Construction of PHC Building Jakhouli Kaman
2026_HRY_550352_1
2026601CFBA5 3E12 48F2 AD87 CC08EFDA18632167DEV
Open Tender
Civil Works
Works
720 days
JAKHOLI KAMAN JAKHOLI KAMAN
2 documents required · 2 mandatory
₹15,000
₹7.4 L
Yes
25 Sept 2026
25 Sept 2026
12 Oct 2026
25 Sept 2026
9 Oct 2026
25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Providing and fixing in position the industrial type pressure gauges with gun
metal / brass valves complete as required (DSR 23.34.8) | 6 | Each | - | - |
| 2 | Control Panel :- Fabrication, supplying, Installation testing and commissioning
of Electrical control panel of cubical construction, floor mounted type, fabricated
out of 2mm thick CRCA sheet, compartmentalised with hinged lockable doors,
dust and vermin proof, powder coated of approved shade after 7 tank treatment
process, cable alley, inter-connection with suitable size copper conductor
cable/solid copper strip, having switchgears and accessories, mountings and
internal wiring, earth terminals, numbering etc. complete in all respect, suitable for
main fire pump, pressurisation pump and diesel pump set complete as per CPWD
specification with following in coming and Outgoings, suitable for operation on 415V,
3 phase, 50Hz Ac Supply with enclosure protection class IP 42 as required:
Incomings
400A, 50kA 4 Pole MCCB, Ics=100% Icu Rating
Digital Voltmeter 0-500V with selector switch Ammeter (0-400 A) with selector
swtich and CTs etc. LED type RYB phase indicating lamps, ON, OFF, trip indicating lamps
Set of Copper Bus Bar 500Amps
Outgoings
(Note: All outgoing feeders for pumps should have digital Ammeter with selector
switches, and LED type ON, OFF, trip indicating lamps)
Main Fire Pumps
125 Amp, 50kA TPN MCCB, Ics=100% Icu, with fully automatic Star/Delta starter
suitable for 60 hp pump. with overload protection, current sensing type single phase
preventor complete with all acceessories and internal wiring required for
automatic operation, selector switch for local/remote, auto/manual/OFF operation. -
2 sets Jockey Pump
63 Amp, 50kA TPN MCCB, Ics 100% Icu, with Suitable HP fully automatic Star/Delta
starter with overload protection, current sensing type single phase preventor
complete with all acceessories and internal wiring required for automatic
operation, selector switch for local/remote, auto/manual/OFF operation. 2 sets
Diesel Engine Control Control for diesel engine comprising -Automatic/Manual selctor
switch and 3 attempts starting device, timers and relays as required, push buttons,
start/stop in manual mode Indicating lamp for high/Low Lub. Oil pressure, High
Water Temp and Engine on indication
Battery charger suitbale for 12V/24 V DC with boost and trickle selector switch, 0-30
V DC volt meter, and 0-20 A DC Ammeter
All standard relays and accessories for automatic operation of diesel engine
System Controller
Designing, Supply, Installation, Testing and commissioning of system
controller to control operation of main electric fire pump, diesel pump, Pressurization
pump, Terrace pump in sequence as per specification consisting of relays, (ns) | 1 | Per Metre | - | - |
| 3 | Providing and fixing Gunmetal fire bridage suction hose coupling ( Draw out
connection) with nut for female coupling as per IS:9021974 complete with 100mm
dia. 1 no C.I foot valve flanged (to be connected to static water tank) (NS) | 1 | Each | - | - |
| 4 | Providing and Fixing ISI marked (IS: 16018) Fire Extinguisher, Trolley mounted
carbon dioxide type capacity 22.5 Kg. Flat base Item Including valve, discharge hose of
not less than 10mm dia Im long complete in all respects including wheeled trolley,
carrying handle and initial fill with CO2 gas as per IS: 307-1996 filled to a filling ratio
of not more than 0.667(NS) | 1 | Each | - | - |
| 5 | Supplying, installation, testing and commissioning sector panel suitable for following
zones, complete with visual indications for short circuit fault, open circuit fault, fire
condition and all other standard facilities as per IS:2189 with mimic diagram for all
area/zone covered, complete with all connections, interconnections as required.10
zone (DSR 2018 code 17.1.9.3)(NS) | 1 | Each | - | - |
| 6 | Supplying and laying of 2x1.5 sqm fire alarm armoured cable, 600/1000V rated with
annealed copper conductor having XLPE insulation, steel wire armouring and FRLS
outer sheath complete as required. (DSR 2018 code 17.5.2) (NS) | 1,320 | Each | - | - |
| 7 | MCP/TBS. (NS) | 3 | Each | - | - |
| 8 | Hooter (NS) | 3 | Each | - | - |
| 9 | Supplying, installation, testing and commissioning of smoke detector with builtin LED
and mounting base complete with all connections etc. as required. (DSR 2018 code
17.1.2) NS | 80 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.88 MB
BOQ_630128.xls
BOQ • 0.30 MB
OT0179359.pdf
Other Document • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .