Tender Value
₹27.7 L
EMD Value
₹55,500
Closing Date
1 Mar 2023, 6:00 pmClosed
COL VIKAS KESARWANI
HQ CWE AF LOHEGAON
SPECIAL REPAIR REPLACEMENT TO OLD TRANSFORMER AT SUB STATION NO 1 AND 2 AT SITE P AT AFS THANE UNDER GE (AF) THANE
2023_MES_578855_1
82637/E8
Open Tender
Civil Works
Item Rate
180 days
GE AF THANE
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE AF THANE
₹55,500
Yes
10 Apr 2023
3 Feb 2023
8 Mar 2023
3 Feb 2023
1 Mar 2023
17 Feb 2023
Amount
Taking down Old unsv Transformer & deposited to MES stored yard back and Supply & fixing , Testing & commissioning of Transformer 250 KVA ,22000V/433V , 3 phase,50C/s oil Immersed,naturally cooled outdoor type transformer having no load voltage ratio 22000/433V ,Vector group Dyn 11 with 2½±5±7½% in step of 2.5% tapping as under taken out on the HT side and connected to externaly hand operated 22 KV OFF circuit tap changing switch, HT winding connected in delta and LT winding conected in star and neutral brought out and connected to a seprate terminal for earthing with outdoor open porcelain bushing on HV side and cable box on LV side with the temperature rise not exceeding 40 ﮿c by thermometre in oil and 45 ﮿ c by resistance and ambient temperature 45 ﮿ c with first filing of oil with following(Copper double wound) complete with all conections as specified and as directed by engineer in charge. Note :- The Under Mentioned Fitting and Acessories are required to Meet the Complete Requirement as Per IS-1180, Z% - 4.5 (a) 22 KV Externally hand operated OFF cuircuit Tap changing switch with locking device. (b) Conservator tank with oil gauge Glass, Oil filling hole with plug, drain plug and filling cap. (c) Silica gel dehydrating breather charged with silica gel. (d) Oil level gauge. (e) Oil filter valve. (f) Oil drain valve. (g) Thermometre pocket. (h) Diagram and rating plate. (j) Two earthing arrangement. (k) Lifting lugs, Top Cover Lugs. (l) Bidirectional plain roller - 04 Nos. (m) Air vent plug. (n) Explosion vent. (o) Bare bushings on HV side. (p) Cable box on LV Side. (q) Additional neutral terminal brought outside the LV cable box for earthing
Taking down Old unsv Transformer & deposited to MES stored yard back and Supply & fixing , Testing & commissioning of Transformer 315 KVA ,22000V/433V , 3 phase,50C/s oil Immersed,naturally cooled outdoor type transformer having no load voltage ratio 22000/433V ,Vector group Dyn 11 with 2½±5±7½% in step of 2.5% tapping as under taken out on the HT side and connected to externaly hand operated 22 KV OFF circuit tap changing switch, HT winding connected in delta and LT winding conected in star and neutral brought out and connected to a seprate terminal for earthing with outdoor open porcelain bushing on HV side and cable box on LV side with the temperature rise not exceeding 40 ﮿c by thermometre in oil and 45 ﮿ c by resistance and ambient temperature 45 ﮿ c with first filing of oil with following(Copper double wound) complete with all conections as specified and as directed by engineer in charge. Note :- The Under Mentioned Fitting and Acessories are required to Meet the Complete Requirement as Per IS-1180, Z% - 4.5 (a) 22 KV Externally hand operated OFF cuircuit Tap changing switch with locking device. (b) Conservator tank with oil gauge Glass, Oil filling hole with plug, drain plug and filling cap. (c) Silica gel dehydrating breather charged with silica gel. (d) Oil level gauge. (e) Oil filter valve. (f) Oil drain valve. (g) Thermometre pocket. (h) Diagram and rating plate. (j) Two earthing arrangement. (k) Lifting lugs, Top Cover Lugs. (l) Bidirectional plain roller - 04 Nos. (m) Air vent plug. (n) Explosion vent. (o) Bare bushings on HV side. (p) Cable box on LV Side. (q) Additional neutral terminal brought outside the LV cable box for earthing
M&L for earthing complete with Copper earth plate electrode 600x 600x 3.15 mm buried directly in ground with top edge of the plate not less than 1.5 mtrs below normal gound level and connected to earth test point by means of copper Strip of size 20x3 mm all as specified and shown in electric plate No 3 of MES SSR Part-I 2009 including earthwork, PCC chamber, CI cover, protection and watering pipe, funnel, mesh etc all as required at site and all as directed. Note: (i) 7.5 RM Copper strip in deemed to be included in quoted rates beyond 7.5 RM strip shall be measured and paid separately. (ii) Earth resistance of earth pit should be less than 0.5 Ohms. On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost. (iii) Rate quoted by the tenderer is deemed to include salt & Charcoal upto & above 450 mm top of Copper plate complete all as specified and directed by engineer in charge.
Supplying, jointing and commissioning indoor/outdoor type cable end termination jointing kit heat shrinkable type suitable for under ground XLPE cable size 3 core 95 Sqmm HT cable complete all as specified and directed by engineer in charge.
Supplying, jointing and commissioning outdoor type cable end termination jointing kit heat shrinkable type suitable for under ground XLPE cable size 3.5 core 240 Sqmm LT cable complete all as specified and directed by engineer in charge .
Taking down old unsv cable and supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 22000 volts grade, of size 3 core 95 sq mm complete all as specified and directed by engineer in charge
Taking down old unsv cable and supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 240 sq mm complete all as specified and directed by engineer in charge
Taking down old unsv and supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts grade, of size 3.5 core 300 sq mm complete all as specified and directed by engineer in charge
sapana enterprises
Veer High Tech Solution
MONA GENERATOR SEVICES PVT. LTD.
somnath engineering corporation
M/s Mukesh Engineers
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .