Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.1 LAccepted-AOC 15 CP COLONY MORAR GWALIOR MP 474 006 | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹14.6 L+₹18,100 (1.26%)Rejected-Finance | L2 | Rejected-Finance 1455500.00 | |
| 3 | L3₹15.8 L+₹1.4 L (9.90%)Rejected-Finance | L3 | Rejected-Finance 1579700.00 | |
| 4 | L4₹16.4 L+₹2.0 L (14.0%)Rejected-Finance | L4 | Rejected-Finance 1639200.00 |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
16 Nov 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF ADM AREA
GE AF ADM AREA GWALIOR-474020
REPAIR/MAINT/ REPLACEMENT OF 11KV UG CABLES, JOINTS AND CONNECTED WORKS AT AF STATION GWALIOR
2023_MES_624046_1
8362/E8
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
GE AF ADM AREA GWALIOR
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF ADM AREA
₹40,000
Yes
15 Jan 2024
19 Oct 2023
24 Nov 2023
19 Oct 2023
16 Nov 2023
2 Nov 2023
Amount
Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers.
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed by Engineer-in-Charge.
Removal of surplus excavated spoil not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified.
Material & labour for sand filling with clean dry find sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed by Engineer-in-Charge.
Supplying & Laying un-reinforced pre cast flat concrete cable protection cover of class HV, type I, size 300mm x 180mm x 40mm, factory made, complete all as specified and directed by the Engineer-in-Charge.
laying only old retrieved cable protection cover of any description as obtained from dismantling of the cable complete all as specified and directed by the Engineer-in-Charge.
Disconnecting, taking out and removing old existing unserviceable under ground, HT 11 KV cable of any type and in any position complete including taking down protection pipe, cable covers etc all as specified and directed by the Engineer-in-Charge of the following sizes:-
(a) 95 Sqmm to 120 Sqmm 3 core
(b) 150 Sqmm to 240 Sqmm 3 core
Laying, jointing and testing 11KV, HT UG cable of any type laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed by the Engineer-in-charge of following sizes :-.
(a) 95 Sqmm to 120 Sqmm 3 core
(b) 150 Sqmm to 240 Sqmm 3 core
Supply, laying , jointing & testing 11 KV (Earthed) , aluminum conductor, screened, XLPE insulated, armoured shielded and PVC sheathed cables conforming to IS 7098 (Part-II) amended up to date having following cross sectional area complete all as specified and directed by the Engineer-in-Charge.
(a) 95 Sqmm, 3 core
(b) 120 Sqmm, 3 core
(c) 185 sqmm, 3 core
(d) 240 sqmm, 3 core
Excavation for removing/checking of HT cable joint with draining out water in trenches including returning filling of existing soil, sand , PCC cable cover and making good disturbed surfaced complete all as specified and directed by Engineer-in-Charge.
M & L in Replacement Jointing and testing of Straight through Heat shrinkable joint suitable for 11 KV, XLPE/PVC insulated cable of following sizes complete material and labour including cutting the faulty straight through of any type and in any position. Note :-(i) All Necessary T & P required shall be arranged by the Contractor at his own cost. (ii) The contractor has to rectifie the joint within 4 Hrs after the complaint, in case of failure the penalty of Rs.1000 per hours shall be recovered from the contractor.
(a) 50 Sqmm to 95 Sqmm, 3 core
(b) 120 Sqmm to 185 Sqmm 3 core
(c) 240 Sqmm to 300 Sqmm 3 core
M & L in Replacement , jointing and testing for indoor type Heat shrinkable end termination joint suitable for 11 KV, XLPE/PVC insulated cable of following sizes complete material and labour including cutting the faulty indoor end termination joint of any type and in any position. Note :-(i) All Necessary T & P required shall be arranged by the Contractor at his own cost. (ii) The contractor has to rectifie the joint within 4 Hrs after the complaint, in case of failure the penalty of Rs.1000 per hours shall be recovered from the contractor.
(a) 50 Sqmm to 95 Sqmm, 3 core
(b) 120 Sqmm to 185 Sqmm 3 core
(c) 240 Sqmm to 300 Sqmm 3 core
M & L in Replacement jointing and testing for outdoor type Heat shrinkable end termination joint suitable for 11 KV, XLPE insulated cable of following sizes complete material and labour including cutting the faulty outdoor end termination joint of any type and in any position. Note :-(i) All Necessary T & P required shall be arranged by the Contractor at his own cost. (ii) The contractor has to rectifie the joint within 4 Hrs after the complaint, in case of failure the penalty of Rs.1000 per hours shall be recovered from the contractor.
(a) 50 Sqmm to 95 Sqmm, 3 core
(b) 120 Sqmm to 185 Sqmm 3 core
(c) 240 Sqmm to 300 Sqmm 3 core
Demolition for cement concrete/road in ground floor and paving n. exc 15 cm thickness below or above ground level including removal of rubbish to a distance exc 1.50 Km and n.exc 5.00 Km etc complete all as specified
M&L fro Plain Cement concrete C-1 (1:3:6) using 20 mm crushed stone aggregate for foundations and mass including necessary filling complete alla s specified and direcetd.
M&L for Boring of hole under road, pavement, hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure. all as specified and directed by Engineer-in-Charge. Note : Pipes shall be laid minimum 1.00 mtr below/under existing road surfaces/ taxi track/ apron /floors etc.
M & L in Replacement, laying & jointing GI water tubing, 80 mm bore, light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed by Engineer-in-Charge.
All is item No 17.00 here-in-before but GI tubing 100 mm bore.
Material and labour for checking and finding out pin point location of fault in HT 11 KV underground cable with the help of fault locating High Tech mobile machine complete all as directed. Note : (i) Charges for rent and transportation of the fault locating high tech mobile machine including DG Set, necessary earth work for repair HT cable, testing of cable after repair, charges for operator, engineer, electricians etc deemed to be included in the quoted rate. (ii) Fault locating high tech mobile machine will be provided as and when required on short notice otherwise an amount of Rs. 5000/Per day will be charged as penalty.
Supply, installation, testing and commissioning of factory fabricated CPRI approved outdoor Kiosk type HV junction panel for 3 phase, 11 KV, AC, 50 Hz supply & aluminium bus bar of 600 amp rating of suitable size , cubical of appropriate size made of 3.00 mm thick CRCA steel sheet and angle iron base & legs 25mm x25mm x 5mm totally enclosed with top canopy, free standing, water, dust & vermin proof with IP 65 protection powder coated internally and externally not less than 80 micron thick after seven tank pretreatment process including locking arrangement and embeding angle iron legs in PCC (1:3:6) type C-1 precast blocks of size 20X20X45 cm deep all as specified & directed.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 metre below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 32mm x 6 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt alround earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit , internal surface of concrete shall be given 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover 1 : 2 : 4 ,type B-1( using 20 mm graded crushed stone aggregare ) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with 12mm dia round bar as in handle including taking down of existing earthing complete all as specified & directed by Engineer-in-Charge. Note: (i) Test result of earthing to be submitted by the contractor for all earthing . (ii) Earth filling shall be done by vegetable soil. (iii) Soil should be free from stone, boulders,aggragates,gravel etc. (iv) The rate quoted by the bidders shall be also be deemed to include :-(a) Excavation upto 5 mtr depth and returning filling in any type of soil and disposal of surplus soil. (b) Supply of charcoal and common salt.
Supply the hard core broken stone/ boulders of gauge n exc. 63 mm, deposited, spread and levelled in layers n exc. 15 cm thick, to a true surface at the places as specified and directed by Engineer-in-charge.
M/S Amit Traders
Kumar Sales Corporation
Om Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .