| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.2 LAccepted-AOC | L1 | Accepted-AOC Being the lowest and reasonable bidder | |
| 2 | L2₹17.6 L+₹1.9 L (12.1%)Rejected-AOC | L2 | Rejected-AOC Being the other than lowest bidder | |
| 3 | L3₹19.4 L+₹3.7 L (23.6%)Rejected-AOC C O SECTOR 02 HOUSING COLONY CHANNI HIMMAT JAMMU J K PIN 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L3 | Rejected-AOC Being the other than lowest bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
19 Apr 2022, 6:00 pmClosed
HQ CWE Nagrota
HQ CWE Nagrota Co 56 APO
REPAIR AND MAINTENANCE TO GOD, LT PANELS, HT PANELS, LIGHTNING ARRESTORS AND UG HT CABLES AND MISC ITEMS OF EXTERNAL ELECTRIC SUPPLY UNDER GE NAGROTA
2022_MES_514664_1
CWE/NGT-53/2021-22
Open Tender
Civil Works
Item Rate
182 days
Nagrota
As per NIT and tender documents
8 documents required · 8 mandatory
₹500
Yes
GE Nagrota
₹40,000
Yes
27 Apr 2022
22 Mar 2022
21 Apr 2022
22 Mar 2022
19 Apr 2022
5 Apr 2022
22 Mar 2022 - 29 Mar 2022
Amount
Calibration to HT RMU SF6 VCB type, 11 KV, 3 phase, 630 amps outdoor/ indoor type installed at sub stations after disconnecting the main supply incoming panel for repairs and replacement of unserviceable parts and refixing the same after repair and testing on full load from OEM or authorised dealer (Cost of spare parts and other job works will be paid under respective items) complete all as specified and directed. Note :- (a) Rates are deemed to include the cost of all tools, material and labour required for dismantling taking out and assembling of VCB with replacement of worn out nuts and bolts, gaskets, A grade greasing and oiling of moving parts and refixing the same. (b) Rates are deemed to include the cost of material and labour required to make alternative arrangement to bypass the electric supply through the HT panel or other HT line to avoid long period of shut down of electric supply.
Opening the VCB/RMU and replacing the single phase burnt motor of VCB/RMU with appropriate size of motor complete all as directed.
Repair of motor charging gear complete all as specified and directed.
Repair/replacement of lifting lock in and out complete all as specified and directed.
Replacement of burnt trip coil/MTD device assembly 24 V DC complete all as specified and directed.
Replacement of burnt closing coil assembly 24V DC complete all as specified and directed.
Replacement of burnt wiring including cut out switches complete all as specified and directed.
Replacement of TNT/auxiliary switch complete all as specified and directed.
Replacement of Vacuum interrupter complete all as directed
Replacement of VCB Power Pack with battery backup 24 DC complete all as directed
Replacement of Voltage Indicator lamps complete all as directed
Supply and Fixing of 3 phase digital type Amp meter 0- 120 Amp class 0.5 suitable for 11 KV RMU/ VCB to match the ratio of existing CTs complete all as specified and directed by Engr in Charge.
Supply and Fixing of 3 phase digital type Volt meter suitable for 11 KV VCB/RMU panel to match the ratio of existing CTs complete all as specified and as directed.
S & F in Replacement of 2 Volt battery bank ( UPST) comprising of 55 No cell of 165 AH each suitable complete all as directed by Engr-in-charge
Repair of battery Charger 415 V, AC 3 Phase 50 Hz 110 V out put 40 Amps output Current , 8.5 KVA Capacity
M&L for Servicing of LT Distribution Panels at Various Sub Stations, 415 V, and decorbonising complete contact points, cleaning of bus bar complete, oiling/greasing of moveable parts and replacement of burnt/unserviceable parts including checking of control wiring all as specified below and as directed:- Note:- Spares replaced shall be measured and paid under relerent items herein after. (a) Repair/ replacement of damaged hinges of each compartment (b) Taking down existing bus bars cleaning with CTC applying with becktol red solution, providing bus bar insulation and refixing with new nuts, bolts, washers etc. (c) Replacement of damaged copper flexible cable and fixing new copper flexible cable for incoming and out going connections of each MCCB/switches terminals to bus bars (d) Replacement of damaged/ worn out/ loose connections/ cable lugs for incoming & outgoing cables (e) Replacement of neoprene gasket for all doors of panel board. (f) Taking down rusted portion of sheet of feeder pillar boxes, damaged hinges etc and supply and fix new hinges heavy duty type, MS sheet patch work by cutting, welding and fabricating at site as required not exceeding 0.5 Sqm , painting with two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified.
Note : i) Cost for replacement of spares included in above quoted rates. ii) The rate shall be deemed to be included for replacement of worn out rusted hinges, bolts, split pins and cable lugs, cable glands and neoprene gasket to all doors including raising of foundation to 0.2 M height etc at places where directed by Engr-in-Charge., iii) Cost of replacement of MCCB's, repairs to MCCB's/SFUs not included in the scope of work. iv) Providing metallic tags with indication of starting and destination marking shall be provided for each cable as directed by Engr-in-Charge.
Suppy current Transformer of rating from 100/5 to 400/5 CT ratio in existing panel complete all as specified. Make : AE / Kappa
Supply Volt meter Digital type, 3 phase, 415 V in existing panel complete all as specified. Make : L&T Cat Part No : WDS301FEV00 or equivalent in Legrand / ABB / Siemens or equivalent make
Supply Ammeter digital type, 3 phase, 415 V in existing panel complete all as specified. Make: L&T Cat No. WDS301FCA00 or equivalent in Legrand / ABB / Siemens or equivalent make
Supply and fixing in replacement MCCB of capacity 630 amps, FP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 400 amps, FP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 320 amps, FP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 250 amps, TP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 200 amps, FP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 100 amps, TP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
Supply and fixing in replacement MCCB of capacity 63 amps, TP 415 volt with breaking cap 36 KA,including taking down existing MCCB complete all as specified.
S & F in replacement MCB TPN 32 Amp 415 volts 50 Hz AC 10 KA with necessary lugs including lugs, including taking down existing MCB complete all as specified.
S & F in repair MCB TPN 63 Amp 415 volts 50 Hz AC 10 KA with necessary lugs including lugs, including taking down existing MCCB complete all as specified.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in any type of soil for errection of HT/LT poles, laying of HT/LT UG cables and provn of stay assembly complete
All as per Item No- 29 here in before but depth beyond first 1.5 m and not exceeding 3 m.
Returning, filling in, including spreading levelling, watering and well ramming in layers not exceeding 25 cm thick in any type soil complete all as specified.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point and entire satisfaction of Engnr-in-Charge complete all as specified and directed
Sand (dry clean) as cushioning to underground electric cable all as specified in clause 19.75 of SSR Part -I 2009, and Spreading and levelling in layers for four pole Structure , MES Yard complete all as speficied.
Supplying and laying un-reinforced precast concrete cable cover, class HVP,type 1 with peak, size 300mm x 180mm x 40mm
Brick covering with width equal to length of brick as mechanical protection to cables with well burnt sub class ‘B’ (old size) bricks laid dry flat all as directed.
Supply, laying, jointing and testing XLPE cable insulated, armoured, heavy duty electric cable with aluminium conductor,HT 11000 volts grade, cross-sectional area 120 Sqmm 3 core, including taking down old unserviceable cable complete all as specified and directed .
All as per srl item No 36 here-in-before but cross-sectional area 95 Sqmm 3 Core.
Supply, laying, jointing and testing XLPE insulated PVC sheathed armoured under ground cable heavy duty with aluminium conductor LT 1100 V grade cross sectional area 185 Sqmm 3.5 core, including taking down old unserviceable cable complete all as specified and directed by Engineer-in-Charge
All as per srl item no 38 here-in-above but cross sectional area 120 sqmm 3.5 Core
Supply, fixing and erection truly in vertical position steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.00m long) including painting with two coats of synthetic enamelled, and making alternate white & black strips each 30cm wide upto 1.5 m above from coping including dismantling of existing Poles/Struts of any type and size and removing the same from site out side of MOD land complete all as specified and directed. Note:-The item are not for reuse and will be credited.
M&L for Cross arms, bracings, supports, clamps and chequered steel back plates, angle iron equal size or any size fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size for cover for cable duct any size and holding of two pole strucures, GOD, street light GI bracket, junction boxes and fabrication of anti climbing devices, other works etc as indicated or directed and duly painted with synthetic enamel aluminium/smoke grey paint over a coat of primer fixed "as in repairs" including dismantling cross-arms of M.S. channel or angle sections etc. complete all as specified and directed.
M&L for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete in foundation of pole/stays etc complete all as specified
M&L for PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete in foundation of pole/stays etc complete all as specified
M&L for PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregates) as in coping/above ground level around the pole etc complete all as specified.
Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 volts grade fixed "as in repairs" including dismantling insulators of any type and size complete all as specified. Make- BHEL/Jaipuria Brothers/Seimens or equivalent from the makes given in particular specifications.
Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green 'Two-in-series' assembly for tension with tension clamps for conductors working pressure 11000 volts grade fixed "as in repairs" including dismantling insulators of any type and size complete all as specified. Make- BHEL/Jaipuria Brothers/Seimens or equivalent from the makes given in particular specifications.
All as per Srl item No. 46 here in before but for single disc assembly.
Loop type insulator, vitreous porcelain, white, brown or green large size, with overall dimensions 90x140mm, clearance of hole 25.5mm fixed "as in repairs" including dismantling insulators of any type and size complete all as specified. Make- BHEL/Jaipuria Brothers/Seimens or equivalent from the makes given in particular specifications.
Painting of 11 mtr long steel pole with cross arms, clamp of any length and shape for HT overhead line with two coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 20 cm dia yellow circle & marking three black & two yellow bends width 30 cm by fluorescent paint from bottom of pole to 1.5 Mtr height, complete all as specified and directed.
Aluminium conductor, steel reinforced of any size on HT/LT Poles including straining,binding with insulators with Al/copper binding wire with insulators as in OH conductors, providing PVC Sleeves for jumper fixed "as in repairs" including dismantling of ACSR or AAC conductors of any size complete all as directed.
Switch air break gang operated (Swing out expulsion fuse insulators), triple pole mechnical operated from ground level mounted on insulator and steel frame (15 insulators type) out door type suitable for vertical installation single break provided with locking arrangement consisting of MS channel HT post top insulator with drop out fuses operating rod 20mm dia GI medium grade pipe worked from ground level confirming of IS 1818 of 1972 and contineous current rating upto 200 amp and volt 11 KV complete fixed "as in repairs" including dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism any type,any size and removing the same from site out side of MOD land complete all as specified and directed. Make: BHEL/PACTIL or equivalent from the makes given in particular specifications.
All as per srl item No 44 above but of current rating 400 amps.
Lightning arrestor non linear resistor type complying with IS 3070 Part -I 1985 for alternating current system multple spark gap suitable for voltage grade 11000 volt having discharge capacity 65 KA complete with all fittings and all as specified.
Earthing complete with galvanised mild steel earth plate electrode 60x60cmx6mmthick buried directly in ground preferably in vertical position (Earth pit not less than 2.25 mtr below ground level) with top edge of the earth plate not less than 1.5 mtr below normal ground level connected to galvanised iron strip of size 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron including PCC pit 1:2:4 type B-1 pre cast RCC cover slab of size 550x550x75mm with suitable built in handle made from 12mmdia MS round bar, excavation and earth work in any type of soil 20mm dia bore medium grade galvanised iron water tubing fixed with cast iron funnel and wire mesh at one end and 15mm bore light grade galvanised iron protection pipe for earth lead wire upto 5m length, charcoal, common salt complete all as shown in electric plate No 3 of SSR 2009 Part I connected to equipment complete all as specified and testing on completion
Aluminium strip of size 25 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specified.
GI strip of size 32 x 6 mm for earth continuity conductor or main earthing lead fixed to wall buried in ground fixed alongwith poles complete all as specified.
Copper strip of size 32 x 6 mm for earth continuity conductor or main earthing lead fixed to wall buried in ground fixed alongwith poles complete all as specified.
Supply, installation, testing & commissioning of advanced free tripod ring earthing system by boring the required no of holes in semi hard soil or hard soil consisting of three Nos UL 467 listed and CPRI Attested copper bonding high tensile low carbon steel core electrode of 17.2 mm dia with a minimum coating thickness of 250 microns and length of 3 meters tested according to IEC 625612 with min 10 years of life span (the rod should be marked as per the UL certification) AGE APLI with down side GI plate (1 f x 1 f) attached with GI 40 MM tube as outer covered of electrode internally and externally covered with compound minimium 3x25 KG bags electrode of earth enhancing compound for the earthing pit electrode in one tripod earthing minimum 06 electrode to be fixed considering as 1 earthing. The enhancing compound should have resistivity less than 50 Ohm Meter with chemically insert to sub soil that should not pollute the environment and non corrosive to the earth electrode itself tripod connected to 25x3mm copper strip. Result of earthing should be less than 01 Ohm up to satisfaction of Engr-in -Charge.
Copper bonding arrestor of length 1 meter and GI pole of length 3 meter having dia 60 mm with copper wire (10 Nos) of length 15 meter for isolated installation, complete all as specified.
Tubular Earthing GI Electrode of outer dia 50 mm with solid rod dia 20 mm (inner) having length 2 mtr of galvanised 80-100 microns backfill compound ( 01 bag 25 KG ) with pit cover complete all as specified.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed. Make 3M India Ltd / M seal / Denson or equivalent from the makes given in particular specifications.
All as per Srl item No. 62 here in before but for cable of cross sectional area 120 to 185 sqmm.
All as per Srl item No. 62 here in before but for cable of cross sectional area 240 to 300 sqmm.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed. Make 3M India Ltd / M seal / Denson or equivalent from the makes given in particular specifications.
All as per Srl item No. 65 here-in-before but for cable of cross sectional area 120 to 185 sqmm.
All as per Srl item No. 65 here in before but for cable of cross sectional area 240 to 300 sqmm.
M&L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm.
All as per Srl item No. 68 here in before but for cable of cross sectional area 120 to 185 sqmm.
Labour and tools for trimming tree branches up to 100 mm grith of any location around existing HT/LT OH lines giving clearance of 1.5 m on all sides after arranging shut down and taking all precaution while working on lines including all T&P required for the purpose complete all as specified and directed by Engineer-in- charge. (Note - Trimming of tree branches irrespective in numbers in each span shall be measured as one unit)
Material and labour for spreading and leveling evenly (any thickness) 20 mm graded stone aggregates complete all as specified and directed.
Material and labour for spreading and leveling evenly (any thickness) 40 mm graded stone aggregates complete all as specified and directed.
Note:- Schedule of credit Rs. 55,230.50 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents.
ARNABH ASSOCIATES
MAMTA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .