Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.1 LAccepted-Finance | L1 | Accepted-Finance Lower Bidder | |
| 2 | L2₹7.2 L+₹1.1 L (18.0%)Rejected-Finance BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L2 | Rejected-Finance Higher Bidder | |
| 3 | L3₹8.3 L+₹2.2 L (35.9%)Rejected-Finance 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L3 | Rejected-Finance Higher Bidder | |
| 4 | L4₹8.7 L+₹2.5 L (41.5%)Rejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L4 | Rejected-Finance Higher Bidder |
Tender Value
Refer Docs
EMD Value
₹14,500
Closing Date
13 May 2025, 1:00 pmClosed
EE/KNED, PWD
P 5 CIT Road Kolkata 700014
Repair and Renovation work for Minerva Natya Sanskriti Charcha Kendra Electrical Installation, Stage Lighting, AC system, Fire Detection, Servicing and allied works SITC of Fire Detection and Alarm System
2025_WBPWD_839103_1
WBPWD/EE/KNED/eNIT38/24-25/2ND
Open Tender
ELECTRICAL WORKS ORG
Item Rate
20 days
Minerva Natya Sanskriti Charcha Kendra
Please refer tender documents
7 documents required · 7 mandatory
₹14,500
Kolkata North Electrical Division, PWD
10 Jun 2025
26 Apr 2025
15 May 2025
26 Apr 2025
13 May 2025
3 May 2025
2 May 2025
Amount
SITC of Microprocessor based Intelligent, addressable fire alarm control panel ( VDS / UL / FM / ULC approved ) fully networkable having requisite numbers of loop with 20% spare capacity with each loop capable of taking requisite number of devices as per latest IS/NBC, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS. 1.1) The panel shall have in built rectifier, provision for external & internal printer ( if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required. 2.2) The FACP shall be capable of being networked ( future expansion ) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS( RS 485 ). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ).
SITC of Analog Addressable Intelligent multisensor detector ( VDS / UL / FM / ULC approved ) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor )
SITC of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ).
SITC of Addressable Manual Call Point ( VDS / UL / FM / ULC approved )soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ).
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ).
SITC of LED type Response Indicator ( VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ).
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab ) with 20 mm NB PVC rigid conduit pipe(Make: Precision /AKG/ATUL /VIP/ Universal /BEC/Polycab) on the surface of the wall.
Supply, installation, testing & commissioning of conventional type been (infra-Red Light) detector (VDS/UL/ERTL/LPCB/FM approved) with long range projected beam consist of seperate transmeter & receiver, having input module for individual addressing of the detector, as required for high hight application. (Approved make: Cerberus pro/Jhonson Control / Edward/ Securiton /Secutron/Apollo/Morley/Eaton/GST)
TERMS & CONDITIONS: a.The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
b. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
c. Auto CAD Drawing of whole FDA system & submission of 5 set hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
d. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
e. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Note: 1) All the above rates should be quoted inclusive of all taxes & duties and LWC as applicable. 2) Total is rounded off to the nearest rupees.
Computer Gallery (BID ID -6392849)
PERFECT IMAGE SOLUTIONS (BID ID -6386752)
Creative Projects (BID ID -6387560)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .