CoA CEERI PILANI
CSIR CEERI PILANI
Provision of air conditioning work for Millimeter wave lab Climate response building MEMS SSMG(RN 132A 132B and 133 at First floor at CSIR CEERI Pilani Rajasthan
2026_CSIR_281860_1
13-8(180)/2026-EME
Open Tender
Electrical Works
45 days
CSIR CEERI PILANI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
DIRECTOR CSIR CEERI PILANI
₹62,130
Yes
25 Jun 2026
25 Jun 2026
10 Jul 2026
25 Jun 2026
9 Jul 2026
25 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply,installation,testing,commissioning of following modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled outdoor units suitable for cooling and heating having 100% hermetically sealed inverter type rotary/ scroll compressor(s),minimum two compressors(with individual separate PCB) for above 14HP module,microprocessor based controller,top discharge type condensing unit(s), with R-410A refrigerant or equivalent,Vibration isolators with suitable duly primered and painted MS stand and suitable masonary foundation work etc. complete as required.To have a better efficiency condenser fan shall be capable to operate at different speed with respect to load.The unit shall deliver the rated capacity and in confirmation as per IS 18728:2024 and CPWD specification and work even at 50 degree celcius ambient temperature without tripping.The unit shall be suitable to work on 400V +/-10%,3 Phase,50 Hz AC power supply and BMS compatible.The unit shall be filled with first charge of refrigerant and ready for use as required.The condenser should be coated with hydrophilic film to prevent water accumulation on the surface of the heat exchanger,enhance water dispersion and reduce the risk of degradation,thereby improving overall performance and durability.The ISEER of the unit shall be as per ECSBC-2024 as below and complete as per CPWD specification ,connections and interconnections etc. as required. (For Capacity < 40kWr ISEER 5.4,Capacity > 40 and <70 ISEER 5.5, Capacity > 70 ISEER 5.6 for ECSBC building) | |||||
| 1.1 | Outdoor unit- 20HP | - | No. | - | - |
| 1.2 | Outdoor unit- 18HP | - | No. | - | - |
| 1.3 | Outdoor unit- 14HP | - | No. | - | - |
| 2Supply,installation,testing,commissioning of following minimum capacity VRV/VRF High wall type Indoor unit equipped with washable synthetic media pre filter,fan section with low noise fan/dynammically balanced blower,multispeed motor,coil section with DX copper coil,electronic expansion valve,outer cabinet,cord less remote control,drain pan, neceessary accessaries etc., suitable for operation on 230V +/- 10%, 50Hz,single phase AC supply,complete as required.The unit shall have force shut down provision in case of fire on receiving signal from BMS system.The cooling capacity of indoor unit will be at air inlet conditions of 27 degree C DB and 19 degree C WB temperature. (Make will be same as of outdoor unit) | |||||
| 2.1 | High Wall type Indoor unit 2.0 TR | - | Nos. | - | - |
| 2.2 | High Wall type Indoor unit 1.5 TR | - | Nos. | - | - |
| 3Supplying and installaton following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors,bends,tee etc. fitted on wall/floor/ceiling i/c base of suitable size MS/GI angle, bolts & nuts, painting suspenders, fastener etc as required. | |||||
| 3.1 | 300 mm width X 62.5 mm depth X 2.0 mm thickness | - | RMT | - | - |
| 4Laying and fixing one number of PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on surface wall as required. | |||||