Loading…
Loading…
Tender Value
₹9.8 L
EMD Value
₹20,000
Closing Date
24 Sept 2026, 6:00 pm
AGE (I) Nyoma
AGE (I) Nyoma PIN-901313 C/o 56 APO
Misc repair / maint work of various external electric supply items, LT panals, under ground cable and other allied wks at Zone -I under AGE (I) Nyoma
2026_MES_787581_1
8100/NIT-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE (I) Nyoma
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
AGE (I) Nyoma
₹20,000
3 Sept 2026
3 Sept 2026
26 Sept 2026
3 Sept 2026
24 Sept 2026
17 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking out un-serviceable/faulty cable/service connection cable of any grade / type / class of any size for repair / replacement from pole / wall / cable duct under ground trench etc for re-use or removal from site of work all as specified and as directed by the Engineer-in-charge (Note- Excavation and earth work shall be measured and paid separately) | 900 | RM | - | - |
| 2 | Supply, laying,fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 2 core 16 sqmm, complete all as specified and directed by Engr-in-Charge. | 200 | RM | - | - |
| 3 | Supply, laying,fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 4 core 16 sqmm, complete all as specified and directed by Engr-in-Charge. | 200 | RM | - | - |
| 4 | Supply, laying,fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 3.5 core 35 sqmm , complete all as specified and directed by Engr-in-Charge. | 200 | RM | - | - |
| 5 | Supply, laying,fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 3.5 core 50 sqmm, complete all as specified and directed by Engr-in-Charge. | 150 | RM | - | - |
| 6 | Supply, laying,fixing, passing through pipe or laid in trenches and testing underground XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 3.5 core 70 sqmm, complete all as specified and directed by Engr-in-Charge. | 150 | RM | - | - |
| 7 | Supply and fixing Aluminium bus bar chamber 3 phase, 200 Amp capacity with 4 nos Al strips not less than 600 mm long, outdoor type including one MCCB of 125 Amps 4 Pole as incommer with locking arangement, grouting in pcc 1:3:6 and connecting with UG XLPE cable with suitable copper thimbles, complete all as specified and directed by Engr-in-Charge. | 4 | Each | - | - |
| 8 | M&L for Earthing complete with galvanized steel earth plate electrode 600x600x60mm thickness not less than 6mm thick buried directly in ground( earth plate not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 2.5 mtr below the normal ground level connected to galvanized iron wire 4 mm dia by means of nuts bolts, nuts, check nuts and washers of GI steel all as shown in electrc plate Ni 5 connected to earth test point all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe light grade 40mm bore and GI watering pipe 20mm bore medium grade with funnel and wire mesh ,40mm thick pre cast RCC M-15 ( Nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40X40X3mm frame for cover,PCC M-15 ( Nminal mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed by Engineer-in-charge. | 3 | Each | - | - |
| 9 | Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtrs in depth for laying of cable, fixing of stay etc 10 Sqm on plan and n exc 1.5 in depth and getting out in hard/dence soil complete all as specified and directed by Engineer-in-Charge. | 227.5 | Cum | - | - |
| 10 | Returing, filling in incl spreading, levelling watering and well remming in layers n.exc 25cm width, Complete all as specified and directed by Engineer-in-Charge. | 124.2 | Cum | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.15 MB
Tender25.pdf
Tender Documents • 0.74 MB
BOQ_882684.xls
BOQ • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .