Providing and fixing of 11 kv overhead line network allotted Industrial plots no. D 38 and D 38 1 to D35 5 in Surajpur site B Industrial Area
2022_SIDC_761616_1
ED-II(105) Date 07/092022 Rs. 12.12 Lacs
Open Tender
Electrical Works
Item Rate
30 days
Surajpur
As per Technical Bid Documents
2 documents required · 2 mandatory
₹1,475
Sr Manager
₹16,000
17 Feb 2023
23 Dec 2022
4 Jan 2023
23 Dec 2022
3 Jan 2023
23 Dec 2022
Amount
Electrical Works.
Supply and Erection of steel tubular pole 410-SP-56, 11 M. long, 241 Kg. complete with 1/6th| Number of overall length of pole in cement concrete with 30 cm dia cement plinth all round the pole and 30 cm above ground level. The foundation of underground will be of cement concrete in the ratio of 1:3:6 alround the pole. The brick ballast used will be of 1.2 cm size with stone pad| 30cm x 30cm x 7.5 cm. at the base. The cost includes all materials including MS pole cap| complete in all respect
Supply & Fixing of Straight MS Channel 75x40 mm, 2.24 m long. Complete in all respect.
Supply and Erection of Double pole Structure consisting of 410-SP56, 11 mtr long ST pole including fitting and mounting , T&P and men for proper completion of work.
Supply and fixing of clamp suitable for securing the channel & cross arm, with the hole made Number out of MS flat 50 x 6 mm including all bolts, washers, T&P and men & material complete in all respect.
Supply and fixing of 11 KV pin with insulator on the channel & cross arms fixed on ST pole Number including all nuts, bolts, washers, T&P and men & material complete in all respect.
Supply and fixing of 11 KV Disk Insulator with galavanised insulator fitting, ball and socket type complete with strain clamp, bolts , nuts, washers etc. including cost of material , men & T&P . complete in all respect.
S/B of 40 mm dia x 4.5 mtr. long G.I. pipe vertically for earthing having 12 mm dia. Holes Number spaced 75 mm apart drilled upto 2 mtr. from the bottom complete with earthing lead of no.6 to 8 SWG GI wire in G.lpipe upto apron upto switch board 30 cm squarc box with hinged cover masonry encosure. Funnel of top, alternate layers of charcoal and salt at least 150 mm thick alround etc. as per direction El complete in all respect
Supply & erection of stay of HT lines for ST pole with Gl anchor plate (152x1 52x6mm) stay Number rod (16mm dia x 1.85 m long) Gl stay bow (16 mm dia rod, thimble, double stay tightener clamps& stay wire (GS 7/3.15 mm) including grouting in 1:4:8 ratio of cement concrete using| coarse sand, over burnt brick ballast as per direction of engineer in charge complete in all respect
Supply, sagging, jointing and binding of ACSR Raccoon conductor including cost of aluminium tape binding wire and jointing sleaves etc. complete in all respect including men &&| material, T&P proper completion of work as per direction of Engincer in-charge
Supply, sagging, tensioning, jointing and binding of G.I. wire no.6 SWG on ST poles complete| in all respect including all men and material,T&P required for proper completion of work
Supply and laying of 120x 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level in existing DWC HDPE PVC Pipe /GI pipe /RCC pipe /MS pipe etc or along the wall/pole/panel /High mast . The armouring of cable shall be properly connected with earth conductor by clamps etc
Supply and laying of 120x 3 core standered aluminium conductor XLPE (Cross linked polyethylene) insulated PVC bedded, Galvanised flat steel strip armoured cables confirming to I.S. 7098 (Part-II with latest amendments) II KV grade at a depth of 900 mm below ground level over a cushion of 100 mm thick fine river sand all around and protected with well burnt bricks on sides and on top put across in laying of cable complete in all respect as per direction E/I
S/F of push on type heat shrink cable jointing kit suitable for 3 core 120 sq.mm 11 KV HT Cableoutdoor type including all material, labour and T&Prequired for proper completion of work.
Supply & fixing of danger board fabricated from 10 gauge M.S Sheet
Supply & laying of 150 mm dia G.I.pipes 'B' class for climbing up the cable from ground to over head line including all accessories, material, labours and T&P required for proper completion of work as per specification as per
Supply & Laying of 63 mm HDPE pipe ISI marked along with all accessories like socket,bend,couple etc. confirming to IS 14930 Part II complete with fitting and cutting,jointing etc in existing treanch. including cost of material,labour and T&P.
Supply & Laying of 160 mm HDPE pipe ISI marked along with all accessories like socket,bend,couple etc. confirming to IS 14930 Part II complete with fitting and cutting,jointing etc in existing treanch. including cost of material,labour and T&P.
Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 75 to 90 Watt. Confirming to IP 66 Protection complete in all respect CAT-AA
S/L of 16x2 core Al. armoured cable PVC insulated Ar. served & sheathed cable 1100 V grade at a depth of 750 mm below ground level in existing DWC HDPE PVC Pipe /GI pipe /Rcc pipe /ms pipe etc or along the wall/pole/panel /High mast as directed by the E/I.Complete in all respects . The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Make -Grandlay / Havells/Polycabe/Gloster
S/L of 16x2 core Al. armoured cable PVC insulated Ar. served & sheathed cable 1100 V grade at a depth of 750 mm below ground level with protection of burnt bricks on sides and top put across with over a cushin of 75 mm thick sand arround the cable complete in all respect as per direction E/I. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. Make -Grandlay / Havells/Polycabe/Gloster
S/F of 10 sq.mm Plain or Pin type copper tin plated cable socket (Lug) to the cable lead, insulating with tape and making connector etc. Complete in all respects as per Direction of EI
S/F of 16 sq.mm Plain or Pin type copper tin plated cable socket (Lug) to the cable lead, insulating with tape and making connector etc. Complete in all respects as per Direction of EI
Supply & fixing of MS Box for controlling of LED Street Light and with arrangement to avoid entry of mosture as well as rain water etc with 4 way cadmium connector & 20 Amp SPMCB including making connector
Supply & fixing of 100x110 mm Shakle Insulator 100x80 mm Pin Insulator including GI bolt spendle nuts etc.
Supply & fixing of 32 mm dia 1.2 meter long GI Pipe Bracket for fixing of LED Street Light cutting complete in all respect.
Supply & fixing of following capacity of automatic street light cubicle control panel painted with anticorrosive alkali and acid proof paint consisting of timer swicth TSO 100 series with contractors HRC fuse, isolating switch Metering instrument box with CTS etc. 25 amp. SPN.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .