Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.2 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹62.9 L+₹19.6 L (45.2%)Rejected-Finance BLOCK C 14 GROUND FLOOR PLOT 618 624 BHIVANDIWALA TERRACE JAGANNATH SHANKARSHETH MARG DHOBI TALAO NEAR KALBADEVI POST OFFICE MUMBAI 400002 | MUMBAI | MAHARASHTRA | 400002 | L2 | Rejected-Finance Being other than lowest | |
| 3 | Rejected-Technical | - | Rejected-Technical Fake documents submitted | |
| 4 | Rejected-Technical T 16 1 SHETTY HOTEL OLD NAVY NAGAR COLABA MUMBAI 400005 | MUMBAI | MUMBAI | MAHARASHTRA | 400005 | - | Rejected-Technical Banned by CWE Scbad |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
14 Jan 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE NW MUMBAI
CWE NW MUMBAI DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI
REPAIRMAINTENANCETOFIREALARMSYSTEMANDFIREFIGHTINGSYSTEMANDALLIEDCONNECTEDWORKSINHIGHRISEBUILDINGSATNOFRAUNDERGENWNAVYNAGARCOLABAMUMBAI
2020_MES_373627_2
8119/CWE(NW)/MUMBAI
Open Tender
Civil Works
Item Rate
330 days
GE NW NAVY NAGAR
Class C and Category c (vi)
7 documents required · 7 mandatory
₹1,000
Yes
GE NW NAVY NAGAR
₹1.3 L
Yes
5 Mar 2021
18 Dec 2020
16 Jan 2021
18 Dec 2020
14 Jan 2021
31 Dec 2020
18 Dec 2020 - 31 Dec 2020
60 days
Amount
Repair/Routine maintenance including carrying out daily check of fire alarm/fire fighting system complete with electronic control panel consisting of 16 zones in 02 (Two) Buildings Meena, Swati (G+13 floors) ie 13 stories including personnel to attend the fire alarm system faults, testing, checking and replacement of unserviceable components ie nuts, bolts, washers etc other than mentioned in schedule here-in after. The fire alarm system consisting the following :- (a) Indicator (b) Electronic hooter (c) Manual call point (d) Smoke detector (e) Heat detector (f) Electronic fire control panel (g) Main/Zone cards (h) Battery of Fire panel DC supply (J) All wiring and cable connections
All as above item No 1 but 17 zones in 4 (Four) Buildings Kanya, Chitra, Anuradha & Alaknanda (G+13 floors) ie 15 stories and 01 (One) Buildings Archana (G+15 floors).
All as per item No 1 above but 15 zones in 04 (Four) Buildings Bharani, Saravana, Vidya & Vijaya (G+12 floors) ie 13 stories
All as per item No 1 above bu 12 zones in 04 (Four) Buildings Revati, Rohini, Karthikeya & Gemini (G+9 floors) ie 10 stories .
Repair/Routine maintenance including carrying out daily check of fire fighting system 09 zone complete 04 (Four) Buildings WNC Mess main bldg, Annex bldg, Hemadri and transist bldg (G+07 floors) ie 08 stories 04 (Four) Buildings Narmada, Tapti, Kaveri, Hoogly and Vishkarma bldg (G+06 floors) ie 07 stories including attending system faults, testing, checking including replacement of unserviceable components ie nuts, bolts, washers etc other than mentioned in schedule “A” here-in after complete all as specified and directed
Supply and replacement, installation, testing & commissioning of micro processor based 2 wire fault tolerant loop, required loop networkable type 2 loop (each loop accessing maximum 99 detectors and 99 modules ) fire alarm/detection control panel. The panel shall be able to give location of all fire/fault conditions of addressable units via the address codes. Further, the panel must be able to automatically switch ON /OFFrespective control module whenever any alarm is triggered. The panel shall have rectifier, Loop cards, 80 character L C D unit to indicate Fire/Fault Signal with address and analog output, external/inbuilt printer to log all fire or fault events complete in all respects. The Panel shall support 24 zones Addressable 2 way Talk Back fire fighter communication, in case of emergency. The panel shall have ability to get integrated with PA System for zone wise annoucements. The panel shall support both Loop Powered & conventional Notification devices for emergency responses. the Panel shall support Auto learn feature. The panel shall have a built in power supply and battery charger along with maintenance free 24 AH, 2 x 12 volt SMF Lead acid batteries capable of running for a minimum of 48 hours with battery charger complete as required.and as per specifications. conforming to BS5839 Standards and Duly Approved by EN54/LPCB/VDS/UL/BSA complete all as specified and directed by Engineer-in-Charge, Make:- Bosch/Honeywell/Schneider
Supply & fix in repair detectors Complying with and type certified to EN - 45 Addressable type multisensor detector with heat and smoke combination complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply & fix in repair Maintenance free battery duly charged 12 V 7.2 AH complete all as specified and directed Make :- EXIDE / TATA / Green / Amaron
Material and labour for factory fabricated MS fire cabinet box as per Existing design made out flat CRCA of appropriate size and thickness 2 mm all as directed including and applying two coats of synthetic enamel paint over a coat of red oxide primer on panel fitted inside bldg on each floor by approved colour & fixed on wall with necessary nuts/bolts or welding to existing MS pipe by supporting angle complete all as specified & directed.
Supply & fix in repair rubber hose pipe 30 mtr,20mm dia plain 2 ply rayon confirming IS-12585 braided high pressure complete all as specified and directed. Make:-Minimax / Safex /DUNLOP
Supply & fix in repair canvas fire hose 63mm bore 15 m long confirming to IS 636-1988 having male/female brass coupling both end complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair Stainless steel Nozzle 25 mm bore suitable for 63mm dia canvas pipe complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair hose Reel drum suitable for 30 mtrs X 20 mm dia rubber hose pipe complete all as specified and directed. Make:-Minimax/Safex/DUNLOP / Jyothi
Supply & fix in repair 100 mm dia ERW MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipe including supporting brackets complete all as specified and directed. Make:- Jindal /Tata /Zenith/BST/Sail
Supply & fix in repair 150 mm dia ERW MS pipe confirming IS-1239 and applying two coats of synthetic enamel paint over a coat of red oxide primer to pipe including supporting brackets. complete all as specified and directed. Make:- Jindal /Tata /Zenith/BST/Sail
Supply & fix in repair gun metal Two way fire brigade inlet conection with adaptor of size 80 mm dia X 63 mm dia complete all as specified and directed. Make :- Minimax / Safex / DUNLOP
Supply & fix in repairs Branch pipe gun metal 63mm instantaneous inlet, made threaded outlet, 15mm bore nozzle complete all as specified and directed. Make :- Minimax / Safex / DUNLOP
Supply & fix in repair twin outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair single outlet hydrant valve 100mm having 65mm outlet with lock pin wheel complete all as specified and directed. Make:-Minimax/Safex/DUNLOP
Supply & fix in repair sluice valve 150mm size both ends flayed with high tensile stainless steel spindle, I body as per IS-14846, ISI Marked,PN-1.6 including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. Make:Kirloskar/Leader/L&T (Andco)
Supply & fix in repair Sluice Valve 100mm size both ends flayed with high tensile brass spindle, body including all joints with rubber or fibre board, nuts, bolts, washers complete all as specified and directed. Make:Kirloskar/Leader/L&T(Andco)
Supply and fix in repair Foot valve ball type10/15Kg/sqcm (MODEL B-5) of (ISI marked) in position at location including M&L for making flanged joints and repair and making good to existing PCC surface complete all as specified and directed. Make NORMEX / Kartar/ Kirloskar or equivalentof following sizes :-
100 mm dia
150 mm dia
Material and labour for disconnecting LT cables of various sizes from electric motor of 15 HP/11 KW capacites and decoupling from the pumping sets. Removing and taking down carefully and transporting to authorised workshop for rewinding. Strip opening and dismanting complete rotor and stator assembly. Cutting and taking out old burnt copper winding from the stator assembly and cleaning the slots of stator with carbon tetra chloride solution. Material and labour for rewinding, complete stator assembly with and including super enamelled copper winding, wire of suitable gauge matching with existing. Applying the minimum two coats of insulation varnish and keeping the stator assembly in heating chamber to improve for insulation value. Assembling the motor, transporting to site of work, coupled with the pumping set, alignments properly, connecting the LT cables and commissioning complete of the following capacity of Electric motors complete all as specified and directed.
Material and labour for disconnecting LT cables of various sizes from electric motor of 55KW/75HP capacites and decoupling from the pumping sets. Removing and taking down carefully and transporting to authorised workshop for rewinding. Strip opening and dismanting complete rotor and stator assembly. Cutting and taking out old burnt copper winding from the stator assembly and cleaning the slots of stator with carbon tetra chloride solution. Material and labour for rewinding, complete stator assembly with and including super enamelled copper winding, wire of suitable gauge matching with existing. Applying the minimum two coats of insulation varnish and keeping the stator assembly in heating chamber to improve for insulation value. Assembling the motor, transporting to site of work, coupled with the pumping set, alignments properly, connecting the LT cables and commissioning complete of the following capacity of Electric motors complete all as specified and directed.
Supply & fix in repair DE bearing including necessary greasing reassemble the motor connect, testing and commissioning complete for Motor capacity 75 HP bearing No1314 complete all as specified and directed. Make : SKF or equivalent as approved by GE
Supply & fix in repair DE bearing including necessary greasing reassemble the motor connect, testing and commissioning complete for Motor capacity15 HP bearing No 6213/C4 complete all as specified and directed. Make - SKF or equivalent as approved by GE
Supply, laying, jointing and testing in replacement of PVC insulated and FR PVC Round Sheathed, Copper Conductor (flexible) industrial cable, 1100 Volt, conforming to IS 694 6 Core 0.5 sqmm including making necessary connection, with busbar/MCCB/DB's & testing complete all as specified and directed. Make :- Polycab / Havells / HPL / Gloster
Supply,replacement, Installation,Testing & Commissioning of Addressable Type Manual Call Point with Mounting Base as required conforming (UL's Latest Edition Approved and NFPA compliant / VDS or LPCB tested and EN54 compliant) complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply fix in replacement, Installation,Testing & Commissioning of Addressable electronic sounder cum strobe complete all as specified and directed. Make :- Schneider / Honey Well / Bosch
Supply and fix in repair Star Delta starter suitable for 15 HP/11 KW pump set current relay range 9-13Amp ,3 phase 430 V ,50Hz complete all as specified and directed. Make :-L&T/Havells/HPL
Material and labour for disconnecting horizontal split casing pump of any make/model, dismantling and taking out pump shaft assembly complete for replacement of pump gasket and brass bush including greasing the pumpset connecting to coupling testing & commissioning with providing MS guard complete all as specified and directed for following sizes / capacities of pump :-
Pump coupled with motor of capacity 75 HP
Pump coupled with motor of capacity15 HP
AGRAWAL ASSOCIATES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .