Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.4 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹14.4 L+₹522 (0.04%)Rejected-AOC | L2 | Rejected-AOC Rejected | |
| 3 | Rejected-Technical | - | Rejected-Technical Not enlisted in appropriate category | |
| 4 | Rejected-Technical | - | Rejected-Technical Not submitted all documents as per NIT |
Tender Value
₹16.5 L
EMD Value
₹33,000
Closing Date
23 Apr 2022, 6:00 pmClosed
Commander Works Engineers Navy
Commander Works Engineers Navy Military Engineer Services Fort St George Rajaji Salai Chennai 600 009
82500 PROVISION OF NEW ADDRESSABLE FIRE DETECTION SYSTEM AT COMNETCEN UNDER AGE(I) NAVY CHENNAI
2022_MES_511189_3
CWE/NAVY/CHN/82500/E8 of 2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
150 days
Chennai
As per tender documents
9 documents required · 9 mandatory
₹500
AGE(I) NAVY CHENNAI
₹33,000
Yes
26 May 2022
9 Apr 2022
25 Apr 2022
9 Apr 2022
23 Apr 2022
9 Apr 2022
Amount
Supply, installation, Testing & Commissioning of Microprocessor based 2 loop capacity, Networkable analogue addressable type fire alarm control panel complying with BSEN 54 with min.600 character LCD display, The panel should be equipped with sufficient numbers of 1 loop with up to 10 to 15% spare capacity with each loop having a capacity of minimum 99 detectors and 99 analog addressable devices in one loop. Four access levels, capable of taking Flash Scan devices, flash EPROM sufficient numbers of programmable relay controls for controlling fire hydrant pump, 240 volts AC power supply, automatic battery charger including 24 volts sealed lead acid batteries suitable for 24 hours normal working and then be capable of operating the system for 2 hours during an emergency conditions as required and panels shall have provision of integration with BMS System all as specified and directed. NOTE: (i) No extra payment shall be made for any additionally connected items and contractor shall be completely responsible for making the AFDS completely functional as per the particular specifications.
Supply, installation, Testing & Commissioning of LANDLINE FIRE ALARM AUTO DIALER with sms and memory available to store 10 phone numbers dialling facility to get the intimation about the location of the area built in Emergency Speech Dialler with 8 Numbers & 1/2 Messages, NO/NC contacts for both fire and fault, Automatic changeover arrangement to standby supply with battery charger with low battery indication, Fault/failure indication such as main fail, short, open, battery fail etc, micro-controller based system, both dialling modes can be cased (Pulse/Tone), Recorded message playback speaker provision available complete all as specified and as directed
Supply, installation, Testing & Commissioning of analog addressable Multi Criteria (Optical/smoke + thermal/heat) detectors complying with and type certified to EN-45 addressable type smoke detector Photoelectric /Optical with base with self built intelligence as per IS:11360 alongwith mounting accessories and connected items complete all as specified and as directed.
Supply, Installation, Testing & Commissioning addressable Manual call point (Pull down/Break Glass Type). The device shall have an LED which shall blink in normal state and get steady on activation to monitor the health status of the device and shall be underwriters laboratories listed, semi flush type alongwith mounting accessories and connected items complete all as specified and as directed.
Supply, Installation, Testing & Commissioning of Strobe lights cum hooter single stage continuous normal operation with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of +5 DB 1000 mtrs range with 110 cd alongwith mounting accessories and connected items complete all as specified and as directed.
Supply, Installation, Testing & Commissioning of fault isolator module with automatic resetting arrangement alongwith mounting accessories and connected items complete all as specified and directed.
Supply, Installation, Testing & Commissioning of Addressable control modules for Access control Integration for Hooters / Sounders / Strobes and connected items complete all as specified and directed.
Supply, Installation, Testing & Commissioning of Addressable monitor modules and connected items complete all as specified and directed.
Supply, Installation, Testing & Commissioning of Input module and connected items complete all as specified and directed.
Supply, Installation, Testing & Commissioning of UV-IR Flame detector with built in test explosion enclosure sensate to a wide range of flammable fuels including hydrocarbons, sulphur, hydrazine and ammonia etc alongwith mounting accessories and connected items complete all as specified and directed.
Material and labour for sub main wiring concealed type with two runs of single core 1.5sqmm PVC insulated, unsheathed multistranded copper conductor 1100 volts FRLS cable, with one run of 1.5sqmm single core PVC insulated unsheathed multistranded copper conductor 1100 volts FRLS cable as earth continuity conductor drawn through and including one run of metallic steel conduit not less than 25mm dia including conduit accessories etc complete all as specified and as directed. Note: (i) Two runs of main cable, one run of earth continuity conductor cable and one run of Metallic steel conduit will be measured as one unit for payment purpose. (ii) It shall be the responsibility of contractor to make the distrubed surfaces good and the quoted rates shall be inclusive of the same.No extra payment shall be made on this account.
Supply and fixing of online ups with battery of size 3KVA, complete all as specified and as directed
Material and labour for sub main wiring concealed type with two runs of single core 6 sqmm PVC insulated, unsheathed multistranded copper conductor 1100 volts FRLS cable, with one run of 4 sqmm single core PVC insulated unsheathed multistranded copper conductor 1100 volts FRLS cable as earth continuity conductor drawn through and including one run of non metallic PVC conduit not less than 25mm dia including conduit accessories etc complete all as specified and as directed. Note: (i) Two runs of main cable, one run of earth continuity conductor cable and one run of PVC conduit will be measured as one unit for payment purpose.(ii) It shall be the responsibility of contractor to make the distrubed surfaces good and the quoted rates shall be inclusive of the same.No extra payment shall be made on this account.
Continental Engineers and contractors
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .