Loading…
Loading…
Tender Value
₹13.4 L
EMD Value
₹26,800
Closing Date
24 Aug 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
PND WORKS
12 conditions · 1 needing a document upload
No Technical & Financial eligibility criteria are required for the work costing upto 50 Lakhs but recent documents should be submitted in evidence of tenderer's capacity to carry out the work efficiently and of sound financial capacity. In addition, the tenderer should submit Electrical Contractor license, recent Income tax Return clearance, pan card, GST registration certificate & the tenderers shall submit a self- declarationas per tender condition etc.Note:- Non-Submission of Valid Electrical Contractor License, Recent Income Tax Return Clearance or Balance sheet, GST Registration Certificate, PAN Card by the Bidder shall result in summarily rejection of his/their bid.The firm may submit work experience certificate related to electrical works, Bank Mandate form, Cancelled Cheque, EPF, ESI, Trade License, etc (If available).The tenderer shall have submitted an undertaking that he is not blacklisted or debarred by Railways or any other Ministry/Department of Govt. of India from participation in tender on the date of opening of bids, either in individual capacity or as a member of the partnership firm or JV in which he was/is a partner/member (Format in Annexure-VA). Concealment/wrong information in regard to above shall make the contract liable for determination under Clause 62 of the General Conditions of Contract.
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
6 conditions · 4 needing a document upload
GST registration certificate along with its supportive documents as per GCC 2022 or its latest amendments must be summitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
Recent Income Tax Return clearance 'OR' Balance sheet must be submitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
PAN Card must be submitted by the firm. Note:- Non-submission of this document by the bidder shall result in summarily rejection of his/their bid.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
GCC 2022 and its all amendments from Railway Board will be followed.
Renovation of development of Schaku Coupler section as centre of excellence for electrical (G) works under the jurisdiction of Dy.CEE/G/KPA
KPA-EG-OT-02-26-27
KPA-EG-OT-02-26-27
Open
Works - General
12 Months
North 24 Parganas, West Bengal
₹0
₹26,800
24 Aug 2026
31 Jul 2026
10 Aug 2026
77 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 13,38,621.17 | ||
| — | — | — | 4,577.3 | ||
| Supply, erection, testing and commissioning of LT XLPE cable gland with aluminium sockets (4 Nos.) suitable for LT 4 core (50-95) sq.mm XLPE aluminium conductor armoured cable. | — | 14.00 | — | — | |
| — | — | — | 3,021.44 | ||
| Supply, erection, testing and commissioning of LT XLPE cable gland with aluminium sockets (4 Nos.) suitable for LT 4 core (120-185) sq.mm XLPE aluminium conductor armoured cable. | — | 8.00 | — | — | |
| — | — | — | 1,10,145 | ||
| HT/LT cable trenching in underground by digging earth and protection of the cable with sand and brick and filling with earth after laying of cable including making good of damages as per CEE/E.Rlys Drg. No. E4 GPST/033/87 | — | 500.00 | — | — | |
| — | — | — | 43,405.5 | ||
| Supply and laying of 100mm dia. heavy duty GI pipe confirming to IS:1239 (Part-1) underground by cutting trench/road/track recessing in wall/platform/along with Rly. Track etc. (Make: As per Annexure-l) | — | Breakup for | details. | — | |
| — | — | — | 74,298 | ||
| Supply, laying & fixing of FRP cable tray of size 300mm including supports, nuts, bolts, washers and other accessories. | — | Breakup for | details. | — | |
| — | — | — | 12,135.5 | ||
| Laying of cable through trench, GI Pipe, HDPE pipe, PVC pipe, FRP cable tray,cable duct etc. with making good of damages after laying of cable and connection with switchgears along with necessary materials as required. N.B: only cable will be supplied by Rly, all other materials required during execution of work and connection to be supplied by the firm. | — | 650.00 | — | — | |
| — | — | — | 9,865.5 | ||
| Laying, jointing, connection, testing & commissioning of LT cable 1100V grade of sizes upto 95 sq.mm along the wall by necessary clamping arrangement including socketing and termination with epoxy end jointing where necessary. Clamps should be made of 50mm x 6mm MS flat. N.B: Only cable will be supplied by Rly, all other materials required during execution of work and connection to be supplied by firm. | — | 150.00 | — | — | |
| — | — | — | 25,742 | ||
| Laying, jointing, connection, testing & commissioning of LT cable 1100V grade of sizes above 95 sq.mm along the wall by necessary clamping arrangement including socketing and termination with epoxy end jointing where necessary. Clamps should be made of 50mm x 6mm MS flat. N.B: Only cable will be supplied by Rly, all other materials required during execution of work and connection to be supplied by firm. | — | 200.00 | — | — | |
| — | — | — | 59,629.94 | ||
| Supply, installation, connection, testing and commissioning of 4 pole 400 A, 415 V, 50 Hz MCCB of 50KA breaking capacity with adjustable thermal magnetic trip unit, over load, earth fault and short circuit protection in a suitable powder coated sheet steel enclosure with all accessories including connection with gland, socketing, cable entry box etc. as required. (Make: As per Annexure-l). | — | Breakup for | details. | — | |
| — | — | — | 46,040.68 | ||
| Supply, installation, connection, testing and commissioning of 4 pole, 250A, 415V, 50Hz MCCB of 35/36 KA breaking capacity with adjustable thermal magnetic trip unit, over load, earth fault and short circuit protection in a suitable powder coated sheet steel enclosure with all accessories including connection with gland, socketing, cable entry box etc. as required. (Make: As per Annexure-l). | — | Breakup for | details. | — | |
| — | — | — | 86,773.56 | ||
| Supply, installation, connection, testing and commissioning of 4 pole, 160A, 415V, 50Hz MCCB of 35/36 KA breaking capacity with adjustable thermal magnetic trip unit, over load, earth fault and short circuit protection in a suitable powder coated sheet steel enclosure with all accessories including connection with gland, socketing, cable entry box etc. as required. (Make: As per Annexure-l). | — | Breakup for | details. | — | |
| — | — | — | 6,006.2 | ||
| Supply, installation, connection, testing and commissioning of suitable size 4 pole copper busbar of 100A capacity including 4 way sheet steel enclosure having a minimum size of 400mm x 300mm x 150mm with proper fixing arrangement along with incoming and outgoing cable connection with socketing and gland etc. | — | Breakup for | details. | — | |
| — | — | — | 5,677.2 | ||
| Supply, installation, connection, testing and commissioning of suitable size 4 pole copper busbar of 200A capacity including 4 way sheet steel enclosure having a minimum size of 400mm x 300mm x 150mm with proper fixing arrangement along with incoming and outgoing cable connection with socketing and gland etc. | — | Breakup for | details. | — | |
| — | — | — | 10,990.55 | ||
| Supply, installation, testing and commissioning of 8 way SPN MCB DB consisting of the followings: (i) 8 way SPN MCB DB -1 No. (ii) SP MCB / Isolator (40A) - 1 No. (iii) SP MCB (6-32 A) - 7 Nos. (Make : As per Annexure-l) | — | Breakup for | details. | — | |
| — | — | — | 3,35,698.28 | ||
| Supply, installation, connection, testing and commissioning of indoor type 14 SWG LT M.S. Distribution panel board with castle lock arrangement consisting of the following: (i) MCCB 400 A, 4 pole, 35/36 kA, 415 V - 2 Nos. (ii) MCCB 200 A, 4 pole, 35/36 kA, 415 V - 4 Nos. (iii) MCCB 100 A, 4 pole, 35/36 kA, 415 V - 3 Nos. (iv) Multi functional Digital type metering system such as energy meter, trivector meter, voltmeter, ammeter etc. with LED indication lamp - 1 set (v) 4 pole copper busbar of 800 A or higher capacity - 1 set. (vi) Suitable MS Enclosure - 1 set. The work also includes dismantling of existing panels, if any. (Make : As per Annexure-l) | — | Breakup for | details. | — | |
| — | — | — | 12,038 | ||
| Wiring of main / sub-main line in casing-capping / conduit with 02 Nos. 6 sq.mm (for phase and neutral) and 01 No. 2.5 sq.mm (for earth connection continuity) copper wire in suitable size heavy gauge PVC pipe including all other accessories with dismantling of existing wiring, if any, and making good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ZHFR/FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 100.00 | — | — | |
| — | — | — | 30,876 | ||
| Wiring of main / sub-main line with 02 Nos. 4 sq.mm (for phase and neutral) and 01 No. 2.5 sq.mm (for earth connection continuity) copper wire in casing-capping / conduit in suitable size heavy gauge PVC pipe including all other accessories with dismantling of existing wiring, if any, and making good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ZHFR/FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 300.00 | — | — | |
| — | — | — | 48,308.04 | ||
| Wiring of light, fan, exhaust fan, wall bracket fan, call bell etc. with 02 Nos. 1.5 sq.mm (for phase and neutral) and 01 No. 1.5 sq.mm (for earth connection continuity) copper wire in casing-capping / conduit in suitable size heavy gauge PVC pipe with provision of suitable size PVC board, switch, fuse, indicator lamp, ceiling rose, angular holder and all other required accessories & fixing and commissioning electronic fan regulator in case of fan point (excluding supply of fan & electronic regulator) with dismantling of existing wiring (if any) including make good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ZHFR/FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 99.00 | — | — | |
| — | — | — | 8,250 | ||
| Supply of LED Tube light, T-8, 4 ft, 18-22 W (Retrofit type), SMD LED chip, life span of LED >/= 50,000 burning hours, CRI >/= 70, system efficacy >/= 120 lm/W, color temperature: 6500 K (cool white), PF >/= 0.9 with inbuilt driver having short circuit protection and driver efficiency >/= 85% with aluminium / polycarbonate housing & polycarbonate diffuser, IP 20 suitable for 220 -240 V AC, 50 Hz. (Make : As per Annexure-l) | — | 50.00 | — | — | |
| — | — | — | 5,251 | ||
| Supply of batten suitable for 1 No. LED tube light of 4 feet long, both side holder, without ballast and starter with copper wiring having protection of IP65. | — | 50.00 | — | — | |
| — | — | — | 7,857 | ||
| Fixing, connection, testing and commissioning of LED tube light fittings with batten for indoor use with suitable size GI clamps and GI nut bolts and PVC insulated twin copper flexible cord as connected lead including old fittings to be removed. | — | 50.00 | — | — | |
| — | — | — | 53,970 | ||
| Supply and testing of LED surface mounted ceiling light having 2ft x 2ft flat panel, 34-38 W, life span of LED >/= 50,000 burning hours, CRI >/= 70, system efficacy >/= 100 Lm/W, color temperature: 6500 K (cool white), PF >/= 0.9 with inbuilt driver having short circuit protection with aluminium / polycarbonate housing & polycarbonate diffuser, IP20 suitable for 220 -240 V AC, 50 Hz. (Make : As per Annexure-l) | — | 30.00 | — | — | |
| — | — | — | 6,313.2 | ||
| Fixing, connection, testing & commissioning of LED surface mounted 2ft x 2ft flat panel ceiling light with necessary arrangement and accessories. | — | 30.00 | — | — | |
| — | — | — | 63,593.57 | ||
| Supply, fixing, connection, testing and commissioning of wall bracket fan of 400mm sweep, 230V, 50Hz including all accessories. (Make : As per Annexure-l) | — | Breakup for | details. | — | |
| — | — | — | 34,080 | ||
| Supply of BLDC ceiling fan, 1200mm sweep, 5 star rated, remote controlled with battery, double ball bearing, single phase, 230V AC, 50Hz, IS:374:2019 or latest with accessories including remote, canopies, nuts, bolts, clamps, etc. (Make : As per Annexure-l) | — | 15.00 | — | — | |
| — | — | — | 1,957.35 | ||
| Installation, connection, testing and commissioning of the ceiling fan by suitable size GI clamps made of GI flat / 'S' hook & GI nut-bolts including PVC insulated twin copper flexible cord as connected lead. N.B: All materials required for execution of the work & connection is to be supplied by the firm. | — | 15.00 | — | — | |
| — | — | — | 52,864 | ||
| Supply of BLDC wall mounted (girder) air circulator propeller fan of 750mm sweep, single phase, 220-230 V AC, 160-200 W (Make : As per Annexure-l) | — | 4.00 | — | — | |
| — | — | — | 4,212.4 | ||
| Installation, connection, testing and commissioning of the BLDC wall mounted (girder) air circulator fan by suitable size GI clamps & GI nut-bolts including PVC insulated twin copper flexible cord as connected lead. | — | 4.00 | — | — | |
| — | — | — | 4,366.8 | ||
| Supply, fixing and Wiring of multi-plug point power supply board in casing-capping / conduit with 02 Nos. 4 sq.mm (phase and neutral) and 01 No. 2.5 sq.mm (for earth connection continuity) copper wire in suitable size heavy gauge PVC pipe and suitable size individual PVC board consisting of the following: (i) 03 Nos. 6A - 3/5 pin plug-socket (ii) 03 Nos. 6 A switch (iii) 01 No. 16A - 3/ 5/6 pin plug-socket (iv) 01 No. 16 A switch (v) 01 No. 16A kit-kat fuse (vi) 01 No. indicator with all other required accessories with dismantling of existing wiring (if any) and making good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ ZHFR/ FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 6.00 | — | — | |
| — | — | — | 4,447.6 | ||
| Supply, fixing and wiring of 6A plug-socket point in casing-capping / conduit with 02 Nos. 2.5 sq.mm (phase and neutral) and 01 No. 1.5 sq.mm (for earth connection continuity) copper wire in suitable size heavy gauge PVC pipe and suitable size PVC board consisting of: (i) 01 No. 6A - 3/5 pin plug-socket (ii) 01 No. 6 A switch (iii) 01 No. 6 A kit-kat fuse with all other required accessories with dismantling of existing wiring (if any) and making good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ ZHFR/ FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 20.00 | — | — | |
| — | — | — | 7,425 | ||
| Wiring of 16A plug-socket point in casing-capping / conduit with 02 Nos. 4 sq.mm (phase and neutral) and 01 No. 2.5 sq.mm (for earth connection continuity) copper wire in suitable size heavy gauge PVC pipe and suitable size individual PVC board consisting of:(i) 01 No. 16A - 3/5/6 pin plug-socket (ii) 01 No. 16A switch (iii) 01 No. 16A kit-kat fuse(iv) 01 No. LED indicatorwith all other required accessories with dismantling of existing wiring if any and making good of wall / ceiling surface as its original condition. Copper wire should be PVC insulated multi strand single core FR/ ZHFR/ FRLSH 1100V grade conforming to IS 694:1990 or latest. (Make : As per Annexure-l) | — | 10.00 | — | — | |
| — | — | — | 1,439.6 | ||
| Powder coated wall mounted metallic stand with accessories suitable for outdoor unit of 1.5 Ton high wall split air-conditioner including installation, testing and commissioning of the same at wall with suitable nuts, bolts, fasteners, washer and other required accessories. | — | 2.00 | — | — | |
| — | — | — | 9,800 | ||
| Copper refrigerant pipe (1/2 inch dia. and 1/4 inch dia.) with thermal insulation suitable for 1.5Ton high wall split air-conditioner. | — | 10.00 | — | — | |
| — | — | — | 865.6 | ||
| water proof, heavy duty, thermal insulating, self-adhesive, protective PVC wrapping tape, white/cream colored, 48mm width (min.), 20 mtr. Long (min.) in a roll, for protection of copper refrigerant tube/pipes of air-conditioner. | — | Breakup for | details. | — | |
| — | — | — | 2,154.4 | ||
| Water drain pipe with accessories suitable for high wall split air-conditioner. | — | 20.00 | — | — | |
| — | — | — | 4,102.14 | ||
| Supply, fixing & connection of 32/25 Amps SPN/DP modular MCB & starter suitable for single phase AC machines of capacity upto 2 Ton in suitable board with all accessories including 16A / 25A Shuttered plug socket. (Make : As per Annexure-l) | — | Breakup for | details. | — | |
| — | — | — | 1,20,979.98 | ||
| Supply, installation, testing & commissioning of 63A, 415V, 3 phase metal type industrial power plug-socket assembly with 63A, 25/26kA, 4P MCCB in a suitable powder coated MS enclosure with all accessories including connection with gland, socketing etc. as required | — | 6.00 | — | — | |
| — | — | — | 19,462.84 | ||
| Supply, digging, insertion, testing and commissioning of earth pipe made of heavy duty GI pipe of size 50 mm dia, 3 mtr long including construction of earth pit and each pit should be provided with 2 Nos. of above pipe duly shorted by suitable length of G.I flat (50 mm x 6 mm) including necessary earth connection from pit to the distribution panel with 4 SWG GI wire. The earth pit should be encashed with panel with alternate layer of salt and charcoal to be spreaded inside the pit. Earth pit shall be completed with necessary civil work like brick chamber, PCC work & finally covered with medium duty cast iron hinged cover of size 400mm x 400mm. (Make of GI pipe : As per Annexure-l) N.B: The earthing should be done as per CEE/KKK's specification. All earth value should be marked on MS plate with date by painting work. The MS flat, plate should be painted by one coat of red oxide and 2 coats of black paint before execution. The marking should be done by white paint. | — | Breakup for | details. | — |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC2022.pdf
ATTACHMENT
AdvancecorrectionslipsofGCC2022.pdf Advance correction slips of GCC2022
ATTACHMENT
TenderDocument.pdf
ATTACHMENT
Scheduleofwork.pdf
ATTACHMENT
MakeAnnexure-1.pdf
ATTACHMENT
GeneralSpecification.pdf
ATTACHMENT
Checklist.pdf
ATTACHMENT
Annexure-IaIbIIIIIVVA.pdf
ATTACHMENT
Annexure-IVVIVIAVIIVIII.pdf
ATTACHMENT
SharamikKalyalSpecialCondition.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .