Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | Admitted-Finance |
| 4 | Rejected-Technical NAKARI BORIGAON SIDING JORHAT 785001 ASSAM | JORHAT | JORHAT | ASSAM | 785001 | Rejected-Technical Not Recommended as the contractor is not enlisted in b(iii) category |
| 5 | Rejected-Technical | Rejected-Technical Due to No remark WLR of QE Dec 2022 circulated ADG NEI Guwahati vide letter No 80017/ADG NEI/WLR/D TO S/594/E8 DT 28 Feb 2023 |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
9 Jan 2023, 6:00 pmClosed
GE (AF) JORHAT
GE (AF) JORHAT PIN-785005
REPAIR / MAINT OF HT ELECTRIC SUPPLY, 33 KV VCB, 11 KVA VCB, CT, PT, LIGHTNING ARRESTORS, HT CABLES AND OTHER CONNECTED WORKS AT AFS UNDER GE (AF) JORHAT
2022_MES_568791_1
8501/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) JORHAT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (AF) JORHAT
₹70,000
Yes
11 Mar 2023
13 Dec 2022
11 Jan 2023
13 Dec 2022
9 Jan 2023
26 Dec 2022
Amount
Disconnecting and taking out existing 11 KV HT VCBs of any make from housing and cleaning, rubbing and overhauling the mechanical parts and Servicing of 11 KV in door VCB, checking of quality of vacuum interrupter, insulation resistances, static contact resistance, Testing ( IR value, Ratio test, Polarity test) and connection verification of 6.6 KV Current transformer( Set of three) by PRIMARY INJECTION KIT ,and Testing and calibration of relay (set of two Over current and one earth fault) by SECONDARY INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs. setting right the mechanism and reassembling, testing and commissioning etc as required complete all as specified and directed.
(a) Taking out trolley unit from metal clad housing and dismantling complete, carrying out inspection cleaning, mechanical spring complete all as specified and directed. (b) Opening of bus bar chambers, carrying out inspection, cleaning of complete unit and refixing of the bus bar complete all as specified and directed. (c) Carrying out testing of all metering instruments replacement of worn out spares, meter, wiring cable etc and testing complete. (d) Inspection and checking of all protection devices, relays, complete all as specified and directed. (e) Carrying out inspection and testing of auxiliary power system, complete all as specified and directed. (f) Assembling of complete HT switch gear unit, proper greasing oiling / for easy operation and connection of incoming and outgoing cable and make all necessary adjustment and testing complete all as specified and directed.
Note : Replacement of spares such as Gasket set, ht trolley bushes, plug insulators, busbar insulator for HT VCB , PT Bush for HT VCB, PT housing bush for HT VCB, interrupter of HT VCB HT HBC fuse link IDMTL relay, power pack 230 V/110 V DC 20A and CT ratio 100-50/5A etc shall be paid separately under relevant item here-in-before
Supply only 11 KV Vacuum Interrupter with TC suitable for 11 KV VCB Panel complete all as specified and directed. Make : Schneider Model VG2 / ABB / Siemens
Supply only HT trolley chamber suitable for HT VCB Panel complete all as specified and directed. Make : Schneider / ABB / Siemens
Supply only CA3KN22FD, 2NO+2NC, 3P, 110Volt DC control relay suitable for HT VCB Panel complete all as specified and directed. Make : Schneider
Supply only mono block diode suitable for HT VCB Panel complete all as specified and directed. Make : Schneider / ABB / Siemens
Supply only MK II A, 80W, 230V, panel space heater suitable for HT VCB Panel complete all as specified and directed. Make : BE / ABB / SIEMENS/ GE / SCHNEIDER
Supply only of CT ratio 100-50/5-5A. 15 VA, class 1 Accuracy for metering and protection resin cast current transformer as per existing make or equivalent complete all as specified and directed. Make : ECS/Pragati/JSL/Gemini /Schneider/L&T
S&F LED indicator with wiring suitable for existing HT VCB Panel as per existing make complete all as specified and directed.
S&F 2.5 sqmm, 4 core copper multistand cable 1100 V after taking down carefully old u/s cable complete all as specified and directed.
S&F in replacement of HT 11KV VCB panel spout insulator complete all as specified and directed. Make : ECS/Pragati/JSL/Gemini /Schneider/L&T or as per sample in existing VCB's.
S&F in replacement of HT 11KV VCB panel TNC Switch BCA02 as per sample in existing VCB's complete all as specified and directed
S&F HT 11 KV Bus Bar insulator with nut, bolts etc complete all as specified and directed.
Labour for shifting of 11KV HT VCB panel after carefully disconnecting cable , gland etc from the existing panel and re-fixing the same at specified location complete all as specified and directed
Supply only cable gland of the following size complete all as specified and directed
Supply only aluminium lug of the following size complete all as specified and directed
Repair to LT ACB of capacity 800/1000 amps by disconnecting from the busbar and replacing all unserviceable parts of finger contact with male female set and wiring with new copper conductor cable of 2.5 sq mm . Replacing the U/S mechanical spring system , fixed and moving contacts, replacement of bearing of spring charge motor and rewinding of control transformer with super enamelled copper wire of gauge and replacement of FRCD (free return charge device) all connected work including require at site for proper and smooth functioning of air circuit breaker complete all as specified and directed at 36 Bldg, and LC-III power house
S&F cam switch with wiring Suitable for existing ACB Panel as per existing make complete all as specified and directed.
Supply only SCR for E1-E6, 220-240V AC/DC suitable for existing ACB Panel complete all as specified and directed. Make : ABB / SIEMENS /SCHNEIDER /L&T
Supply only SOR for E1-E6,220-240V AC/DC suitable for existing ACB Panel complete all as specified and directed. Make : ABB / SIEMENS /SCHNEIDER /L&T
Supply only 1SDA038312R1, 220V U/V release for E1/6-T8 suitable for existing ACB Panel complete all as specified and directed. Make : ABB / SIMENS /SCHNEIDER /L&T
Supply only Spring charge motor with gear suitable for ACB Panel as per existing make complete all as specified and directed. Make : ABB / SIMENS /SCHNEIDER /L&T
S&F LED indicator with wiring suitable for existing ACB Panel as per existing make complete all as specified and directed.
S&F Pin type 33KV composite polymer insulator complete all as specified and directed.
S&F Disc type 33KV composite polymer insulator complete all as specified and directed.
S&F Pin type 11KV composite polymer insulator complete all as specified and directed.
S&F Disc type 11KV composite polymer insulator complete all as specified and directed.
M&L for cable in passing through pipe, XLPE insulated, heavy duty, galvanised steel strip or wire armoured electric LT cable with stranded Copper conductor for 1100 volts grade cross sectional area 2.5 sqmm 4 core complete all as specified and directed.
S&F in repair connector box 12 Pole for 33KV CT complete all as specified and directed.
S&F in repair PT terminal box 6 Pole for 33KV PT complete all as specified and directed.
S&F cadium bolt & Nut complete all as specified and directed
S&F 33 KV single phase out door oil cooled PT of ratio 33 KV/rt 3/110V/rt 3/110V/rt 3 Class 0.5-3, Burden 50 VA – 50 VA, insulation level 70KV/170 KV, voltage factor 1.2 Cont and 1.9 for 30 Sec, conforming to IS-3156 including dismantling taking out of existing unserviceable 33 KV PT including all connection etc complete all as specified and directed. Make; AE/Areva T&D /Crompton greaves/Schneider.
M&L for disconnection, connection and servicing of 33KV CT/PT vertical / horizontal mounted including Insulators and Operating Mechanism for repair/replacement of broken / worn out components etc complete all as specified and directed. NOTE :- (a) Parts needed to be replaced shall be measured and paid separately as 'supply only' against appropriate Items of Schedule. However Labour component involved in replacement is included in Unit Rate quoted against this Item. The Unit Rate shall deemed to be included for handling of serviceable materials for reuse to site complete all as specified and directed. (b) Any minor repairs involved to make the CT/PT functional even if notified by Engineer-in-Charge shall be carried out by the Contractor without any extra cost to the Department.
Dismantling Air Break Gang Operated Switches HT 11 KV 3 Phase, any capacity ( 200/400 ) Amps vertical / horizontal mounted including Insulators and Operating Mechanism for repair/replacement of broken / worn out components and insulators etc. with or without taking down from Pole all as directed. NOTE :- (a) Parts needed to be replaced shall be measured and paid separately as 'supply only' against appropriate Items of Schedule. However Labour component involved in replacement is included in Unit Rate quoted against this Item. The Unit Rate shall deemed to be included for handling of serviceable materials for reuse to site and as directed (b) Any minor repairs involved to make the GOD functional even if notified by Engineer-in-Charge shall be carried out by the Contractor without any extra cost to the Department.
Supply only Male Contact/ Moving Contact Blade suitable for Air Break Gang Operated Switches, 11KV, complete all as specified and directed.
Supply only Female Contact/ Fix Contact Jaw suitable for Air Break Gang Operated Switches, 11KV, complete all as specified and directed.
Supply only Tinned Copper Flexible Jumper 200/400 Amps, suitable for Air Break Gang Operated Switches, 11KV, complete all as specified and as directed.
Supply only MS Jumper Carrier, suitable for Air Break Gang Operated Switches, 11KV, complete all as specified and as directed
Supply only Back Connector Plate, suitable for Air Break Gang Operated Switches, 11KV, complete all as specified and as directed
Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc of any size, including Mild Steel Bolts, Nuts, Washers, etc., complete all as specified and directed.
M&L for Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of two coats of Aluminium Paint over a Coat of suitable primer, complete all as specified and directed.
Re-fixing only Cross-arms, Bracings, Supports, Clamps and Back Plates (serviceable materials i.e. Structural Steel Sections obtained from dismantling) including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed including painting complete all as specified and directed.
Disconnecting HV/LV Connections of Transformer, including disconnecting of earthing lead, unscrewing nuts, bolts and washers, testing their un-serviceability (Open and Closed circuit test) with the help of composite unit of Transformer 1000 to 2000 KVA 33000/11000, and power transformer of any capacity complete all as specified and directed
M&L for Dehydration/Filtration of Transformer Oil by means of Centrifugal Filtration Plant to achieve the specified Di-electric Strength of 35 KV to 40 KV at 2.5mm Gap in Existing Position of Transformer of any Capacity and Transformer Oil for Topping Up at various Sub-station complete all as specified and directed. NOTE : Transformer Oil to be used for TOP UP shall be Measured and Paid separately.
Supply & Pouring of New Transformer Oil, conforming to IS:335-1983 to achieve a Di-electric Strength upto 60 KV with Oil Testing Kit 4.0mm thick to Top Up of the Transformer complete all as specified and directed.
M&L for Servicing , Testing of Transformer of 1000 to 2000 KVA , 33/11 KV outdoor, disconnecting all Internal Connections of HT Side for Periodical Maintenance such as Cleaning of Core and Winding by means of Washing by Hosing Down with Clean Dry Oil to removed Dust/Sludge on Core and Coil, Cleaning of Oil Tank to removed Sludge deposited, Replacement of Rusted Gasket Set, Burnt Spindle, Broken/ Unserviceable HV/LV Ceramic Bushing, Broken Arc Horn, Surge Arrestor, Replacement of Silica Gel, etc. and then after assembling to complete all as specified and as directed. NOTE : (a) Cost of Transformer Oil for Cleaning by Hosing down shall deem to be included in the QUOTED UNIT RATE. (b) Replacement of spares parts will paid separately.
Supply only Breather Assembly filled with Silica Gel for Transformer of 1000 to 2000 KVA, 33/11 KV outdoor as Approved complete all as specified and directed.
Supply only Brass Spindle for Terminal on HT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as Approved and suitable for Transformer 1000 to 2000 KVA , 33/11 KV , complete all as specified and directed.
Supply only Brass Spindle for Terminal on LT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as Approved and suitable for Transformer 1000 to 2000 KVA , 33/11 KV , complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on LT Side of Transformer 1000 to 2000 KVA , 33/11 KV complete all as specified and directed.
Supply only Ceramic Bushing and Gasket on HT Side of Transformer 1000 to 2000 KVA , 33/11 KV complete all as specified and directed.
Supply only Gasket (Cock Sheet) 6 mm thick with Conical Rubber Bush Complete as approved and suitable for Transformer 1000 to 2000 KVA , 33/11 KV Volt including Taking down/ out unserviceable Gasket, complete all as specified and directed.
M&L for Servicing , Testing of Transformer of 100 to 630 KVA , 11000/433 volt indoor/outdoor, disconnecting all Internal Connections of HT/LT Side for Periodical Maintenance such as Cleaning of Core and Winding by means of Washing by Hosing Down with Clean Dry Oil to removed Dust/Sludge on Core and Coil, Cleaning of Oil Tank to removed Sludge deposited, Replacement of Rusted Gasket Set, Burnt Spindle, Broken/ Unserviceable HV/LV Ceramic Bushing, Broken Arc Horn, Surge Arrestor, Replacement of Silica Gel, etc. and then after assembling to all complete all as specified and directed. NOTE : (a) Cost of Transformer Oil for Cleaning by Hosing down shall deem to be included in the QUOTED UNIT RATE. (b) Replacement of spares parts will paid separately.
Supply only Breather Assembly filled with Silica Gel for Transformer of 100 to 630 KVA , 11000/433 volt indoor/outdoor as Approved complete all as specified and directed.
Supply only Brass Spindle for Terminal on HT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as Approved and suitable and suitable for Transformer 100 to 630KVA 11000/433 volt, complete all as specified and directed.
Supply only Brass Spindle for Terminal on LT Side Threaded complete with Nut, Washers, etc. of dia as ordered, as Approved and suitable and suitable for Transformer 100 KVA to 630KVA 11000/433 volt, complete all as specified and as directed.
Supply only Ceramic Bushing and Gasket on LT Side of Transformer 100 KVA to 630KVA 11000/433 volt complete all as specified and directed.
Supply only Ceramic Bushing and Gasket on HT Side of Transformer 100KVA to 630KVA 11000/433 volt complete all as specified and directed.
Supply only Gasket (Cock Sheet) 6 mm thick with Conical Rubber Bush Complete as approved and suitable for Transformer 100KVA to 630 KVA 11000/433 Volt including Taking down/ out unserviceable Gasket, complete all as specified and directed.
S&F in replacement silica gel grains in breather assembally of transformer complete all as specified and directed.
Taking down / out unserviceable or serviceable UG cables of any cross sectional area and connections including bricks, etc. of any descriptions, laid in trenches and /or fixing with walls /poles including segregating of serviceable materials viz bricks, cables, etc. and kept in Safe custody for re-use, complete all as specified and directed. (NOTE : Earth Work shall be measured and paid separately under relevant Items here-in-before.)
M&L for HT electric cable unearthed XLPE Insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm. and testing complete all as specified and directed.
Excavation in trenches not exc. 1.50 mtr wide and not exc. 1.50 mtr in depth and getting out in Soft / Loose Soil, complete all as specified and directed.
Returning, Filling in, including Spreading, Levelling, Watering and Well Ramming in layers not exc. 250 mm thick as in Soft/Loose Soil, complete all as specified and directed.
Removing excavated Materials (Soils) not exc. 50.00 mtr and depositing where directed at a level not exc. 1.50 mtr above the Starting Point. complete all as specified and directed.
M&L for Sand cushioning (dry) in trenches for protection of UG Cables (below, above and around the UG Cable laid in trenches) of 230mm Spread thickness and consolidated (punned) upto 180mm thickness, complete all as specified and directed. (NOTE : For the purpose of payment, punning thickness of Sand cushioning shall only be measured and paid).
S&F Sub-Class 'B' brick, well burnt, laid breadth-wise along the length of Cable laid in Trenches over Sand Cushion laid for UG Cable protection, complete all as specified and directed.
Re-laying only old Brick in trenches for under ground Cable Protection (Serviceable Bricks obtained from Item here-in-before), complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm and testing complete all as specified and directed.
M&L for Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm. and testing complete all as specified and directed.
Labour only for Horizontal Boring for Passing Protection Pipe up to 80mm Bore (dia), under Road /Foot Path, not exc. 10.00 mtr in a Single Length, complete all as specified and directed. Note : Pipe to be measured separately.
S&F Galvanised Iron Pipe 80mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and directed.
S&F Galvanised Iron Pipe 50mm Bore (dia) ‘Light Grade’ for protection of UG Cable, laid in Floors/ Road Crossing, fixing to Pole with Mild Steel Clamps, Nuts, Bolts, etc., complete all as specified and directed.
Re-Laying/Fixing or Passing through Pipe, XLPE insulated, Armoured, Electric Power UG Cable (Heavy Duty) with Aluminium Conductor, HT/LT, of any size including Brass Compression Cable Gland, Terminal Lug, etc. complete all as specified and directed.
S&F cable jointing kit for 33 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 240 sqmm complete all as specified and directed.
S&F cable jointing kit for 33 KV grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 240 Sqmm, Indoor/Outdoor type complete all as specified and directed. Note:- The contract sum shall be calculated by deducting the amount shown in Credit Schedule attached to this tender, from total amount of Schedule 'A'/BOQ.
M/S PS ENTERPRISE
PURBANCHAL BUILDERS
Bidder Name
PURBANCHAL BUILDERS
M/S PS ENTERPRISE
M/S SANTOSHI TRADERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .