SE(E/M)-I, KMDA
6th Floor Unnayan Bhavan Salt Lake, KMDA, Kolkata- 700091
Design, Engineering, Supply, Storage, Installation, Commissioning, Trial Run FIVE Years Operation And Maintenance Of Clear Water Booster Pumping Station Of Capacity 18560 M3 per Day And Power Distribution System.
2020_KMDA_309180_1
SE (E/M)-I/3T-01/2017/489
Open Tender
Electrical Work/ Equipment
Item Rate
365 days
UNDER KONNAGAR MUNICIPALITY
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹5 L
OFFICE OF THE SUPERINTENDING ENGINEER (E/M)-I
23 Feb 2021
15 Dec 2020
25 Jan 2021
15 Dec 2020
23 Jan 2021
16 Dec 2020
24 Dec 2020
Amount
PART – A ( SUPPLY PART )
Supply, delivery at site & storage of horizontal Centrifugal pumps axially split case of suitable capacity at 65 Mtr. head as per specification and Technical offer complete with the coupling hub & all other accessories as per specification. Maximum allowable speed of pump shall be 1500 R.P.M
Supply, delivery at site & storage of MS pipes, specials, joints, flanges & common delivery manifold with extended pipe line as per specification and Technical offer.
Supply, delivery at site & storage of valves complete with fixture as per specification and Technical offer & as follows.
Sluice Valve for individual pump Suction pipe line
Butterfly valve for delivery side of pumps fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe line
Non-Return Valve for individual pump delivery pipe line
Butterfly valve fitted with electrical actuator suitable for local and control desk operation and display system for common delivery manifold
Double throat air valve with Isolating Valve at common delivery manifold as per specification
Supply, delivery at site and storage of M.S. dismantling joint assembly for common delivery manifold as per specification and Technical offer
Supply, delivery at site and storage of M.S. dismantling joint assembly for the individual pump suction pipe line as per specification and Technical offer.
Supply, delivery at site and storage of M.S. dismantling joint assembly for the individual pump delivery pipe line as per specification and Technical offer.
Supply, delivery at site and storage of M.S. puddle collar / plate for the individual pump suction pipe line as per specification .
Supply, delivery at site and storage of M.S. puddle collar / plate for common delivery manifold as per specification .
Supply, delivery at site and storage of Full bore electromagnetic type Flow meter, Recorder, Totaliser as per specification and Technical offer.
Supply, delivery at site and storage of Pressure gauges complete with fittings and fixture as per specification and Technical offer & as follows.
Pressure gauge for Delivery side (0– 10 Kg / cm2)
Pressure gauge for common delivery manifold (0 – 10 Kg / cm2 )
Compound gauge for suction side (-) 1 – (+) 1 Kg / cm2
Supply, delivery at site and storage of pressure transmitter and level indicator complete with fitting and fixture as per specification and Technical offer & as follows.
Pressure transmitter for delivery side ( 0 – 10 Kg / cm2 )
Pressure transmitter for common delivery manifold ( 0 – 10 Kg / cm2 )
Radar type Level Monitoring system for Clear Water Level complete with all accessories
Supply, delivery at site and storage of Horizontal squirrel-cage TEFC IE2 motor rated at 415V ±10%, 50Hz ±5%, 3Ph, 1500 R.P.M.(syn.) of adequate capacity to match the pump at sl. no. 1) complete with coupling hub and all other accessories as per specification & Technical offer ( Rating not less than 200 KW )
Supply, delivery at site and storage of multi panel HT PDB of minimum 800 A capacity suitable for operation at 11000 OR 6000 Volt, ± 10%, 3 phase, 50Hz, ± 5%, A.C. system as per specification and Technical offer
Supply, Delivery at site and storage of 525V automatic power factor improvement capacitor bank ( APFC ) with all inter connection complete suitable for 415 V, 50 Hz system as per specification
Supply, delivery at site & storage of ONAN, indoor type 800 KVA Transformer, 11 OR 6.0 KV / 433 volts Delta –Star transformer with neutral brought out as per specification
Supply, delivery at site and storage of MCC cum PDB of 1250 A capacity at the Pump House, suitable for operation at 415 Volt, ± 10%, 3 phase, 50Hz, ± 5%, A.C. system as per specification
Supply, delivery at site & storage of Remote Control Desk & Instrument panel for the motor control, Power Distribution & other system as per specification and Technical offer
Supply, delivery at site & storage of stationary, 110 V DC, 100 Ah with 55 cells sealed maintenance free battery with float and boost battery charger cum DCDB as per Specification
Supply, delivery at site & storage of Exhaust Fans with Control panel (For Sub Station) as per Specification.
Supply, delivery at site and storage of H.T., M.V. and Control Cable as per specification & as follows :
From CESC’s Summation Panel to incoming panel of HT PDB, 11 KV (E ) grade, 300 sq mm dia AL conductor, XLPE insulated, armoured cable as per Specification.
From HT PDB to two numbers 800 KVA transformer H.V. side terminal, 11 KV ( E ) grade, 300 sq mm AL conductor, XLPE insulated, armoured cable as per Specification.
From two numbers of 800 KVA transformer secondary side to the two number incomers of MCC cum PDB , 1.1KV grade, 4 x 3.5 C x 300 sq mm Al. conductor, XLPE insulated armoured cable, 4 lengths each per incomer i.e. total 8 lengths.
From MCC cum PDB to Battery Charger, 1.1 KV grade, 4 C, 4 sq mm, stranded Cu. Conductor XLPE insulated armoured cable
From Battery Charger / DCDB to H.T. PDB, 1.1 KV grade, 2 x 3 C, 2.5 sq mm stranded copper conductor XLPE insulated armoured cable for DC supply ( Duplicate feeder )
From Battery Charger / DCDB at Sub-station to DCDB at Pump House, 1.1 KV grade, 4 C 4sq mm stranded copper conductor XLPE insulated armoured cable
From MCC cum PDB at Pump House to 2 Nos. LDB’s at Sub Station & pump House ( One no. in each location), 1.1 KV 4C, 4 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB at Pump House to Ventilation System and Exhaust Fan Control Panels at Sub Station & Pump House ( One no. in each location), 1.1 KV, 4C, 4 sq mm Multi strand copper conductor XLPE insulated armoured cable
From MCC cum PDB to all Valve Actuators, 1.1 KV, 4C, 2.5 sq mm Multi strand copper conductor XLPE insulated armoured cable
From Control Desk to all Pressure Transmitter, Flow Transmitter, Valve position & other Indicator, 1.1 KV 4C, 0.75 sq mm Screen Cable
From Control Desk to all motor Space Heaters, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB to E.O.T. Crane, 1.1 KV 4C, 6 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From DCDB at Pump House to Control Desk, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable for DC supply
From MCC cum PDB to Control Desk, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable for AC supply
From MCC cum PDB to H.T. PDB at Sub-station, 1.1 KV grade, 3 C, 4 sq mm stranded copper conductor XLPE insulated armoured cable for AC Supply
From MCC cum PDB to Ventilation System Panel at Pump House, 1.1 KV 4C, 6 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB to Main Drive Motor 1.1KV grade, 2 x 3 C x 185 sq mm Al. conductor, XLPE insulated armoured cable, i.e. 2 lengths each per motor
From Control Desk to each Motor RTD / BTD Terminal Box, 650 V grade 10 Triad X 1.5mm PVC insulated stranded copper screened armoured cable, complete for all the motors.
Control Cable for AC & DC supply of stranded copper conductor of various sizes & grade and of suitable length as per specification for all remote control and interlocking circuits
Supply, delivery at site and storage of Jointing materials as per specification & as follows
All H.T. Cable jointing materials ( dry type )
All M.V. Cable jointing materials ( dry type)
All Control & Screen Cable jointing materials ( dry type)
N.B. – No extra payment would be made if the length and dia. & variety of the different sizes of cable varies on the higher side to meet the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints.
Supply, delivery at site and storage of materials for Earthing system as per current I.E. Rule & specification for all equipment
Supply, delivery at site and storage of Lightning Arrestor along with earth strip and earth electrodes all complete as per specification and all other equipment required to comply with latest I.E. Rule
Supply, delivery at site & storage of fire extinguishers and fire buckets as follows:
Dry Powder ( 5Kg. each )
ABC Type ( 5 Kg. each )
ABC Type ( 2 Kg. each ) portable
Fire Bucket ( 9 Litres )
Supply, delivery at site and storage of Ventilation System comprising of forced Air Ventilation Fans, Air Duct & Exhaust fans complete with cowl etc. at the pump house all complete as per specification.
Supply, delivery at site and storage of air conditioner for control room cum office all complete as per specification at Pump House
Supply, delivery at site and storage of M.S. Structural materials for cable tray / rack, panel installation supports, Pipes & valves supports, fabricated stairs & all other fabrication work.
Supply, delivery at site and storage of all luminaries, fittings, fixtures complete with necessary cables with wires and all other accessories for inside lighting of pump house and Sub-station including Lighting Distribution Boards as per specification.
Supply, delivery at site and storage of Misc. Item such as rubber mats, Shock Treatment Chart ,Glow Sign Board, Safety Signage etc. as per specification
Supply, delivery at site and storage of 5T capacity E.O.T. Crane with 1T capacity auxiliary hoist suitable for inching operation with other allied equipment all complete as per specification
Supply and delivery at site and storage of spare parts as per specification
PART-B ( INSTALLATION PART)
Installation at site of horizontal Centrifugal pumps axially split case of suitable capacity and 65 Mtr. head as per specification and Technical offer complete with the coupling hub & all other accessories as per specification. Maximum allowable speed of pump shall be 1500 R.P.M.
Installation at site of MS pipes, specials, joints, flanges & common delivery manifold with extended pipe line as per specification and Technical offer.
Installation at site of valves complete with fixture as per specification and Technical offer & as follows.
Sluice Valve for individual pump Suction pipe line
Butterfly valve for delivery side of pumps fitted with electrical actuator suitable for local and control desk operation and display system for the individual pump delivery pipe line
Non-Return Valve for individual pump delivery pipe line
Butterfly valve fitted with electrical actuator suitable for local and control desk operation and display system for common delivery manifold
Double throat air valve with Isolating Valve at common delivery manifold as per specification
Installation at site of M.S. dismantling joint assembly for common delivery manifold as per specification and Technical offer
Installation at site of M.S. dismantling joint assembly for the individual pump suction pipe line as per specification and Technical offer.
Installation at site of M.S. dismantling joint assembly for the individual pump delivery pipe line as per specification and Technical offer.
Installation at site of M.S. puddle collar / plate for the individual pump suction pipe line as per specification .
Installation at site of M.S. puddle collar / plate for common delivery manifold as per specification .
Installation at site of Full bore electromagnetic type Flow meter, Recorder, Totaliser as per specification and Technical offer.
Installation at site of Pressure gauges complete with fittings and fixture as per specification and Technical offer & as follows.
Pressure gauge for Delivery side (0– 10 Kg / cm2)
Pressure gauge for common delivery manifold (0 – 10 Kg / cm2 )
Compound gauge for suction side (-) 1 – (+) 1 Kg / cm2
Installation at site of pressure transmitter and level indicator complete with fitting and fixture as per specification and Technical offer & as follows.
Pressure transmitter for delivery side ( 0 – 10 Kg / cm2 )
Pressure transmitter for common delivery manifold ( 0 – 10 Kg / cm2 )
Radar type Level Monitoring system for Clear Water Level complete with all accessories
Installation at site of Horizontal squirrel-cage TEFC IE2 motor rated at 415V ±10%, 50Hz ±5%, 3Ph, 1500 R.P.M.(syn.) of adequate capacity to match the pump at sl. no. 1) complete with coupling hub and all other accessories as per specification & Technical offer (Rating not less than 200 KW )
Installation at site of multi panel HT PDB of minimum 800 A capacity suitable for operation at 11000 OR 6000 Volt, ±10%, 3 phase, 50Hz, ± 5%, A.C. system as per specification and Technical offer
Installation at site of 525V automatic power factor improvement capacitor bank ( APFC ) with all inter connection complete suitable for 415 V, 50 Hz system as per specification
Installation at site of ONAN, indoor type 800 KVA Transformer, 11 OR 6.0 KV / 433 volts Delta –Star transformer with neutral brought out as per specification
Installation at site of MCC cum PDB of 1250 A capacity at the Pump House, suitable for operation at 415 Volt, ± 10%, 3 phase, 50Hz, ± 5%, A.C. system as per specification
Installation at site of Remote Control Desk & Instrument panel for the motor control, Power Distribution & other system as per specification and Technical offer
Installation at site of stationary, 110 V DC, 100 Ah with 55 cells sealed maintenance free battery with float and boost battery charger cum DCDB as per Specification
Installation at site of Exhaust Fans with Control panel (For Sub Station) as per Specification.
Installation / Laying at site of H.T., M.V. and Control Cable as per specification & as follows :
From CESC’s Summation Panel to incoming panel of HT PDB, 11 KV (E ) grade, 300 sq mm dia AL conductor, XLPE insulated, armoured cable as per Specification.
From HT PDB to two numbers 800 KVA transformer H.V. side terminal, 11 KV ( E ) grade, 300 sq mm AL conductor, XLPE insulated, armoured cable as per Specification.
From two numbers of 800 KVA transformer secondary side to the two number incomers of MCC cum PDB , 1.1KV grade, 4 x 3.5 C x 300 sq mm Al. conductor, XLPE insulated armoured cable, 4 lengths each per incomer i.e. total 8 lengths.
From MCC cum PDB to Battery Charger, 1.1 KV grade, 4 C, 4 sq mm, stranded Cu. Conductor XLPE insulated armoured cable
From Battery Charger / DCDB to H.T. PDB, 1.1 KV grade, 2 x 3 C, 2.5 sq mm stranded copper conductor XLPE insulated armoured cable for DC supply ( Duplicate feeder )
From Battery Charger / DCDB at Sub-station to DCDB at Pump House, 1.1 KV grade, 4 C 4sq mm stranded copper conductor XLPE insulated armoured cable
From MCC cum PDB at Pump House to 2 Nos. LDB’s at Sub Station & pump House ( One no. in each location), 1.1 KV 4C, 4 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB at Pump House to Ventilation System and Exhaust Fan Control Panels at Sub Station & Pump House ( One no. in each location), 1.1 KV, 4C, 4 sq mm Multi strand copper conductor XLPE insulated armoured cable
From MCC cum PDB to all Valve Actuators, 1.1 KV, 4C, 2.5 sq mm Multi strand copper conductor XLPE insulated armoured cable
From Control Desk to all Pressure Transmitter, Flow Transmitter, Valve position & other Indicator, 1.1 KV 4C, 0.75 sq mm Screen Cable
From Control Desk to all motor Space Heaters, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB to E.O.T. Crane, 1.1 KV 4C, 6 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From DCDB at Pump House to Control Desk, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable for DC supply
From MCC cum PDB to Control Desk, 1.1 KV 3C, 2.5 sq mm Multi strand Copper conductor XLPE insulated armoured cable for AC supply
From MCC cum PDB to H.T. PDB at Sub-station, 1.1 KV grade, 3 C, 4 sq mm stranded copper conductor XLPE insulated armoured cable for AC Supply
From MCC cum PDB to Ventilation System Panel at Pump House, 1.1 KV 4C, 6 sq mm Multi strand Copper conductor XLPE insulated armoured cable
From MCC cum PDB to Main Drive Motor 1.1KV grade, 2 x 3 C x 185 sq mm Al. conductor, XLPE insulated armoured cable, i.e. 2 lengths each per motor
From Control Desk to each Motor RTD / BTD Terminal Box, 650 V grade 10 Triad X 1.5mm PVC insulated stranded copper screened armoured cable, complete for all the motors.
Control Cable for AC & DC supply of stranded copper conductor of various sizes & grade and of suitable length as per specification for all remote control and interlocking circuits
Installation at site of Jointing materials as per specification & as follows
All H.T. Cable jointing materials ( dry type )
All M.V. Cable jointing materials ( dry type)
All Control & Screen Cable jointing materials ( dry type)
N.B. – No extra payment would be made if the length and dia. & variety of the different sizes of cable varies on the higher side to meet the requirement of the specification and site condition. Rates must be quoted carefully. This is also applicable for all type of cable joints.
Installation at site of materials for Earthing system as per current I.E. Rule & specification for all equipment
Installation at site of Lightning Arrestor along with earth strip and earth electrodes all complete as per specification and all other equipment required to comply with latest I.E. Rule
Installation at site of fire extinguishers and fire buckets as follows:
Dry Powder ( 5Kg. each )
ABC Type ( 5 Kg. each )
ABC Type ( 2 Kg. each ) portable
Fire Bucket ( 9 Litres )
Installation at site of Ventilation System comprising of forced Air Ventilation Fans, Air Duct & Exhaust fans complete with cowl etc. at the pump house all complete as per specification.
Installation at site of air conditioner for control room cum office all complete as per specification at Pump House
Installation at site of M.S. Structural materials for cable tray / rack, panel installation supports, Pipes & valves supports, fabricated stairs & all other fabrication work.
Installation at site of all luminaries, fittings, fixtures complete with necessary cables with wires and all other accessories for inside lighting of pump house and Sub-station including Lighting Distribution Boards as per specification.
Installation at site of Misc. Item such as rubber mats, Shock Treatment Chart ,Safety Signage etc. as per specification
Installation at site of 5T capacity E.O.T. Crane with 1T capacity auxiliary hoist suitable for inching operation with other allied equipment all complete as per specification
Painting the whole installation as per specification & direction of E.I.C.
Carrying out pre-commissioning test on H.T & M.V equipments and making ready all H.T. & M.V. equipment for High/Medium pressure tests and submission of test reports
Carrying out Statutory High pressure tests on all H.T. equipment & medium pressure testing on M.V. Equipments as per specification including charges of Govt. Electrical Inspector.
Charges for Diesel Generator set/Temporary power connection from CESC for construction purpose.
Commissioning the whole installation including Trial Run of Pumps for one month with 8 hrs. at a stretch operation as per specification & direction of E.I.C.
Operation & Maintenance of the whole installation for a period of five years ( after trial run ) deploying adequate number of working personnel for round the clock operation as per requirement, specification & direction of E.I.C.
POWER INDIA
Mate Consultants Pvt. Ltd.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .