GE (AF) Gurgaon
Gurgaon
SPECIAL REPAIR REPLACEMENT OF CERTAIN WORN OUT WIRING, DBs SUBMAINS CONTROL PANEL OF PUMP HOUSE NO 02 07 TEJAS ENCLAVE AND CLORINATION SYSTEM ALONGWITH FITTINGS AND FIXTURES AT TEJAS ENCLAVE AT AFSSR UNDER GE AF GURGAON
2022_MES_569575_1
CA NO GE/GUR-/NIT-53/2022-23
Open Tender
Miscellaneous Works
Piece-work
240 days
GE (AF) Gurgaon
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
₹98,000
28 Jan 2023
16 Dec 2022
16 Jan 2023
16 Dec 2022
13 Jan 2023
30 Dec 2022
Amount
Taking down carefully copper/aluminium point wiring (light, Fan, Socket or power) fitting such as switches, ceiling roses, pendents, regulators, sockets etc complete removing material to store for keeping in safe custody and making good disturbed surfaces of walls, floors etc all as specified as directed.
Taking unserviceable sub main wiring of any type/size including wires, conduits/battens etc complete all as specified and directed by Engr-in-Charge.
Taking down unserviceable MCB DB's/AC's box of any size/rating complete all as specified and directed by Engr-in-charge.
M&L for point wiring complete with stranded copper conductor 1.5 Sqmm size (Nominal area) PVC insulated unsheathed FRLS Grade cable 1100 volts grade confirming to IS: 694 for phase and neutral drawn in and including medium duty concealed PVC conduit confirming to ISI marked not less than 20mm dia with concealed sunk-in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and painted with stove enamelled black paint top cover 2.80 mm thick plastic laminated sheet of required colour fixed with brass screwes and cup washers including single core stranded copper conductor 1.5 Sqmm PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same concealed conduit complete all as specified for the following :-
One light point controlled by one switch with cables 1.5 Sqmm size all as specified and directed.
One fan point/Exhaust fan controlled by one switch with cables 1.5 Sqmm size all as specified and directed.
One 5 pin socket oulet 5/6 amps on same board including single core stranded copper conductor 1.5 sqmm PVC insulated and unsheathed cable drawn in same conduit as earth wire to the common earth and connecting to earth dolly all as specified.
One 3 pin socket outlet, 6 Amps, independent, with cables 1.5 sqmm of size all as specified and directed.
M&L for point wiring complete with stranded copper conductor 4 Sqmm size (Nominal area) PVC insulated unsheathed FRLS cable 1100 volts grade confirming to IS: 694 drawn in and including medium grade concealed PVC conduit confirming to ISI marked not less than 25mm dia with concealed sunk-in pressed steel terminal boxes of required size not less than 1.2 mm thick factory made and painted with stove enamelled black paint top cover 2.80 mm thick plastic laminated sheet of required colour fixed with brass screwes and cup washers including single core stranded copper conductor 4 Sqmm PVC insulated unsheathed cable as earth wire to common earth and connected to earth dolly drawn in same concealed conduit complete all as specified for one 6 pin socket outlet two in one 16/6 Amps on an independent board. (for geysers point) Note : For item No 4, 5 & 6 Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit. No Extra payment will be done on this account.
All as per item No 5.00 here-in-before but with cable 2.5 Sqmm and earth continuity conductor of 2.5 Sqmm stranded copper unsheathed complete all as specified and as directed.
Supply and fix in repairs switch piano, flush type single pole, one way, 6 Amps, 240 volts complete all as specified and as directed.
Supply and fixing in repairs socket outlet 2 in 1, 3 pin 5 Amps complete all as specified and as directed.
Supply and fix switch in repairs socket combination 6 Amps/16 Amps, 5 in 1, flush type complete all as specified and as directed.
Supply and fix in repairs ceiling roses, 3 phase, PVC/Polycarbonate, isolated body complete all as specified and as directed.
Supply and fix in repairs stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc as required complete all as specified and as directed.
Supply and fix in replacement of 20 watt (4ft long) decorative box type fitting with blue coloured end caps for LED tube etc complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable from ceiling rose to terminal block and testing complete all as specified and as directed at site.
Supply and fix in replacement of 12 watt 2 ft decorative box type fitting with coloured end caps for LED tube etc complete with all accessories internally pre-wired and including connecting up with twin core twisted flexible copper conductor cable from ceiling rose to terminal block and testing complete all as specified and as directed at site.
Taking down ceiling fan (C/F of any size/make), cleaning its dust properly oiling and hanging the same back to its original position including connecting the wire to ceiling rose etc complete after completing the wiring all as specified and as directed by Engr-in-Charge. Note :- (i) The spares like cotter pin, nuts & bolts, rubber bush & hooks etc defective/damage deemed to be replaced and make the ceiling fans functional. The rates quoted for the same deemed to be included for the above job.
Taking down exhaust fan and re-connecting up including provision of cable from ceiling rose to exhaust fan after cleaning all dust complete all as specified and as directed. Note :- (i) The spares like nuts & bolts etc defective/damage deemed to be replaced and make the fans functional. The rates quoted for the same deemed to be included for the above job.
M&L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground not less than 2.25m deep below normal ground level (with the top edge of the plate not less than 1.50 m below the normal ground level) connected to GI earth wire 4 mm by means of GI bolts, nuts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I connected to earthing test point with and including necessary excavation and earth work in any strata PCC pit 1:3:6 type C-1, 20mm bore medium grade GI pipe for watering 15mm bore light grade pipe for GI wire protection and funnel including 40mm thick RCC slab cover and testing on completion all as specified and as directed.
Supply and fix in replacement of LED building light luminaire 30 watt, pressure die cast aluminium housing with heat resistant toughened glass & IP66 protection complete all as specified and as directed. Make:- Cat.No. PCGLS 01 30 of polycab or equivalent out of makes spd in list of makes.
M&L for in replacement of bracket made from GI pipe light grade 40mm bore bent to shape as required at site for street light fitting 1.2 mtr in length and fixed on wall/pole including necessary MS clamps, nuts, bolts and washers including welding and painting complete all as specified and as directed.
Supply and fix lamp holder, PVC/Polycarbonate type with back plate suitable for batten fitting including with one number 12 watt LED lamp complete all as specified and as directed.
Supply and fix in replacement MCB, DB , SPN 8 way suitable for single phase 240 volts with 100 Amps rated bus bar, double door type suitable for mounting incoming and outgoing MCB's single/double pole complete all as specified and as directed at site.
Supply and fixing in replacement of MCB signle pole 6-32 Amps 230 volts 'C' series complete all as specified and as directed.
Supply and fixing in replacement of MCB single pole and neutral 40 /63 Amps 230 volts 'C' series complete all as specified and as directed at site.
Supply & fix in replacement of SPN enclosure with two pin and earth plug and socket complete with one SP MCB 20 Amps complete all as specified and directed by Engineer-in-Charge. Make:- Model No 607841 of Make Legrand or equivalent out of makes spd in list of makes.
S&F submain wiring with unsheathed multi-stranded FRLS Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 6 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed. Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete. Note 1: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit.
S&F submain wiring with unsheathed multi-stranded FRLS Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 4 Sqmm single core HR Grade and one run of 1.5 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed. Note :- Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete. Note 1: Rates are deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit.
S&F vertical type load line distribution board, double door, 4 way AC, 3 phase 415 volts, TPN bus bar 200 Amps rating and earth bus and din rail including 01 No. MCCB 3 pole 415 volts, 50 Hz, 100Amps 10 KA breaking capacity as incomer complete all as specified and as directed.
S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 100 Amps with breaking capacity 16 KA and dismantling of old unsv MCCB and connecting testing with MCCB complete all as specified and as directed.
Supply and fixing in replacement of MCB TPN 40-63 Amps 230 volts 'B' series complete all as specified and as directed.
Supply and fixing in replacement of MCB TPN 100 Amps 230 volts 'B' series complete all as specified and as directed.
S&F Exhaust Fan steel body AC Single phase, 230V of size 300mm sweep with blades, frame & louvers complete all as specified and as directed.
S&F Exhaust Fan steel body AC Single phase, 230V heavy duty of size 450mm sweep with blades, frame & louvers complete all as specified and as directed.
Supply & fix capacitor of 2.5 mfd complete all as specified and as directed.
All as per item No 32.00 but 3.15 mfd complete all as specified and directed.
All as per item No 32.00 but 4.00 mfd complete all as specified and directed.
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning filling in including spreading, leveling, watering and well ramming in layers exc 25 cm thick complete all as specified and as directed.
Removal of excavated material/surplus soil to a distance n exc 50m and depositing where directed at a level n exc 50m above the starting point complete all as specified and as directed.
Supply and filling river sand in trenches including spreading for cushioning of LT UG cable complete all as specified and as dirceted. Note : Punned down thickness shall be measured and paid .
M&L for sub class ‘B’ bricks old size laid flat dry in trenches over cable, across the direction of cable complete all as specified & as directed .
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 185 Sq mm. complete all as directed. Note : Provision of suitable double crimpped lugs and glands shall deemed to be included in quoted rates.
All as per item No 40.00 described here in before but 3.5 core 120 sqmm.
All as per item No 40.00 described here in before but 3.5 core 95 sqmm.
All as per item No 40.00 described here in before but 3.5 core 70 sqmm.
All as per item No 40.00 described here in before but 3.5 core 50 sqmm.
All as per item No 40.00 described here in before but 4 core 25 sqmm.
All as per item No40.00 described here in before but 4 core 16 sqmm.
S&F ACB (air circuit breaker) draw out type of rating 800 Amps 4 pole, 50 KA, O/L, S/C, micro processor based release and cassette mounted horizontal draw out type fully interlocked cassette door automatic safety shutters, mechanical on and off indicators, service/test/isolated position with position indicators, provision of castell lock, with O/L, S/C with 3 CT's of standard ratings 4 blocks of 6 way sliding type LT disconnectors, error prevention plug, racking handle, safety shutters and painted with finished light grey shade as per IS:631 and as per IS 13947-2-1993 inclusive suitable length of bus bars complete all as directed.
All as per item No 47.00 described here in before but 630 Amps.
S&F MCCB 630 A ,3 pole ,50 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make.
S&F MCCB 200 A ,3 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make.
S&F MCCB 125 A ,3 pole ,16 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make.
S&F MCCB 400 A ,4 pole ,36 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make.
S&F MCCB 160 A ,4 pole ,16 KA with adjustable thermal & fixed magnetic setting with bus bar spreader links for connecting both incoming and outgoing cables with suitable connections with suitable size of glands etc complete including testing & commissioning all as directed as per existing model/make.
M & L for Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of the plate not less than 1.5 metre below normal ground level, connected to and including using galvanised iron strip 32×6mm as earthing strip by means of bolts, nuts, check nuts and washers of galvanized iron or steel, earth plate surrounded by packed layer of char coal dust and common salt, 15cm thick all around bottom and top and watering pipe 20mm bore of GI light grade with funnel, wire mesh and 40 mm dia GI protection pipe medium grade all as shown in electrical plate No 3 of SSR Part-I and connected to earthing test point, main switch board and testing on completion including excavation, earth work concrete pit with 80mm thick RCC cover in RCC 1:2:4 type B-1 duly reinforced with MS bars 8mm dia @ 150C/C both ways and pit chamber in PCC 1:2:4 type B-1 with 2 Nos suitable lifting handles of 12mm MS bar complete all as specified.
Supply and lay in trenches GI strip 25 mm x 4 mm galvanised iron strip for earth continuity earthing all as specified and as directed.
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as spd and as directed.
Supply and lay in trenches /under roads/ crossing or fixed to wall/ pole, GI tubing light grade of size 40mm bore for protection of UG cables complete all as spd and as directed.
All as per item No 57.00 described here in before but 50 mm.
All as per item No 57.00 described here in before but 80 mm.
All as per item No 57.00 described here in before but 100 mm.
Taking down old UNSV fidder pillar and Supply, fixing, testing and commissioning in replacement of feeder pillar panel single door floor mounted and wall/pole mounted outdoor type, as per IP-55 grade, made out of MS sheet 3.15 mm thick of size 540x525x200mm with aluminium bus bar 250 Amps, 4 strip (3 phase) complete drilled, insulated with colour coded insulation tape, mounted on insulators etc with RYB indicator, panel should be dust proof, vermin proof, powder coated , locking should be screw type, mechanical type, inter locking with 150 Amps 25 KA MCCB four pole for incomer cable, should have danger notice for 415 volts, AC, mounted on 50x50x6 mm angle iron frame having minimum 2 feet ground clearance duly embedded in and including PCC block (1:2:4) complete including termination of all incoming and outgoing cables with suitable size thimbles/lugs and glands etc and providing fixing arrangements including earthing lead fixing arrangement, complete all as directed. Note :- Installation, testing, commissioning and connecting of incoming and outgoing cable connection LT feeder pillar panel shall included in rates quoted.
S&F vertical type load line distribution board, double door, 4 way AC, 3 phase 415 volts, TPN bus bar 200 Amps rating and earth bus and din rail including 01 No. MCCB 3/4 pole 415 volts, 50 Hz, 100Amps 16 KA breaking capacity as incomer complete all as specified and as directed.
S&F in replacement of MCCB 4 pole, 415 volts, adjustable type 100 Amps with breaking capacity 16 KA and connecting testing with MCCB complete all as specified and as directed.
S&F170 Ltr FRP solution preparation tank and 100 Ltr Dosing tank with lid, port hole ,inlet/outlet/drain connection, level gauge etc and fitted with speed reducing motor & SS-316 agitator combined with dosing tank with lid, port hole, inlet/outlet/drain connection, level gauge etc complete all as specified and as directed. Make: RAMCO model No CDS 1015 or equivalent as approved by GE.
M&L for submain wiring with unsheathed multi-stranded FR Grade copper conductor cable 1100 volts grade drawn through in and including PVC rigid conduit medium grade of not less than 25mm dia with conduit accessories and concealed in wall/surface of ceiling for two runs of 6 Sqmm single core HR Grade and one run of 4 Sqmm PVC insulated copper conductor for earth continuity wire between main DB to Sub main DB complete all as specified and as directed. Note :- (i) Two run of single core cable with one run of earth continuity conductor and PVC conduit and accessories will be measured as one length including cutting chasing in wall complete. Note (ii): Rates shall deemed to be included for chases of conduit and sunking for boxes cutting and making holes in wall/floor for passing in or through conduit.
A B K Enterprises
k k enterprises
Chaudhary Constructions
M/s GANJOO AND CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .