — | ||
| Providing and fixing 25 mm x 5 mm G.I strip on surface or in recess for connections etc. as required. | — | — | — | 19,520 | |
| — | 40.00 | — | — | ||
| Supply of 20/22 W LED Batten fitting, 240 V AC with diffuser and driver including all connected materials as per detailed tender / SWR specification. | — | — | — | 27,600 | |
| — | 92.00 | — | — | ||
| Supply of LED modular down light fitting with lamp 1' x 1', 22-34 W, recess or surface type as per site requirements including all necessary fixing arrangements complete all as all as per detailed tender / SWR specifications. | — | — | — | 3,39,664 | |
| — | 80.00 | — | — | ||
| Supply of LED modular down light fitting with lamp 2' x 2',@10"45@36 W, recess or surface type as per site requirements including all necessary fixing arrangements complete all as all as per detailed tender / SWR specifications. | — | — | — | 3,64,240 | |
| — | 212.00 | — | — | ||
| Fixing all types and all capacities of LED fittings indoor on the wall/ ceiling /rafters / girders using twin twisted PVC insulated wires, required Nos of round blocks and clamps. | — | — | — | 25,864 | |
| — | 44.00 | — | — | ||
| Supply of BLDC ceiling fans, working on 230 V AC, 50 Hz of Sweep size1200 MM all as per detailed technical specification including provision of necessary down rods of required length, canopies, clamps etc all as per tender specifications & directed. | — | — | — | 1,17,788 | |
| — | 44.00 | — | — | ||
| Fixing of BLDC ceiling Fans, working on 230 V AC , 50 Hz of Sweep size, 1200 MM with connected items such as hooks, nuts, bolts all as per detailed technical specification. | — | — | — | 13,860 | |
| — | 24.00 | — | — | ||
| Supply only single phase AC 230 V, 50 Hz modular type BLDC Exhaust fan 300 mm sweep complete with all accessories such as frame with louvers all as per detailed tender specifications | — | — | — | 44,301.6 | |
| — | 24.00 | — | — | ||
| Fixing of single phase AC 230 V, 50 Hz modular type BLDC Exhaust fan 300 mm sweep complete with all accessories such as frame with louvers, necessary mounting arrangements, nuts, bolts, fasteners including making suitable openings on walls, plastering, painting the wall surfaces matching with the existing tint and shade etc all as specified and directed. | — | — | — | 4,922.4 | |
| — | 12.00 | — | — | ||
| Supply only 70 W, LED flood lights complete all as per detailed tender & SWR specifications. | — | — | — | 81,216 | |
| — | 12.00 | — | — | ||
| Fixing of 70 W, LED flood light fitting on walls / pillars including all necessary fixing arrangements such as clamps, nuts, bolts etc; as per site requirement and per detailed tender specifications. | — | — | — | 1,944 | |
| — | 292.00 | — | — | ||
| Supply and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. | — | — | — | 25,404 | |
| — | 90.00 | — | — | ||
| Supply and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required | — | — | — | 42,930 | |
| — | 90.00 | — | — | ||
| Supply and fixing 3 pin 5/6 A moudular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | — | — | — | 10,980 | |
| — | 90.00 | — | — | ||
| Supply and fixing 3 pin 5/6 A moudular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | — | — | — | 9,270 | |
| — | 30.00 | — | — | ||
| Supply and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required. | — | — | — | 17,580 | |
| — | 30.00 | — | — | ||
| Supply and fixing 6 pin15/16 A moudular socket outlet on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | — | — | — | 5,910 | |
| — | 30.00 | — | — | ||
| Supply and fixing 6 pin 15/16 A moudular switch on the existing modular plate & switch box including connections but excluding modular plate etc. as required. | — | — | — | 4,680 | |
| — | 292.00 | — | — | ||
| Material and labour for point wiring for light point/ fan point/exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required including all necessary connected works such as cutting chases, drilling holes on wall / ceiling etc including plastering / making good the disturbed surfaces all as specified and as directed. Note: Surface wiring shall be opted only where recessed wiring is not feasible and as per the direction / approval of the Engr-In-Charge. | — | — | — | 2,96,380 | |
| — | 1200.00 | — | — | ||
| Material and Labour for circuit/ submain wiring along with earth wire with the size of 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire FRLS PVC insulated copper conductor, single core cable in recessed medium class PVC conduit including all necessary connected works such as cutting chases, drilling holes on wall / ceiling etc including plastering / making good the disturbed surfaces all as specified and as directed. Note: Surface wiring shall be opted only where recessed wiring is not feasible and as per the direction / approval of the Engr-In-Charge. | — | — | — | 3,30,000 | |
| — | 700.00 | — | — | ||
| Material and Labour for circuit/ submain wiring along with earth wire with the size of 2 X 4 sq. mm + 1 X 4 sq. mm earth wire FRLS PVC insulated copper conductor, single core cable in recessed medium class PVC conduit including all necessary connected works such as cutting chases, drilling holes on wall / ceiling etc including plastering / making good the disturbed surfaces all as specified and as directed. Note: Surface wiring shall be opted only where recessed wiring is not feasible and as per the direction / approval of the Engr-In-Charge. | — | — | — | 2,33,800 | |
| — | 500.00 | — | — | ||
| Material and Labour for circuit/ submain wiring along with earth wire with the size of 2 X 6 sq. mm + 1 X 6 sq. mm earth wire FRLS PVC insulated copper conductor, single core cable in recessed medium class PVC conduit including all necessary connected works such as cutting chases, drilling holes on wall / ceiling etc including plastering / making good the disturbed surfaces all as specified and as directed. Note: Surface wiring shall be opted only where recessed wiring is not feasible and as per the direction / approval of the Engr-In-Charge. | — | — | — | 2,19,500 | |
| — | 12.00 | — | — | ||
| Supply, Transportation, Installation, Testing and Commissioning of Ductable Air condition (AC) system of 2 TR Unit Capacity, refrigerant R-410, Single Phase AC, 230 V, 50 Hz, including copper pipe with Nitrel Insulation (9 mm thickness) for inter connection of indoor and outdoor units, control/communication cable, Outdoor Unit stand, GI ducting as required up to 3 mtrs, Duct connection with canvas of suitable length/size, necessary cutting chases/drilling holes on walls, ceilings etc., Aluminium Composite Sheet (ACP) closure for AC unit, Aluminium power coated grill for suitable size for covering the duct and other accessories as required all as per detailed tender specifications. | — | — | — | 11,14,236 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
NEFTForm.pdf
FormatofCertificationforCredentials.pdf
2018_CE-I_CT_9Date04_06_2018LOC.pdf
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27.04.22.pdf
ACS1to6.pdf
JPOforcablecuttings1.pdf
TenderBooklet-ElectarrangementtosignalingElectronicInterlockingSystematKGWPKL.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .