| Sl No | Description | Qty | Unit | M/S PINNACLE ENGINEERING WORKS L1 | M/S RELIANCE ELECTRICALS L2 |
|---|---|---|---|---|---|
| 1.00 | Repairs/replacement to 250 Amp MCCB at WSS Batwani 1st, by way of: -
Disconnecting all the power connections to the panel and then extracting the damaged MCCB. The job includes replacement of damaged MCCB by a new MCCB along with its lugs of following specifications which shall match with the existing MCCB for its fitment in the Panel.
Specifications: -
Model No =d sine (DN2-250D)
No. of poles =4 Pole
Current Rating = 250 Amp.
Rated operational voltage =415 V+ 15%
Rated frequency = 50+/-3%Hz
Ambient temperature = 40C
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
Type of release = Thermal-Magnetic
Thermal Release Range = 200-250A
Overload protection =0.8-1xIn adjustable
Short-circuit protection =6-10xIn adjustable
(Qty = 01 No.) | 1 | Job | 26,000 ₹26,000 | 25,000 ₹25,000 Lowest |
| 2.00 | Repairs to 11 KV, 35 Sq.mm, 3-core ABC HT Cable for WSS Bonpunchgund which comprises the following operations complete in all respects, including provision of skilled manpower, tools, tackles, testing equipment, safety gear and all incidental charges:
A. Lowering of existing 11 KV, 35 Sq.mm ABC HT cable from HT poles manually over an approximate length of 100 meters, including dismantling, handling and safe placement of the cable to facilitate inspection and repair work.
B. Detection and localization of fault/defect in the 11 KV, 35 Sq.mm XLPE HT cable using suitable fault-finding instruments and approved testing procedures.
C. Repair of the damaged cable portion by way of providing, fitting and installing a suitable heat-shrinkable straight- through joint kit of approved/reputed make, including preparation of cable ends, jointing, insulation, sealing and all accessories required for satisfactory operation as per the norms for fitting of cable joint kits for restoration of the cable (ABC Type). (Qty = 03 Nos)
D. Re-erection and refixing of the repaired 11 KV, 35 Sq.mm ABC HT cable on HT poles manually, reconnecting the cable to the existing HT system, carrying out insulation resistance and continuity tests, energizing the line, and testing the cable under both no-load and full-load conditions to ensure satisfactory operation. | 1 | Complete Job | 35,000 ₹35,000 Lowest | 37,900 ₹37,900 |
Tender Value
₹69,500
EMD Value
₹1,390
Closing Date
28 Jul 2026, 11:00 amClosed
Executive Engineer JS PHE Mech. Rural Div. Sgr.
Executive Engineer JS PHE Mech. Rural Div. Sgr.
Electrical works to be carried out at Water Supply Scheme Batwani 1st and Bonpunchgund
2026_PHE_317290_1
PHE/MRD/TS 17 OF 07/2026
Open Tender
Miscellaneous Works
Item Rate
3 days
Srinagar
Please refer Tender documents.
2 documents required · 2 mandatory
₹50
Executive Engineer JS PHE Mech. Rural Div. Sgr.
₹1,390
6 Aug 2026
22 Jul 2026
28 Jul 2026
22 Jul 2026
28 Jul 2026
22 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Repairs/replacement to 250 Amp MCCB at WSS Batwani 1st, by way of: -
Disconnecting all the power connections to the panel and then extracting the damaged MCCB. The job includes replacement of damaged MCCB by a new MCCB along with its lugs of following specifications which shall match with the existing MCCB for its fitment in the Panel.
Specifications: -
Model No =d sine (DN2-250D)
No. of poles =4 Pole
Current Rating = 250 Amp.
Rated operational voltage =415 V+ 15%
Rated frequency = 50+/-3%Hz
Ambient temperature = 40C
Ultimate S.C Breaking Cap. at (415V AC, 50 Hz) = 36 KA
Type of release = Thermal-Magnetic
Thermal Release Range = 200-250A
Overload protection =0.8-1xIn adjustable
Short-circuit protection =6-10xIn adjustable
(Qty = 01 No.) | - | Job | 100 | - |
| 2 | Repairs to 11 KV, 35 Sq.mm, 3-core ABC HT Cable for WSS Bonpunchgund which comprises the following operations complete in all respects, including provision of skilled manpower, tools, tackles, testing equipment, safety gear and all incidental charges:
A. Lowering of existing 11 KV, 35 Sq.mm ABC HT cable from HT poles manually over an approximate length of 100 meters, including dismantling, handling and safe placement of the cable to facilitate inspection and repair work.
B. Detection and localization of fault/defect in the 11 KV, 35 Sq.mm XLPE HT cable using suitable fault-finding instruments and approved testing procedures.
C. Repair of the damaged cable portion by way of providing, fitting and installing a suitable heat-shrinkable straight- through joint kit of approved/reputed make, including preparation of cable ends, jointing, insulation, sealing and all accessories required for satisfactory operation as per the norms for fitting of cable joint kits for restoration of the cable (ABC Type). (Qty = 03 Nos)
D. Re-erection and refixing of the repaired 11 KV, 35 Sq.mm ABC HT cable on HT poles manually, reconnecting the cable to the existing HT system, carrying out insulation resistance and continuity tests, energizing the line, and testing the cable under both no-load and full-load conditions to ensure satisfactory operation. | - | Complete Job | 100 | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.43 MB
BOQ_1039128.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .