Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance B17 ROOMA UPSIDC INDUSTRIAL AREA ROOMA KANPUR KANPUR NAGAR UTTAR PRADESH 209402 | KANPUR NAGAR | UTTAR PRADESH | 209402 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical 111 YADAV ELECTRIC MARKET G B MARG LATOUCHE ROAD LUCKNOW UTTAR PRADESH 226018 | LUCKNOW | UTTAR PRADESH | 226018 | Rejected-Technical Reject |
| 4 | Rejected-Technical | Rejected-Technical Reject |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
1 Sept 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GENERAL MANAGER
U.P. STATE SUGAR CORPORATION LTD., UNIT MOHIUDDINPUR, DISTT. MEERUT, U.P., PIN-250205
01- SUPPLY OF CAPACITOR PANEL 100 KVAR EACH WITH HARMONIC FILTER AND REACTOR- SEASON 2022-23
2022_UPSSC_718950_1
Moh/PD/2022-23/302 Dt. 30-07-2022
Open Tender
Miscellaneous
Item Wise
365 days
MOHIUDDINPUR (MEERUT)
Tender Fee, EMD and Other documents as per the tender document/NIT
2 documents required · 2 mandatory
₹590
U.P. State Sugar Corporation
₹25,000
16 Sept 2022
3 Aug 2022
2 Sept 2022
3 Aug 2022
1 Sept 2022
3 Aug 2022
4 X 25 KVAR= 100 KVAR Self heeling type (may be connected to APFC panel)Capacitor Bank In CRCA Sheet Steel2.00 thickness Enclosure/Housing Panelalongwith 3 phase, 415/440 V, 7%Detuned Copper BounedHarmonic Filter/Reactance confirming to IEC 61558-2-20&IEC 60076-6,H Class insulation (180 deg.C),High temp. Disconnection above 155 deg. C, Ambient temp. +60 deg. C with thermal cut off switch with 525 v Alluminium Bus bar should be 4 pole, ExhaustFans.wiring should be in copper wire , separate internal & external terminal for connection should be provided Reactance% As required for Each Paneltoovercome Harmonics, Linearity % OF Harmonic Filter-upto 200% with guranteecertificate.All measuring meters like amperemeter, voltmeter,pf meter & kwh meter etc& indicating lamps. Shunt Capacitor bank Specifications:- App Heavy Duty& IP20 mpp type super heavy duty confirming to to IS:13340-41/ IEC60831-1&2 , The Capacitor shall be fitted with discharge resistor, pressure sensitive disconnector ( psd) and shall have dissipation factor less than 0.0025 at 50HZ OPERATING LOSS Should be less than 0.25watt per kvar , min. over current capacity 1.8 times rated current & peak inrush current min 300times of rated current , 525 v should life expentency min 165000 hrs. ( rates may be quoted sepratly) Rating- 2x25 KVAR at- 440 V,525V As req. with reactance Freq.- 50Hz Connection – DELTA,ins. Class-H INS. LEVEL – 315 KV, Siemens, Snieder, /NEPTUNE.Price should be Quoted make wise of capacitors
Please enclose a copy of company prevailing price list with tender form duly signed and stamped if applicable.
Quantity may be increased or decreased at the time of placement of order.
ASIAN SWITCHGEAR PVT. LTD
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .