Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹19.4 LAdmitted-Finance | -44.56% | ₹19.4 L | L1 | Admitted-Finance |
| 2 | L2₹22.0 LAdmitted-Finance | -37.40% | ₹22.0 L | L2 | Admitted-Finance |
| 3 | L3₹25.7 LAdmitted-Finance | -26.80% | ₹25.7 L | L3 | Admitted-Finance |
| 4 | L4₹27.4 LAdmitted-Finance | -22.00% | ₹27.4 L | L4 | Admitted-Finance |
| 5 | L5₹29.3 LAdmitted-Finance TETHAR BANIHAL | ANANTNAG | JAMMU AND KASHMIR | 192101 | -16.50% | ₹29.3 L | L5 | Admitted-Finance |
Tender Value
₹35.1 L
EMD Value
₹70,160
Closing Date
11 Feb 2026, 4:00 pmClosed
ADGP Hqrs PHQ
Jammu
Electrification
2026_DGPJK_302209_1
e-NIT/EE-PCD/PHQ/180/2025-26
Open Tender
Electrical Works
90 days
Police Station Ramcoo
Please refer Tender documents.
4 documents required · 4 mandatory
₹2,000
Exen PCD PHQ
₹70,160
12 Feb 2026
4 Feb 2026
12 Feb 2026
4 Feb 2026
11 Feb 2026
5 Feb 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in Existing surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FR PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 1 No 4 sq. mm FR PVC insulated copper conductor single core cable for loop earthing as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in surface/Recessed medium class PVC conduit as required.
2 X 2.5 SQ.MM + 1 X 2.5 SQ.MM EARTH WIRE.
2 X 6 SQ.MM + 1 X 6 SQ.MM EARTH WIRE.
2 X 10 SQ.MM + 1 X 6 SQ.MM EARTH WIRE.
4 X 16 SQ.MM + 2 X 6 SQ.MM EARTH WIRE.
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess , including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection, painting etc. as required.
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, painting etc. as required.
Supplying & fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB, "C" curve including connections, painting etc. as required
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board 2 rows , 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way , Double door.
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
6 way (4 + 18), Single door*
8 way (4 + 32), Single door*
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required
40Amp Isolator*
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40Amp Isolator*
Supplying and Laying of 1 No. PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe/Cable Tray as Required. .
4C x25 mm²PVC Almunium Cable
3.5C x95 mm²PVC Almunium Cable
3.5C x150 mm²PVC Almunium Cable
Supply and make end termination with brass and almunium lugs for following sizes of PVC Insulated /PVC Sheath /XLPE almunium conductor Cable of 1.1KV Grade as required
4 x 25mm² (28mm)*
3.5 x 95 mm² (45mm)*
3.5 x 150 mm² (50mm)*
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required.
90 mm dia (OD-90 mm & ID-76 mm nominal)
SITC of pre-wired concealed type LED Down Light 15 Watts including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required .
SITC of pre-wired 4ft type LED Tube Light 40 Watts surface monted including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required .
SITC of pre-wired external Flood Light W/P IP65 including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required .
Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block including connection etc as required.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
Telephone socket outlet
TV antenna socket outlet
Bell push
Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following size/ modules, GI box along with modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75mmX75mm)
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper conductor, single core cable etc. as required.
1200mm Ceiling Fan Including all accessories & Fitting
250mm Exhast Fan Including all accessories & Fitting
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. ard.
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Supplying and laying 1c x 10 sq mm copper cable with pvc insulation through 32mm PVC Conduit, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.
Supplying and drawing following pair 0.5 mm dia FRLS/HFFR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required
SITC of 35ltr Gyser
Supplying, Installation, Testing and commissioning of CAT6A Copper Information Outlet (IO) with face plate of color as per site requirement, should have ETL/UL verification program certificate for compliance with ANSI/TIA-568.2-D. All copper Cable and Components should be from same OEM to maintain compatibility and interoperability etc. complete as required.
Supplying, Installation, Testing and commissioning of RJ45 Connector for CAT 6/6A Cables. RJ45 modular plug supports 4 twisted pairs, 8 positions, 8 connectors. Housing: PC, UL94V-2, transparent color, Use for 24- 26 AWG stranded wires etc. complete as required.
Supplying, drawing, Installation, Testing and commissioning of CAT6 UTP LSZH 1 Run of Cable
Supply installation commissioning of 6U Rack
Supplying, fabrication, installation, testing and commissioning of cubical type LT panel enclosure made out of CRCA steel sheet of minimum 2.0 mm thickness, suitable for 415 V, 3-phase, 4-wire system, complete with powder coating, gasket, hinges, locks and all accessories, as per IS 8623 / IEC 61439. Approximate enclosure size:0.9 m (W) × 0.6m (H) × 0.30 m (D). Gland Plates must be 3.0 mm Thick The rate shall be inclusive of all materials, fabrication, surface treatment, hardware, accesories Indicator, manual Change over switch , Fuses Control Wires ,CT, PT, Trip Indicator, MFM, relays etc as per SLD labour, testing and commissioning, complete in all respects. Alminium Bar should be of rating minimum 100A alminium and fault level shoild be 25KA for 1 sec (SMDB-SHO-GF) INCOMER MCCB 63 Amps FP (1 No) OUTGOINGS MCCB 40 Amps FP (1 No) MCB 63 Amps DP (1 No) MCB 40Amp DP (1 No.) MCB 32Amp DP (1 No.) 100A FP Manual Changeover Switch
Supplying, fabrication, installation, testing and commissioning of cubical type LT panel enclosure made out of CRCA steel sheet of minimum 2.0 mm thickness, suitable for 415 V, 3-phase, 4-wire system, complete with powder coating, gasket, hinges, locks and all accessories, as per IS 8623 / IEC 61439. Approximate enclosure size:1.0 m (W) × 0.9m (H) × 0.40 m (D). Gland Plates must be 3.0 mm Thick The rate shall be inclusive of all materials, fabrication, surface treatment, hardware, accesories Indicator, manual Change over switch , Fuses Control Wires ,CT, PT, Trip Indicator, MFM, relays etc as per SLD labour, testing and commissioning, complete in all respects. Alminium Bar should be of rating minimum 200A alminium and fault level should be 36KA for 1 sec (SMDB-LSQ-GF) INCOMER MCCB 125 Amps FP (1 Nos) OUTGOINGS MCCB 40 Amps FP (1 Nos) MCB 63 Amps DP (1 Nos) MCB 40Amp DP (16No.) MCB 10Amp SP (2No.)
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
BOQ_980604.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid