| 1 | L1₹7.7 LAccepted-AOC 5 31 EWS PREETAM NAGAR ALLAHABAD 211011 | ALLAHABAD | ALLAHABAD | UTTAR PRADESH | 211011 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹8.5 L+₹62,620 (7.95%)Rejected-Finance 2 2 BLOCK B MAYUR RESIDENCY MISRAPUR KURSI ROAD LUCKNOW 226026 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226026 | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹9.8 L+₹1.9 L (24.3%)Rejected-Finance 161 SADAR BAZAR SADAR BAZAR CANTT AYODHYA UP PIN 224001 | AYODHYA | AYODHYA | UP | 224001 | L3 | Rejected-Finance Not Being L1 |
| Sl No | Description | Qty | Unit | M/S vibhuti enterprises L1 | FUTURE Inc. L2 | Jairajyadav security services L3 |
|---|---|---|---|---|---|---|
| 1.00 | M&L for attending complaints/ breakdowns of AMF panel including disconnecting and general maintenance, cleaning, dusting replacement of minor parts i.e. lugs, parts of Logic control unit, MCB,indicator lamps etc and sercicing of ATS/isolators/circuit breakers/Control unit/CT /door hinges/Handle with oiling greasing etc to make completely functional in all respect and testing after completion of job all as specified and directed by Engr-In-Charge
Note:- Major spare parts required for AMF panel shall be measured and paid for seperately under relevant item of BOQ. | 2 | Each Job | 2,000 ₹4,000 | 10,000 ₹20,000 | 650 ₹1,300 Lowest |
| 2.00 | Disconnecting & taking out of existing AMF panel of any description and in any position, of 62.5/ 63KVA capacity DG set & opening of AMF Panel, checking AC/DC circuits and replacement control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load after completion of repairs complete all as speicified and directed.
Note : The quoted rates shall deem to be included for fixing the serviceable parts in position. The new parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only. Replacement of small/minor parts such as nuts, bolts, washers/lugs/gaskets etc shall also deem to be included in the rates quoted against the item. | 2 | Each Job | 2,500 ₹5,000 | 10,000 ₹20,000 | 1,850 ₹3,700 Lowest |
| 3.00 | S&F in replacement of CT 50/5 to 200/5 complete all as specified and as directed. | 2 | Each | 400 ₹800 | 300 ₹600 Lowest | 1,250 ₹2,500 |
| 4.00 | S&F in replacement of Solenoid switch 12/24 Volts with relay of suitable capacity complete all as specified and as directed. | 2 | Each | 1,000 ₹2,000 Lowest | 2,500 ₹5,000 | 5,000 ₹10,000 |
| 5.00 | S&F in replacement of Electronic timer 24 volts AC/DC complete all as specified and as directed. | 2 | Each | 2,000 ₹4,000 | 1,000 ₹2,000 Lowest | 2,600 ₹5,200 |
| 6.00 | S&F in replacement of Engine start relay 24 DC complete all as specified and as directed. | 2 | Each | 1,500 ₹3,000 | 1,200 ₹2,400 Lowest | 3,200 ₹6,400 |
| 7.00 | S&F in replacement of Selector switch of suitable capacity as per site requirement complete all as specified and as directed. | 4 | Each | 300 ₹1,200 Lowest | 450 ₹1,800 | 550 ₹2,200 |
| 8.00 | S&F in replacement of AMF Panel outdoor type, 62.5KVA DG Set with aluminium busbar of capacity 200 Amps, TPN powder coated (coloured ) heat shrinkable sleeves, 3mm CRCA sheet steel enclosure duly powder coated and inbuilt on load change over switch of four pole 100 Amps.The amf panel should mount on angle iron of 3Ft height of size 50x50x6mm includiing PCC and necessary excavation consisting the following:- | 3 | Each | 1,07,000 ₹3,21,000 Lowest | 1,20,000 ₹3,60,000 | 1,16,000 ₹3,48,000 |
| 8.01INCOMING from 62.5 KVA (i) MCCB 100 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Spreaders Link - 01 Set (iii) Extended Rotary handle - 01 No (iv) Power Contactor 100 Amp FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 Volts AC - 01 No (vi) C.T. 100/5A CL-1.0 10 VA - 06 Nos (vii) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Indicating lights (Red-2, Yellow-2. Green-2) (ix) Control MCB 6A SP 10 KA C curve (x) VMR - 01 No (xi) In built on load change over switch four pole 100A for bypassing of AMF panel - 01 No | ||||||
| 8.02Outgoing (i) MCCB 100 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Power Contactor 100 Amps FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 V AC - 01 No (iiI) AMF RELAY CARD 01 Nos (iv) BATTERY CHARGER 12V, DC, 10A - 01 No (v) Emergency stop P.B - 01 No (vi) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Control MCB 6A SP 10 KA C Curve (ix) Hooter - 01 No (x) PROCOM UNIT (DGC6D) FOR control - 01 No (xi)Extended Rotary handle - 01 No (xii) Engine start Relay -01 Nos | ||||||
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
10 Dec 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) Ayodhya Cantt
Asst Garrison Engineer (I), Military Engineer Services, Ayodhya Cantt PIN-224001
REPAIR/ REPLACEMENT TO UNSV/OLD AMF PANEL AT SIGNAL CENTRE/AMN DUMP/MH AND CERTAIN ALLIED WORKS UNDER AGE(I) AYODHYA
2025_MES_740383_1
8400/144/E8
Open Tender
Civil Works
Item Rate
180 days
Ayodhya Cantt
Please refer tender documents
8 documents required · 8 mandatory
₹500
AGE (I) Ayodhya Cantt
₹20,000
Yes
11 Mar 2026
18 Nov 2025
12 Dec 2025
18 Nov 2025
10 Dec 2025
3 Dec 2025
Amount
M&L for attending complaints/ breakdowns of AMF panel including disconnecting and general maintenance, cleaning, dusting replacement of minor parts i.e. lugs, parts of Logic control unit, MCB,indicator lamps etc and sercicing of ATS/isolators/circuit breakers/Control unit/CT /door hinges/Handle with oiling greasing etc to make completely functional in all respect and testing after completion of job all as specified and directed by Engr-In-Charge Note:- Major spare parts required for AMF panel shall be measured and paid for seperately under relevant item of BOQ.
Disconnecting & taking out of existing AMF panel of any description and in any position, of 62.5/ 63KVA capacity DG set & opening of AMF Panel, checking AC/DC circuits and replacement control wiring with 1.5 Sqmm, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items, reassembling the panel & fixing the same in position and testing the AMF panel on full load after completion of repairs complete all as speicified and directed. Note : The quoted rates shall deem to be included for fixing the serviceable parts in position. The new parts shall be measured and paid for separately under appropriate item of Sch `A’ as `supply only. Replacement of small/minor parts such as nuts, bolts, washers/lugs/gaskets etc shall also deem to be included in the rates quoted against the item.
S&F in replacement of CT 50/5 to 200/5 complete all as specified and as directed.
S&F in replacement of Solenoid switch 12/24 Volts with relay of suitable capacity complete all as specified and as directed.
S&F in replacement of Electronic timer 24 volts AC/DC complete all as specified and as directed.
S&F in replacement of Engine start relay 24 DC complete all as specified and as directed.
S&F in replacement of AMF Panel outdoor type, 62.5KVA DG Set with aluminium busbar of capacity 200 Amps, TPN powder coated (coloured ) heat shrinkable sleeves, 3mm CRCA sheet steel enclosure duly powder coated and inbuilt on load change over switch of four pole 100 Amps.The amf panel should mount on angle iron of 3Ft height of size 50x50x6mm includiing PCC and necessary excavation consisting the following:-
INCOMING from 62.5 KVA (i) MCCB 100 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Spreaders Link - 01 Set (iii) Extended Rotary handle - 01 No (iv) Power Contactor 100 Amp FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 Volts AC - 01 No (vi) C.T. 100/5A CL-1.0 10 VA - 06 Nos (vii) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Indicating lights (Red-2, Yellow-2. Green-2) (ix) Control MCB 6A SP 10 KA C curve (x) VMR - 01 No (xi) In built on load change over switch four pole 100A for bypassing of AMF panel - 01 No
Outgoing (i) MCCB 100 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Power Contactor 100 Amps FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 V AC - 01 No (iiI) AMF RELAY CARD 01 Nos (iv) BATTERY CHARGER 12V, DC, 10A - 01 No (v) Emergency stop P.B - 01 No (vi) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Control MCB 6A SP 10 KA C Curve (ix) Hooter - 01 No (x) PROCOM UNIT (DGC6D) FOR control - 01 No (xi)Extended Rotary handle - 01 No (xii) Engine start Relay -01 Nos
S&F in replacement of AMF Panel outdoor type, 160KVA DG Set with aluminium busbar of capacity 400 Amps, TPN powder coated (coloured ) heat shrinkable sleeves, 3mm CRCA sheet steel enclosure duly powder coated and inbuilt on load change over switch of Four pole 250 Amps.The amf panel should mount on angle iron of 3Ft height of size 50x50x6mm includiing PCC and necessary excavation consisting the following:-
INCOMING (i) MCCB 250 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Spreaders link- 01 Set (iii) Extended Rotary handle - 01 No (iv) Power Contactor 250 Amp FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 Volts AC - 01 No (vi) C.T. 400/5A CL-1.0 10 VA - 06 Nos (vii) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Indicating lights (Red-2, Yellow-2. Green-2) (ix) Control MCB 6A SP 10 KA C curve (x) VMR - 01 No (xi) In built on load change over switch 250A four pole for bypassing of AMF panel - 01 No
Outgoing (i) MCCB 250 Amp microprocessor release type Four Pole ,Breaking capacity 36 KA,ICS=100% of ICU - 01 No (ii) Power Contactor 250 Amps FP AC1 Duty with 2 NO and 2 NC Aux block coil voltage 220 V AC - 01 No (iiI) AMF RELAY CARD 01 Nos (iv) BATTERY CHARGER 24V, DC, 10A - 01 No (v) Emergency stop P.B - 01 No (vi) Digital MF meter with 485 Port - 01 No for parameters VLL,VLN,A,PF,F,HOURS,A PEAK ACCURACY CLASS 0.5 (viii) Control MCB 6A SP 10 KA C Curve (ix) Hooter - 01 No (x) PROCOM UNIT (DGC6D) FOR control - 01 No (xi)Extended Rotary handle - 01 No (xii) Engine start Relay=01 NOs
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core complete all as specified and directed.
Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cable ( heavy duty ) 1100 volts grade with stranded aluminium conductor of size 185 sqmm 3.5 core complete all as specified and directed.
Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in soft/loose soilcomplete all as specified and directed by Engr-in-Charge.
Removing excavated materials (soil) n. exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed by Engr-in-Charge.
M & L for sand cushioning to underground cable with clean dry river sand complete all as specified and directed by Engr-in-Charge. Note:- Punned thickness only shall be measured & Paid.
Supply & Laying of sub class 'B'bricks locally available best quality laid flat (length of bricks laid across the length of cable) in tranches for protection of U/G cable complete all as specified and directed by Engr-in-Charge.
M&L Earthing complete with galvanized steel plate elecrode of size 60 cm x 60cm x 6.0 mm thick burried directly in ground vertically to a depth not less than 2.5 mtr below the ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt, connected with GI strip 25x4mm by means of bolts , nuts, check nuts and washers of galvanised iron with thimbles. The other end of GI strip is connected to main switch board and protected by light grade GI pipe of 15 mm bore. provision of 20mm bore light grade GI pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horizontally to the equipment. Cement concrete chamber of PCC ( 1:3:6 ) type C-2 using 40 mm graded stone aggregate.The chamber shall be constructed one metre away from edge of earth pit. 50 mm thick pre cast cover of cement conrete (1:2:4) type B-1 using 20 mm graded stone aggregate, excavation in soft / loose soil, returning filling and removal of surplus soil to a distance of 50 mm as directed and shown in Electrical Plate No- 3 of SSR Part-1 (2009).
Supply and fix in repair earth lead GI strip 25x4mm complete all as specified and directed
S & F in replacement on load Changeover switch 4 pole 100 Amp, 415 volt, open execution type of make: L&T or equivalent in C&S, Scheinider,siemens in existing panel including taking out of old one all as specified and as directed by Engr-in-charge.
S&F in replacement on load Changeover 4 pole 100 Amp, 415 volt, in sheet steel enclosure type of make: L&T or equivalent including taking out of old one all as specified and as directed by Engr-in-charge.
S & F in replacement On load Changeover 4 pole 250 Amp, 415 volt, in sheet steel enclosure type of make: L&T or equivalent including taking out of old one all as specified and as directed by Engr-in-charge.
S & F MCCB 3 pole 100 Amp, 415 volt, Breaking capacity 30 KA,ICS=100% of ICU of make: L&T or equivalent in C&S, Scheinider,siemens in existing panel including taking out of old one all as specified and as directed by Engr-in-charge.
S & F MCCB 4 pole 100 Amp, 415 volt, Breaking capacity 30 KA,ICS=100% of ICU of make: L&T or equivalent in C&S, Scheinider,siemens in existing panel including taking out of old one all as specified and as directed by Engr-in-charge.
Supply only lead acid battery 12 volt 180 Ah including initial charge of make: Exide or equivalent complete all as directed by Engr-In-Charge
M&L for complete servicing of servo voltage stabilizer of 50 KVA of make: Servostar / Vinitec or any other make as per site requirement and connected accessories including repair/replacement of defected old parts like Variac,Variac base,RC network,carbon brush, micro switch, spring ,hexa, stopper, push button,SPDT & DPDT Switches,servo motors, oil / lubricant to keep the plant in running condition including routine maintenance complete all as specified and as directed. [Note: (i) The Contractor need to get the job done through authorised service centre/ agency of OEM (Original Equipment Manufacturer).The cost thereof deemed to be included in the quoted rate. (ii) Labour charges for routine maintenance including properly dismantling of old parts deemed to be included in the quoted rate]
Disconnecting electrically incomming and outgoing LT UG cable of LT panel of any size and replace burn/unsv suitable size of aluminium bus bar, Welding work for hinches and doors, fixing the locking arrangement including scraping outdoor/indoor side of LT Panel and one coat of redoxide, two coat of synthetic enamelled seimens gray spray of outdoor/Indoor side and reconnecting LT UG cable with fixing aluminium lugs by using crimping tool, nut, bolt washer etc and all necesary work required for smooth functioning of LT panel all specified and directed by Engr-in-Charge.
Supply and fix heat shrinkable End termination kits and accessories of following capacities and type:-
Outdoor/indoor 35 to 50 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Outdoor/indoor 70 to 120 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Outdoor/indoor 150 to 185 Sqmm 3.5/4 core cable jointing kit for 1.1 KV grade cable
Supply and lay DWC HDPE pipe 50 mm bore medium class, ISI Marked double wall corrugated for open/underground laying cable, cut to size and making the tubing for cable protection including cutting of road etc/cutting of PCC and making the good surface complete all as specified and directed by Engr-in-Charge. Note :-(a) The using of GI Clamp in the wall/drainage rate are deemed to be included in the quoted rate. (b) The insulation of DWC pipe should be of high that does not deteriorate with UV rays/ heavy sun rays/winter season etc. (c) Drawing existing cable through DWC pipe shall be deemed to be included in the quoted rates. as in cable protection pipe of outer dia 40mm including all fittings complete all as specified and directed.
FUTURE Inc. (BID ID -3493648)
Jairajyadav security services (BID ID -3494357)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Document
0.45 MB
Tender Documents
Tender Documents • 0.70 MB
BOQ
BOQ • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .