Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
13 Feb 2023, 6:00 pmClosed
GE (WEST) PATHANKOT
GE (WEST) PATHANKOT
REPAIR MAINTENANCE OF WATER SUPPLY AND SEWAGE INSTALLATIONS INCL UPKEEPING OF LT PANELS, DISTRIBUTION SYSTEM AND CONNECTED WORKS UNDER GE (W) PATHANKOT
2023_MES_572960_1
GE/PKT-66/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE (WEST) PATHANKOT
Please refer tender documents
9 documents required · 9 mandatory
₹500
GE (WEST) PATHANKOT
₹80,000
Yes
21 Mar 2023
4 Jan 2023
16 Feb 2023
4 Jan 2023
13 Feb 2023
30 Jan 2023
5 Jan 2023 - 14 Jan 2023
Amount
Excavation in trenches n exc 1.5m wide and n exc 1.5m in depth in any type of soil for repairing/ replacement of CI & GI pipes including getting out excavated earth complete all as specified and directed.
Returning, filling in trenches incl spreading and leveling, watering and well ramming in layers n.exc. 25 cm thick complete all as specified and directed.
Removal of excavated soil to a distance n.exc. 50 mtr and depositing the same where directed at a level n.exc. 1.5 mtr above starting point complete all as specified and directed
Taking out cast iron water mains 150 mm dia carefully (including all fittings) with spigot and socket ends and lead joints including burning out joints and recovering lead for relaying or depositing in MES store complete all as specified and directed by Engr- in - Charge. Note- Excavation and earth work shall measured and paid saperately under relative items.
All as per srl Item 4.00 above but of 100 mm dia bore
Supply, laying & testing in repair ductile Iron S/S pipe 150 mm dia bore shall confirm to IS-8329-2000 and 9523-2000. The pipe shall be laid in trenches ,jointed and tested all as per IS 12288-1987 with specials Class “K-9” . The fittings shall withstand hydrostatic pressure without showing any leakage,sweating or defects of any kind as laid down in IS complete all as specified and directed by Engr-in-charge. (Note : 1. Cutting, drilling, welding are deemed to be included in the quoted rate. 2. Necessary Premissions for road cutting in civil areas will be taken from Competatnt Authorities by the contractor without any extra cost to the department.)
Supply, laying & testing in repair ductile Iron S/S pipe 100 mm dia bore shall confirm to IS-8329-2000 and 9523-2000. The pipe shall be laid in trenches ,jointed and tested all as per IS 12288-1987 with specials Class “K-7” . The fittings shall withstand hydrostatic pressure without showing any leakage,sweating or defects of any kind as laid down in IS complete all as specified and directed by Engr-in-charge. (Note : 1. Cutting, drilling, welding are deemed to be included in the quoted rate. 2. Necessary Premissions for road cutting in civil areas will be taken from Competatnt Authorities by the contractor without any extra cost to the department.)
S & F Ductile iron bend (any type radius and angle) taper any type for (straight) bend increasing /decreasing of double socket/flanged etc. Tee piece single branch, Y junction, double branch, collar and plug of upto 150mm bore DI pipe complete all as specified and directed.
Material & labour for Rubber gasket/Tyten joint for 150 mm dia pipe complete all as specified and directed by Engr-in-charge.
Material & labour for Rubber gasket/Tyten joint for 100 mm dia pipe complete all as specified and directed by Engr-in-charge.
Material & labour in repair for Lead wool joint CI pipe 150 mm dia including earth work complete all as specified and directed by Engr-in-charge.
Material & labour in repair for Run lead joint for CI pipe 150 mm dia including earth work complete all as specified and directed by Engr-in-charge.
Material & labour in repair for Run lead joint for CI pipe 100 mm dia including earth work complete all as specified by Engr-in-charge.
Material & labour in repair for Run lead joint for CI pipe 80 mm dia including earth work complete all as specified by Engr-in-charge.
Supply and fixing in replacement of cast iron sluice valve in position 150 mm dia both side flanged PN-1.6 confirming to IS 14846 (ISI marked) with stainless steel spindle and iron wheel non raising type including, nuts and bolts complete all as specified by Engr-in-charge.
All as per srl Item no 15.00 but of size 100mm dia.
Material & labour for Brickwork with fly ash bricks, straight or curved on plan exc 6m mean radius using cement mortar 1:4 complete all as specified by Engr-in-charge.
Taking down cement plaster in any description on brick walls /floors including raking out joints, hacking for key,with water, etc complete all as specified and as directed.
Material & labour for 10 mm thick Rendering in CM 1:4 , on fair faces of brick work or concrete surfaces without using extra cement complete all as specified and as directed.
Material & labour for Cement concrete in foundation , filling and mass concrete type B2 1:2:4 type B-2, 40mm graded aggregate complete all as specified and as directed.
Material & labour for PCC (Nominal mix) using 20mm graded crushed stone aggregates of ratio 1:3:6 as in benching including weathering slightly rouned or chamfered angles and finishing exposed surfaces even and smooth including use of necessary frame work complete all as specified and as directed.
Material & labour for painting after scraping of old dull paints from the surface by scretching by wire brushes of steel surface over width or girth such as CI pipe lines of over head tanks of 15m staging including rising mains, gravity, mains overflow pipe, wash out pipe & Header,by applying two coats of synthetic enamel paint as per colour code decided by Engineer-in Charge and arrow marking & writing by using of all suitable scaffolding, mestles, ladders, cradles complete all as specified and directed. (Note:- Required necessary safety measures during the work will be taken by contractor. if any case of mishappening due to negligency, contractor is wholly responsible for the same. (ii) Rate quoted by the contractor include the cost of scaffolding, ladder, crane and T&P required for completion of work and nothing extra shall be admissible on this account.
Material & labour in repair Air termination, single pointed aluminium rod 12mm dia and 300mm long fitted in OH tanks complete all as specified and as directed.
Supply & fixing in repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc in OH tanks or where reqd for roof conductors/ lightening conductor and down conductors above ground level complete all as specified and directed.
Taking down existing unsv service cable & Supply and laying cable XLPE insulated screened PVC bedded galvanized steel strip or wire armored , electric power cables ( Heavy duty) 1100 volts grade with stranded aluminum conductor of 6 Sqmm 2 Core complete all as specified and as directed.
S&F in repair LED light fitting 100 W LED, new gerneration energy saving & environmental friendly long life versatile pressure die-cast aluminium IP 65 protection and minimum 5700 K CCT,roadway luminaire with high power LED as light source complete and making connections with provision of PVC insulated copper conductor (multistranded) three core cable of 1.5 Sq mm size complete all as specified and directed by Engr-in-Charge.
S&F in repair LED light fitting 45 W LED, new gerneration energy saving & environmental friendly long life versatile pressure die-cast aluminium IP 65 protection and minimum 5700 K CCT,roadway luminaire with high power LED as light source complete and making connections with provision of PVC insulated copper conductor (multistranded) three core cable of 1.5 Sq mm size complete all as specified and directed by Engr-in-Charge.
M&L for Earthing complete ( in repair) with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron strip 32X6 mm by means of nuts bolts,washers, check nuts of GI steel all as shown in electric plate no 3 all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe ,medium grade 40mm and GI watering pipe 20mm ,medium grade with funnel and wire mesh ,40mm thick pre-cast RCC N-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) pit,excavation and earth work in any type of soil and connected all as specified and as directed.
M&L for Earthing complete ( in repair) with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below the normal ground level ) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized iron earth wire of 4 mm dia by means of nuts bolts,washers, check nuts of GI steel all as shown in electric plate no 3 all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe ,medium grade 20mm and GI watering pipe 20mm ,medium grade with funnel and wire mesh ,40mm thick pre-cast RCC N-15 (nominal mix) cover reinforced with XPM weight not less than 4 kg /sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover ,PCC M-15 (nominal Mix) pit,excavation and earth work in any type of soil and connected all as specified and as directed.
Testing of Drinking water at the outlet of service distribution,sampling and anaylisis is to be carried out by NABL accredited authorized LAB per IS - 3025 for essential parameters such as Physical & Chemical analysis : Colour, Odour,Taste,Turbidity,Ph,Total Hardness, Iron, Flouride, TDS and Bacteriological analysis: E-coliform etc complete all as specified and as directed. (Note: Sample of Drinking water is to be collected by contractor in presence of rep of accepting offr and submit result of the test to AGE E/M office every month as directed by Engineer-in-charge.)
Supply and fixing in replacement MCCB 3 Pole LT 415 volt 50 Hz, AC 100 amps 25 kA with thermal magnetic release for OL & SC protection complete all as specified and as directed.
Supply and fixing in replacement MCCB 3 Pole LT 415 volt 50 Hz, AC 125 amps 25 kA with thermal magnetic release for OL & SC protection complete all as specified and as directed.
Supply and fixing in replacement MCCB 3 Pole LT 415 volt 50 Hz, AC 200 amps 25 kA with thermal magnetic release for OL & SC protection Adjustible type complete all as specified and as directed.
Supply and fixing in replacement Change over switch 415 Volts front operated fixed in panel board include locking arrangements 4 pole of capacity 100 Amps complete all as specifed and directed.
Supply and fixing in replacement Change over switch 415 Volts front operated fixed in panel board include locking arrangements 4 pole of capacity 125 Amps complete all as specifed and directed.
Supply and fixing in replacement Change over switch 415 Volts front operated fixed in panel board include locking arrangements 4 pole of capacity 200 Amps complete all as specifed and directed.
Supply and fixing in replacement Elastomer Insulating Mats for Electrical Purposes of thickness 2mm thick of AC proof voltage 11 kV with Anti Skid without metallic derivatives with Chips pastable type to be fixed permanently on the front and and other electrical installations as recommended in IS 15652 : 2006 and marked ISI marked complete all as specified and as directed.
Supply and fixing in replacement Gate light fitting LED type 25 W with CCT not less than 5700 K, and IP 65 Protection, 230V recessed mounting mirror optic luminare complete with all accessories pre-wired and including connecting up with twin core twisted flexible copper conductor cable with suitable size, complete including wire and making connection with pole complete all as specified and directed by Engr-in-charge. (Make: Havells Cat Part No CORALPT25WLED757PSYMTOPC or equivalent in any of the make mentioned in the list of Product)
Taking down old Aviation light and S & F Solar Aviation obstriction light with 10 Watt solar panel, 3 Watt LED light with back up of 24hrs & 12 V, 7.5 Ah Dry Battery fixed in top of 40' OH Tank with suitable MS clamp, nuts & bolts, testing and commissioning complete all as specified and directed. (Note:- Rate quoted by the contractor include the cost of all T&P, ladder, scaffolding etc required for installation of solar panel complete and nothing shall be admissible on this account.)
Supply and laying in repair GI Pipe medium grade with all fitttings fixed to walls or laid in floors/trenches of size 15 mm dia complete all as specified and directed .
All as per srl item No 40.00 above but of size 20 mm dia.
All as per srl item No 40.00 above but of size 25 mm dia.
Surface excavation not exc 30 cm deep and averaging 15 cm deep in foul condition for removing heaps of waste , cleaning of floura- founa , foliage and bushes around installations , removing debris/heaps of bushes etc from vicinity and depositing at place where directed by Engineer-in-charge
S & F in replacement Electric motor Satarter for 3 phase, 415 V, 20 HP submersiblae pump set with relay range 20-33 Amp and coil voltage 380 V, complete all as specifed and directed. (Make:- model No:- MU-G30 FASD with wideband coil, HSN code - 8536, cat part No- CS96008 COEO of L&T or equivalent in any of the make mentioned in the list of products)
S & F in replacement Electric motor Satarter for 3 phase, 415 V, 30 HP submersiblae pump set with relay range 30-50 Amp and coil voltage 380 V, complete all as specifed and directed. (Make:- model No:- MU-G40 FASD with wideband coil, HSN code - 8536, cat part No- CS90908 LOGO of L&T or equivalent in any of the make mentioned in the list of products)
S & F in replacement Electric motor Satarter for 3 phase, 415 V, 40 HP submersiblae pump set with relay range 36-60 Amp and coil voltage 380 V, complete all as specifed and directed. (Make:- model No:- MU-G40 FASD with wideband coil, HSN code - 8536, cat part No- CS90908 LOTO of L&T or equivalent in any of the make mentioned in the list of products)
Repair & Replacement auxiliary contactors 2NO-2NC pole composition 230v coil operated with add on contact block complete all as specifed and directed.
S & F in replacement auxiliary relay 2co 230v coil operated, repair the Mechanical contact position indicator, Front LED, Diode in parallel with the coil and Push test button with all accessories complete all as specifed and directed.
S & F in replacement of Ultra Sonic non contact for level monitoring for over head tank consisting of following of features:- (a) Principal:-Ultra sonic sound waves water level sensing (b) O/P Pot 4-20 ma/0-20v (c) Data transmitting output port (d) iot operation output port (e) Range 8.00 - 10.00 metres depth (f) Corrosion free Plastic body with pipe fitting.
S & F in repalcement of high torque motorized valve with gears and adopters self lubricating type, Weather proof with protection against,Over voltage jamming of valve and over current protection with manual by pass arrangement to Open/Close the valve on power failure Including taking down complete mechanical work , flanged end, jointing material, rubber gaskets, nut-bolts and piping for valve fitting of size 150mm complete all as specified and directed by Engineer in charge and consisting of following of features:- (a) Valve Size 150MM bore (b) Designed line pressure 4 kg/sq cm (c) Operating angle - 90 degree (d) Disc material - CI with nylon coating (e) Valve type -Butter fly valve PN-10 with geared motor on top (f) With iot output POT (g) With Torque 35 Nm running time 20s (h) With close off presure 1200 kpa (i) With operating voltage 230 Vac with 2 in built auxiliary switch, IP 67
Supply & Fixing in replacement on wall/ laying in ground 4 pair x 1.5 Sqmm copper conductor, PVC insulated & Sheathed, armored cable with heavy duty PVC Saddles 60 cm apart complete all as specified and directed by Engineer-in-charge.
Taking down and Repair/Replacement, and refurbishing of Programmable logic controller for expandable PLC type, onboard chip level repair, replacement of damage onboard relays expansion module 8-20 digital inputs, 6-16 digital out relays for Sewage PLC Panel of existing make, Best Performance, external memory, PN, DP, Central processing unit for the low and medium performance range of the central and decentralized control, programming by means of FBD, LAD, STL in accordance with IEC 61131-5, SCL, CFC, processing times (bin.) 0.05 μs and (floating point arithmatic) 0.45 μs, 256 counters, 384 kB RAM, data blocks 1024, address range 2 kB, 16.384 digital inputs and outputs and 1024 analog inputs and outputs can be parameterized, can be expanded to up to three module racks, operating hours counter, process diagnostics messages, start-up function, control of variables, diagnostics buffer with up to 500 entries, routing function, interfaces MPI and DP master, buffering by means of MMC, Profinet CBA communication, hardware clock (real time) supply and mount ready-to operate complete all as specified and directed
Repair, Replacement, and Refurbishing of 250watt 24v DC Switch mode power Supply by chip level repair of onboard electrolytic input and output capacitors failed, faulty inductor, FET and faulty diodes complete all as specified and directed.
Repair, Replacement, and Refurbishing of Supervisory control and data acquisition with minimum tag of 600 along with Desining & developent as per the user requirement on site along with update with the Existing system complete all as specified and directed
Repair and reprograming of schneider GXO model hmi colour high intensity replacemnt of internal CMOS battery, HMI for Pump automation, Multi-panel for operating and monitoring pumping station, use as thin client for terminal services, remote maintenance and services via the Internet/Intranet, OPC interfacing to different manufacturers, display of HTML documents, with pixel-graphics TFT- touch display with background lighting, 65536 colors, resolution 640 x 480 pixels, MTBF 50000 h, Windows CE operating system, ARM CPU, mouse and curve functions and bar display, calculation functions, external evaluations with Excel and MS Access,input/output fields, configurable buttons with 16 functions simultaneously, online evaluation using characteristics, Visual Basic Scripting, signalling system with different alarm/message classes, message buffer for 512 entries, 500 process images, 50 archieves per project, 10000 entries per archieve, recipe memory for 300 recipes,10 user groups can be set, password protection, 16 online. languages, multi media card data carrier support, time interrupt function for cyclic function processing, display of graphics, bars, predefined texts, buttons. Integrated signalling system with 4000 messages, remote download for configuring USB, MPI, Profibus DP, Ethernet, Modem, http and SD/Multi Media Card, degree of protection IP-65 on the front, according to IEC 60068-x, IEC 6199-4-x, IEC 61131-2, including operating instructions, Compact Flash card, back-up battery; supply and mount ready-to-operate complete all as specified and directed including dismantling old unserviceable complete all as specified and directed
Service/ maintenance work of pump automation panels includes both hardware and software related items. The vendor should take all needful in keeping the system under good working condition for all the time Breakdown calls,Ensure proper backups, Preventative maintenance, Proper system protection, Documentation and Spares management with following detailed check list to be a) IOT sytems of Pump automation b) Performance test of sensors c) Cleaning of system components such as sensors, resistors, valves, MODBUS controllers etc., d) Motorised valves grease or lubricate and functional check. e) 8 pin PLA relays (230VAC/24VAC) functional check. f) Control transformer primary/secondry supply check. g) Shielded communication cables functional check. h) Panel exhaust fans functional check. i) Visual checks of hmi/plc. j) Indicators funtional test. k) hmi functional and touch sentivity check. l) Smps power regualtor supply check. m) Earthing functional check. n) plc functional check. Note:- (i) Repair and replacement of items should be paid separately under the respective items of BOQ as supply & fixing. Location:- TW No 04, 05, 06, 17 & 18. (ii) In addition to monthly check up/repairs if contractor fails to attend/ rectify the complaint within 02 hours recovery will be made @ Rs. 500/- for first 02 hours and Rs 100/- for every additional hours till the fault is rectified.
Supply and commissioning of Static IP solution provider based SIM card for implement effective remote monitoring, M2M and IoT services. The cost of 1 year internet subscription included in the sim card.The cost of 1 yr Broadband connection to the existing computer at AGE E/M office is also deemed to be included in the quoted rate complete all as specified and directed
S & F in replacement VMR (Voltage Monitoring Relay) 415V, AC, 2 C/O 3/1 phase in existing LT panel by properly mounting on chanels and making connections with copper cables complete all as specified and directed by Engineer-in-Charge.
S & F in replacement Soft Starters of capacity 20 to 30 HP, 3 phase, 415 V, AC complete all as specified and directed by Engineer-in-Charge.
S & F in replacement Single phase Preventor three phase for three phase motor panels of any capacity/make complete including making connections using suitable size lugs & copper conductor cables of proper colour coding complete all as specified and directed by Engineer-in-Charge.
M & L for Repairs to Salt based electrochlorinator (Chloronome plants) by cleaning electrodes with acid/replacing the worn out parts and making/upkeeping the plant serviceable all as site requirement specified and directed by Engineer-in-Charge. (Note:- Spares will be measured and paid separetaly under respective items of BOQ as supply only.)
Supply only Electrode as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only transformer of AC to DC rectifier as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only Diode as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only DC volt meter as per existing size/capacity as and per manufacturer's design complete all as specified and directed
Supply only DC Ampere meter as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only Verisc (Varyer) as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only Dosing pump spares as per existing size/capacity and as per manufacturer's design complete all as specified and directed
Supply only pipe (PE tubing D-5/8 mm ) as per existing size/capacity (From Dozing pump to Injecting point) and as per manufacturer's design complete all as specified and directed
Supply, laying & testing in repair ductile Iron flanged pipe 150 mm dia bore shall confirm to IS-8329-2000 and 9523-2000. The pipe shall be laid in trenches/fixed vertically for pipe lines of over head tanks of 15m staging including rising mains, gravity mains, overflow pipe, wash out pipe & Header, jointed with nuts, bolts,washers, etc and tested all as per IS 12288-1987 with specials Class “K-9” . The fittings shall withstand hydrostatic pressure without showing any leakage,sweating or defects of any kind as laid down in IS complete all as specified and directed by Engr-in-charge.
Supply and replace of MS float weight into stainless steel float weight of size 1'x 1'x 1' including necessary hook and counter weight and scratching and painting the gauges, marking the levels with synthetic enamel paint complete for Mechanical water level indicator on overhead reservoir of any capacity (appx 50' to 60' height) complete all as specified and directed by Engr-in-charge.
M&L for repairing of pipe line of size 150 mm dia, in position fixed at overhead tank (appx 50'to 60' height) by using of all suitable scaffolding, mestles, ladders, cradles, chain pulley for holdiing the pipe etc incl necessary repair work such as welding,cutting ,replacing of pipe etc as per site requirement complete all as specified and directed by Engr-in-charge. (Note for srl item no. 72.00 & 73.00 :- (i) All T&P required shall be supplied by the contarctor without extra cost to the department (ii) Cutting, drilling, welding are deemed to be included in the quoted rate. (iii) In case of replacement of pipe , it should be measured and paid seperately under relevant item of Sch (iv) Required necessary safety measures during the work will be taken by contractor. if any case of mishappening due to negligency, contractor is wholly responsible for the same.)
S & F Shock treatment chart with wooden frame & glass cover of size 3'x2' complete all as directed by Engr-in-charge.
S & F Residual Chlorine testing kit at water pump houses complete all as directed by Engr-in-charge.
S & F Capacitor Bank of capacity 5 KVAr, 3Ph,Super Heavy duty, shall be housed in self-extinguishing insulating material operated on 3 Ph 415 volts AC, 50 Hz. The dielectric should be mixed dielectric type with built in over pressure safety device. Min static life expectancy is more than 115000 hrs and switched life 100000 hrs alonwith protection degree IP30 and as per IS - 13340-1986/IEC : 60831 alongwith contactor and connected with panel board. Make :- Havell's, Cat No - QHSTMC5005X0 or equivalent of equivalent in any of the make mentioned in the list of product.
All as per srl item No 76.00 above but of capacity 6 KVAr (Make: Cat part No - QHSTMC5006X0 of Havells or equivalent of equivalent in any of the make mentioned in the list of product.)
All as per srl item No 76.00 above but of capacity 7.5 KVAr ((Make: Cat part No - QHSTMC5007X5 of Havells or equivalent of equivalent in any of the make mentioned in the list of product.)
All as per srl item No 76.00 above but of capacity 10 KVAr ((Make: Cat part No - QHSTMC5010X0 of Havells or equivalent of equivalent in any of the make mentioned in the list of product.)
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) TP of current carrying capacity 32 Amp in the DB/Panel complete with connection testing and commissioning complete all as spd and directed.
Material and labour for painting of LT panels/feeder pillar boxes outdoor /indoor type of any sizes or rating installed at varoius location under GE (wset) Pathankot with two coat of super enamelled paint of approved colour with spray painting after cleaning the surface and preparing the same for painting complete all as specied and directed.
M & L for welding work to LT panels/feeder pillar box as per requirement at site to match with existing complete all as spd and directed.
M&L for MS sheet thickness 3.15 mm for repairing existing damaged panel doors due to corrison of different type and sizes complete with hinges, hot, cold welding work,fabricating, locking arrangement etc including painting with one coat of red oxide and two coats of complete all as specified and directed.
S & F in replacement of three phase Digital Ammeter 0-500 Amp, AC, including suitable range of CTs and making connections complete all as specied and directed. (Make: Schneider cat part no : METSEDM3110 or equivalent in any of the make mentioned in list of product.
S & F in replacement of three phase Digital Voltmeter 0 - 500 V, AC, including making connections complete all as specied and directed. (Make: Schneider cat part no : METSEDM3210 or equivalent in any of the make mentioned in list of product.
Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, sockets, Bracke sketch fitting, ceiling roses, lamp holders, brackets, pendants, regulators, sockets, light fitting etc. removing materials to store for taking credit and making good disturbed surfaces of walls, floors, etc complete all as specified and directed. Note:- The damaged surfaces to be made good with plastering (1:6). & applying colour wash in required coats to matching with existing surfaces as directed by Engineer-in-charge. Cost of the same deem to be included in quoted rates and nothing extra on this account admissible.
M&L for Point wiring with 1.5 Sq. mm (nominal area) FRLS PVC insulated and unsheathed multistranded copper conductor cable 1100 Volts grade drawn through and incl PVC rigid concealed conduit (ISI Marked) suitable size with all accessories having thickness not less than 1.8mm incl sheet steel/ CI terminal box of adequate size having thickness not less than 2mm including 3mm thick hylem/masonite sheet including 1.5 Sqmm FRLS PVC insulated unsheathed copper conductor multistranded cable of green colour as earth conductor connected to common earth dolly complete all as specified and directed for one light / fan point controlled by one switch 5 Amp, SP, one way, 240 Volts complete all as specied and directed. Note: 1. Connections of cable with MCBs/Switch Sockets shall be done through proper size copper/brass thimbles. 2. Conduit shall be fixed on surface of roof with necessary saddles where concealing of conduit in not feasible. 3. Proper colour code will be used for wiring as per the electrical rule and as directed.
All as per Srl item No 87.00 here-in-before but for one 5 pin 5 Amp socket outlet point on inependent board controlled by one switch SP, one way 5 Amp, 240Volts.
All as per Srl item No 87.00 here-in-before but for one 5 pin 5 Amp socket outlet point on same board controlled by one switch SP, one way 5 Amp, 240Volts.
M & L for point wiring with 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor FRLS cable with in and including PVC concealed conduit heavy duty 20mm dia having thickness not less than 1.8 mm with all fittings including anodise pressed steel sunken box having thickness not less than 2mm with 3mm bakelite laminated sheet ISI marked suitable for 5 pin 15 amps socket outlet ,including 2.5 sqmm single core PVC insulated unsheathed multistranded copper conductor FRLS cable as earth continuity conductor connected to comman earth dolly in and including cutting chiseling for concealed piping and making good disturbed surface finishing the surface to match with the existingsurface complete all as specified and directed. Note: (a) Insulation test of point wiring (b) colour coding is to be maintained
S & F switch piano flush button single pole one way 5 Amp AC 240 volts, complete all as specified and directed.
S & F switch piano flush type one way 15 amps SP 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 3 pin 5 amps flush type 240 volts complete all as specified and directed.
S & F socket outlet 2 in 1, 3 pin, 5 and 15 amps flush type 230 volts complete all as specified and directed.
S & F lamp holder/batton holder/angle holder insulated body with bakelite back plate suitable for fittings complete all as specified and directed.
M & L for ceiling rose, PVC/Polycarbonate, insulated body, surface Bakelite 65mm dia three terminals all as specified and as directed.
Supply and fixing of ceiling fan regulator electronic socket type 5 stage speed variation ISI marked complete all as specified and directed.
S&F in replacement mirror light 10 Watt LED 2' length prewired with all accessories including lamp and connected electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor 3core cable of size 0.50Sqmm complete all as specified and directed. Make :- WIPRO Cat Part No. D531065 or equivalent in any of the make mentioned in list of product.
S & F LED Bulb , B22 type ,14 watt White, complete all as specified and directed.
S&F 22W surface / wall mounted batten LED luminair, extruded aluminium housing with PC diffuser and ind electronic driver with high efficiency long life, CRI = 80 (Minimum), PF > 0.95, luminous efficacy > 100 lumens/Watt operating voltage 140V-240V, CCT (K) > 6500, THD < 10% complete including 22W LED tube rod with all accessories internally prewired and including connecting up with 3 core flexible copper conductor cable of suitable size from ceiling rose to connector of LED fitting complete all as specified and directedories prewired and including making connections with 3 core twisted flexible copper cable of size 23/.0076 from ceilling rose/PVC connector to light fittings complete all as specified and directed. Make of LED Fitting:- CROMPTON DMLN1LT8-16 or equivalent in any of the make mentioned in list of product.
S&F in replacement Energy saving, surface mounted, bulk head LED luminaire 10 W with PDC aluminium housing and polycarbonate diffuser with IP 66 protection complete including connecting up with three core twisted flexible copper conductor cable of suitable size.all as specified. Make :- CROMPTON Cat Part No. LBHP-10-CDL or equivalent in any of the make mentioned in list of product.
S & F of sheet metal enclosure MCB distribution board, double door with IP-43 protection single phase 240 volts 6 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good the distributed wall surfaces to match with existing specification complete all as specified and directed by Engr-in-charge.
S&F MCB SP 240V, 50Hz, 10 KA, 'C' curve of rating 6 to 32 Amp complete all as specified and directed.
S&F MCB SPN 240V, 50Hz, 10 KA, 'C' curve of rating 6-32 Amp complete all as specified and directed.
M&L for sub Main Wiring with 2 run of single core, 6 Sqmm FRLS PVC insulated and unsheathed, multi starndedcopper conductor cable using colour code for phase red and neutral black with and including 6 Sqmm FRLS PVC insulated and unsheathed copper conductor cable in green colour as earth conductor connected to common earth dolly, drawn in and including concealed PVC rigid conduit of suitable size having thickness not less than 1.8mm (ISI marked) with and including all accessories complete and making good to disturbed surface of wall/floor with cement mortar and finishes to match existing surface including taking down of existing unserviceable surface/cocealed sub main wiring any type complete all as specified and directed. Note: Two run of submain wire (phase and neutral), and one run of earth including PVC conduit and accessories will be measured as one run.
Demolition of brickwork or stone/ boulder masonry, built in lime mortar including all quoins, arches, pillar, etc, but excluding ashlar facings, dressed stonework and precast concrete articles complete all as specified and directed.
Notes :- (a) The contract sum shall be arrived at after deduction of amount of Schedule of Credit. (Rs. 1,74,675.00). (b) PERFORMANCE SECURITY :- (Refer condition 19 of IAFW-2249) The performance security for an amount equivalent to 3% (Three percent) of the accepted contract sum shall be delivered by the successful bidder immediately after the date of intimation letter of acceptance and all provisions shall be applicable as per condition 19 of IAFW 2249
M/S GULATI ENGINEERING WORKS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .