HE RAC
room no 225 department of hospital Engineering and planning RAC division
Replacement of 4 Nos existing AHUs with new AHUs having combination of chilled water DX type coil for O Ts at Advanced Eye Care Centre PGIMER Chandigarh
2026_PGIME_910982_1
PGI/Engg/RAC/2026/314
Open Tender
Miscellaneous Works
90 days
Eye Care centre
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹1.3 L
1 Jun 2026
1 Jun 2026
12 Jun 2026
1 Jun 2026
11 Jun 2026
1 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount | Item Code |
|---|---|---|---|---|---|---|
| 1Supply, Installation ,Testing and commissioning of sheet metal sectionalized construction double skin AHU , complete with chilled water coils of copper tube and aluminum fins construction , squirrel cage induction motor , DIDW BACKWARD CURVE centrifugal fan , V-belt drive package (including taper lock pulley arrangement) and vibration isolation (spring mounted). The AHU shall have 25 mm thick panels made out of 0.8 mm thick external Galvanized steel sheet (scratch free plastisol coating) and internal Aluminum sheets of thickness 0.8 mm, with PUF injection inside and static pressure of AHU is 135 mm with HEPA filter. Cooling coil section with 6 rows deep chilled water coil (3 + 3 combination), Heating coil 2 row deep, Cooling coil DX type 3 row deep and gap between all the coils minimum 450 mm and coil tube thickness 0.5 mm.PUF (40 kG/CuM density) injection would be done in a controlled factory environment, by using a PUF injection molding machine. The blower shall be of approved make and specifications, AMCA certified-210 and AMCA 300. Entire unit vibration level as per ISO 2372/3945. The AHU assembly shall be complete with electrically inter-locked fan guard, access doors with nylon hinges, nylon door locks handles, port holes in fan section, sealed screw end caps , internal light and limit switches , SS drain pan & Discharge of AHU etc. Floor mounted AHU motor shall be three phase motor suitable for VFD drive. Motor shall be IE-3. AHU will be compatible with BMS system | ||||||
| 1.01 | 5000 CFM | 1 | No. | 6,99,931 | ₹6,99,931 | BI01010001010000000000000515BI0100001114 |
| 1.02 | 6200 CFM | 2 | No. | 7,64,228 | ₹15,28,456 | BI01010001010000000000000515BI0100001115 |
| 2Supply, Installation ,Testing and commissioning of sheet metal sectionalized construction double skin AHU , complete with chilled water coils of copper tube and aluminum fins construction , squirrel cage induction motor , DIDW BACKWARD CURVE centrifugal fan , V-belt drive package (including taper lock pulley arrangement) and vibration isolation (spring mounted). The AHU shall have 25 mm thick panels made out of 0.8 mm thick external (scratch free plastisol coating) and internal GSS pre-painted sheets of thickness 0.8mm, with PUF injection inside and static pressure of AHU is 65 mm with Micro filter. Cooling coil section with 6 rows deep chilled water coil (3 + 3 combination), gap between the coils minimum 450 mm and coil tube thickness 0.5 mm.PUF (40 kG/CuM density) injection would be done in a controlled factory environment, by using a PUF injection moulding machine. The blower shall be of approved make and specifications, AMCA certified-210 and AMCA 300. Entire unit vibration level as per ISO 2372/3945. The AHU assembly shall be complete with electrically inter-locked fan guard, access doors with nylon hinges, nylon door locks handles, port holes in fan section, sealed screw end caps , internal light and limit switches , SS drain pan & Discharge of AHU etc. Floor mounted AHU motor shall be three phase motor suitable for VFD drive. Motor shall be IE-3. AHU will be compatible with BMS system | ||||||
| 2.01 | 10000 CFM | 1 | No. | 5,31,184 | ₹5,31,184 | BI01010001010000000000000515BI0100001117 |
| 3Supply, Installation, Testing & commissioning of Outdoor units with twin compressors, statically dynamically balanced centrifugal blower, multi rows cooling coil internally grooved copper tube with Aluminum fins, Inbuilt safety devices for compressor protection like thermal protector, Internal pressure, cutout enclosure shall be equipped with synthetic filter with following capacity. | ||||||
| 3.01 | 16.5 TR Outdoor Condensing unit. (2 Compressor) (Refrigerant - R 410/407) | 2 | No. | 2,90,690 | ₹5,81,380 | BI01010001010000000000000515BI0100001119 |
| 3.02 | 11 TR Outdoor Condensing unit (2 Compressor) (Refrigerant - R 410/407) | 1 | No. | 2,09,407 | ₹2,09,407 | BI01010001010000000000000515BI0100001120 |
| 4Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for HVAC system, complete with fittings ,with suitable adjustable ring type hanger supports, jointing / brazing including accessories, insulated with XPLE Class-O tubular insulation with Class-O closed cell elastomeric nitrile rubber tubular sleeves section so specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required : | ||||||
| 4.01 | 28.58mmdia(OD)(Harddrawn)with tube thickness 1.2mm with 19mm thick insulation | 50 | Rmt | 1,108 | ₹55,400 | BI01010001010000000000000515BI0100001122 |