Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.7 LAccepted-AOC 05 MR PRASHANT DESHMUKH PLOT NO 05 SHUBHALAKSHMI APARTMENT ADHYAPAK LAYOUT HINGNA T POINT NAGPUR 440036 MH NAGPUR | NAGPUR | MAHARASHTRA | 440036 | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹21.4 L+₹66,871 (3.23%)Rejected-Finance | L2 | Rejected-Finance Other than L1 bidder | |
| 3 | L3₹24.4 L+₹3.7 L (17.7%)Rejected-Finance | L3 | Rejected-Finance Other than L1 bidder | |
| 4 | L4₹25.1 L+₹4.4 L (21.3%)Rejected-Finance | L4 | Rejected-Finance Other than L1 bidder | |
| 5 | L5₹25.4 L+₹4.6 L (22.3%)Rejected-Finance | L5 | Rejected-Finance Other than L1 bidder |
| Sl No | Description | Qty | Unit | V.H.Constructions L2 | POWER CONSTRUCTION COMPANY | POWER CONSTRUCTION COMPANY L3 | L and S ENTERPRISES L7 | AKSHITA ELECTRICAL L6 | VACON INFRASTRUCTURES L4 | GLOBAL POWER SYSTEMS L1 | TIRUMALA ENTERPRISES L5 |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying installing testing and commissioning diesel engine driven generating set as per CPCB IV norms 415 V, 3 phase, 4 wire as per BS 5514/IS-10002 complete with standard control panel, of capacity continuous rating 100 KVA/80 KW at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and comprising of the following complete all as specified and as directed :-
Alternator : Self regulated with brushless self excitation 100 KVA, 415 V, 3 phase, 4 wire, 50 HZ, 0.8 P.F.,1500 RPM, with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted, screen protected drip proof type with class 'F' insulation, closed coupled single bearing alternator, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772 capable of supplying unbalanced load.
Engine : Multi/cylinder,compression ignition, heavy duty,compact diesel engine liquid cooled with standard accessories, all as per BS-5514/ISO-3046,1500 RPM,control gauges, RPM/Hours meters etc; shaft H.P. suitable for generating application and capable of giving an output of 100 KVA/80 KW for coupled alternator under NTP conditions, complete with following:- | 1 | EACH | 17,40,002 ₹17,40,002 | 20,51,100 ₹20,51,100 | 20,51,100 ₹20,51,100 | 22,50,000 ₹22,50,000 | 21,33,000 ₹21,33,000 | 20,05,000 ₹20,05,000 | 17,17,171 ₹17,17,171 Lowest | 21,00,000 ₹21,00,000 |
| 1.01(i) Flywheel housing with flywheel to suit closed coupled single bearing alternator. (ii) Air-cleaner dry type with vacuum indicator. (iii) Fuel pump and fuel piping 15mm M.S. pipe with bends, flanges etc. (iv) Fuel filter with water separator and filter element. (v) Lub-oil filter with filter element (vi) D.C. starter 12 volts. (vii) Storage Batteries of suitable voltage and ampere-hours as recommended by the manufacturers. (viii) Residential silencer as per CPCB IV norms (ix) Supporting/fixing arrangement for muffler with celiling through antivibration pads. (x) Engine overspeed stop/trip switch. (xi) Radiator with fan. (xii) Dynamo for battery charging. (xiii) Corrosion inhibitor coolant. (xiv) Engine control panel electronic digital display type consisting of battery voltage indicator, lub oil temp and pressure gauges coolant water temp gauge, RPM indicator cum hour meter etc. (xv) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP). (xvi) Any other devices/accessories recommended/supplied by the manufacturers as standard eqpt. | |||||||||||
| 1.02AMF Panel : AMF panel shall be of suitable size factory made indoor cubical type front openable fabricated from CRCA steel sheet 1.6 mm thick complete as per manufacturer specification of Diesel Engine suitable for DG Set of capacity 100 KVA grouted inbuilt/fixing inside the DG set as per manufacturers recommendations complete in all respects and consisting of the following :- (i) Contactor ML of suitable capacity. (ii) Aluminium bus bar of capacity 200 Amps (04 Nos) for phase and neutral. (iii) Sensitivity relay set unit with auxiliary relay CT's. (iv) Electronic latch circuit with tripping indication. (v) Instantneous tripping device suitable for complete panel over current 0.5 Amp. (vi) Reset facilities for complete protection of AMF Panel. (vii) Self squential starting relay unit 12 volts DC complete with alarm and power contactor. (viii) Electronic timer 220 Volts for main contactor with 1 No NC auxiliary contactor. (ix) Electronic timer 220 volts for fuel cut off operation for with 1 No NC auxiliary contactor. (x) Battery charging unit 12 volts 20 amp complete with digital volt metre & Amp metre. | |||||||||||
| 1.03(xi) All as per item No (ix) here in before but for fuel cut off operation. (xii) Electrical starter 12 volts DC as per manufacturer's design. (xiii) Digital volt meter 0-500 volts panel mounting type size 96 square mm with digital selector switch. (xiv) 3 Phase electronic energy meter for measuring meter for measuring generated units. (xv)Frequency meter (Digital type) of suitable rating. (xvi) MCCB 160 Amps 4 Pole 36 kA breaking capacity with fixed thermal and magnetic release, for main supply & DG Supply adjustable over load and adjustable short circuit each 01 No (xvii) The AMF panel shall have manually by pass arrangement in case of failure of AMF Panel. | |||||||||||
| 1.04(xviii) Other accessories, if any , as per manufacturer instructions. Diesel tank shall be provided as per OEM derain with caliberated scale (fuel level indicator) dip stick, fuel inlet/outlet , Air vent, drain plug and inlet arrangement for direct filling, including suitable size gate valve in outlet, tank to be fitted at suitable height. Sound proof enclosure with residential silencer (CPCB IV approved) the sound less than 75 db at a distance of 1 meter from canopy in free field zone. PCC / RCC foundation complete as per manufacturers own design/ Or as per directions of Engineer-in- charge. Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty/test certificates, schematic diagrams of control panels. Other items : List of tools and two years normal maintenance spares as per manufacturers recommended lists, duly priced, item wise. Notes : (i) Contractor will satisfactorily conduct load test of DG set for 12 hours including run on 10% overload for 1 hour. | |||||||||||
| 1.05(ii) Testing equipment including load bank for any other alternative arrangement shall be arranged by the contractor and cost of the same shall be deemed included in quoted rate. (iii) Fuel/oil required for load test shall be arranged by the contractor and cost thereof is deemed to be included in quoted rate by the contractor. (iv) AMF panel and DG set shall be procured from same OEM i.e make of both shall be same. (v) DG set shall be tested by the representative of Accepting Officer before commissioning and cost thereof deemed to be included in quoted rates. | |||||||||||
| 2.00 | Supply and laying for XLPE LT cable 50 sqmm 3.5 core, 1100 volt grade heavy duty electric cable XLPE insulated & PVC outer sheathed with aluminium stranded conductor armoured conforming IS 7098 Part-I (1988) with latest amendments, complete all as specified and directed. | 200 | RM | 370 ₹74,000 Lowest | 475 ₹95,000 | 475 ₹95,000 | 477 ₹95,400 | 531 ₹1,06,200 | 625 ₹1,25,000 | 505.05 ₹1,01,010 | 588 ₹1,17,600 |
| 3.00 | Supply and laying for XLPE LT cable 70 sqmm 3.5 core, 1100 volt grade heavy duty electric cable XLPE insulated & PVC outer sheathed with aluminium stranded conductor armoured conforming IS 7098 Part-I (1988) with latest amendments, complete all as specified and directed. | 100 | RM | 515 ₹51,500 Lowest | 634 ₹63,400 | 634 ₹63,400 | 558 ₹55,800 | 648 ₹64,800 | 825 ₹82,500 | 707.07 ₹70,707 | 805 ₹80,500 |
| 4.00 | Supply and laying for XLPE LT cable 25 sqmm 4 core, 1100 volt grade heavy duty electric cable XLPE insulated & PVC outer sheathed with aluminium stranded conductor armoured conforming IS 7098 Part-I (1988) with latest amendments, complete all as specified and directed. | 200 | RM | 220 ₹44,000 Lowest | 311 ₹62,200 | 311 ₹62,200 | 243 ₹48,600 | 360 ₹72,000 | 350 ₹70,000 | 303.03 ₹60,606 | 367 ₹73,400 |
| 5.00 | Supply and fix on wall with necessary arrangements busbar chamber 200 amps 4 way 4 pole wall mounted IP -54 , made out of 1.6 mm thick CRCA sheet epoxy powdwer coated single layer operational voltage 440 Volt , Short circuit current capacity 25 KA for 1 Second including necessary cable connections and outgoing 1 Nos of MCCB of Capacity 100 Amp 4 Pole 16 KA complete all as specified and directed. Note: Quoted rates inclusive of necessary fixing arrangement and cable connections , cable glands as required for proper fixing / functioning of Bus Bar Chamber. | 2 | Job | 36,000 ₹72,000 | 28,000 ₹56,000 | 28,000 ₹56,000 | 16,200 ₹32,400 Lowest | 36,000 ₹72,000 | 65,000 ₹1,30,000 | 22,222 ₹44,444 | 30,000 ₹60,000 |
Tender Value
₹27.9 L
EMD Value
₹56,000
Closing Date
17 Apr 2026, 6:00 pmClosed
CWE (Army) Secunderabad
Commander Works Engineers Mudfort, MES Office Complex Secunderabad-500 003
PROVN OF 100 KVA DG SET AT NCC DIRECTORATE (AP and T) UNDER GE (U) SECUNDERABAD.
2026_MES_758087_1
86307
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Secunderabad
as per NIT
7 documents required · 7 mandatory
₹500
GE (UTILITY) Secunderabad
₹56,000
Yes
27 May 2026
27 Mar 2026
24 Apr 2026
27 Mar 2026
17 Apr 2026
10 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supplying installing testing and commissioning diesel engine driven generating set as per CPCB IV norms 415 V, 3 phase, 4 wire as per BS 5514/IS-10002 complete with standard control panel, of capacity continuous rating 100 KVA/80 KW at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and comprising of the following complete all as specified and as directed :- Alternator : Self regulated with brushless self excitation 100 KVA, 415 V, 3 phase, 4 wire, 50 HZ, 0.8 P.F.,1500 RPM, with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted, screen protected drip proof type with class 'F' insulation, closed coupled single bearing alternator, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772 capable of supplying unbalanced load. Engine : Multi/cylinder,compression ignition, heavy duty,compact diesel engine liquid cooled with standard accessories, all as per BS-5514/ISO-3046,1500 RPM,control gauges, RPM/Hours meters etc; shaft H.P. suitable for generating application and capable of giving an output of 100 KVA/80 KW for coupled alternator under NTP conditions, complete with following:- | |||||
| 1.01 | (i) Flywheel housing with flywheel to suit closed coupled single bearing alternator.
(ii) Air-cleaner dry type with vacuum indicator.
(iii) Fuel pump and fuel piping 15mm M.S. pipe with bends, flanges etc.
(iv) Fuel filter with water separator and filter element.
(v) Lub-oil filter with filter element
(vi) D.C. starter 12 volts.
(vii) Storage Batteries of suitable voltage and ampere-hours as recommended by the manufacturers.
(viii) Residential silencer as per CPCB IV norms
(ix) Supporting/fixing arrangement for muffler with celiling through antivibration pads.
(x) Engine overspeed stop/trip switch.
(xi) Radiator with fan.
(xii) Dynamo for battery charging.
(xiii) Corrosion inhibitor coolant.
(xiv) Engine control panel electronic digital display type consisting of battery voltage indicator, lub oil temp and pressure gauges coolant water temp gauge, RPM indicator cum hour meter etc.
(xv) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP).
(xvi) Any other devices/accessories recommended/supplied by the manufacturers as standard eqpt. | - | - | - | - |
| 1.02 | AMF Panel : AMF panel shall be of suitable size factory made indoor cubical type front openable fabricated from CRCA steel sheet 1.6 mm thick complete as per manufacturer specification of Diesel Engine suitable for DG Set of capacity 100 KVA grouted inbuilt/fixing inside the DG set as per manufacturers recommendations complete in all respects and consisting of the following :-
(i) Contactor ML of suitable capacity.
(ii) Aluminium bus bar of capacity 200 Amps (04 Nos) for phase and neutral.
(iii) Sensitivity relay set unit with auxiliary relay CT's.
(iv) Electronic latch circuit with tripping indication.
(v) Instantneous tripping device suitable for complete panel over current 0.5 Amp.
(vi) Reset facilities for complete protection of AMF Panel.
(vii) Self squential starting relay unit 12 volts DC complete with alarm and power contactor.
(viii) Electronic timer 220 Volts for main contactor with 1 No NC auxiliary contactor.
(ix) Electronic timer 220 volts for fuel cut off operation for with 1 No NC auxiliary contactor.
(x) Battery charging unit 12 volts 20 amp complete with digital volt metre & Amp metre. | - | - | - | - |
| 1.03 | (xi) All as per item No (ix) here in before but for fuel cut off operation.
(xii) Electrical starter 12 volts DC as per manufacturer's design.
(xiii) Digital volt meter 0-500 volts panel mounting type size 96 square mm with digital selector switch.
(xiv) 3 Phase electronic energy meter for measuring meter for measuring generated units.
(xv)Frequency meter (Digital type) of suitable rating.
(xvi) MCCB 160 Amps 4 Pole 36 kA breaking capacity with fixed thermal and magnetic release, for main supply & DG Supply adjustable over load and adjustable short circuit each 01 No
(xvii) The AMF panel shall have manually by pass arrangement in case of failure of AMF Panel. | - | - | - | - |
| 1.04 | (xviii) Other accessories, if any , as per manufacturer instructions.
Diesel tank shall be provided as per OEM derain with caliberated scale (fuel level indicator) dip stick, fuel inlet/outlet , Air vent, drain plug and inlet arrangement for direct filling, including suitable size gate valve in outlet, tank to be fitted at suitable height.
Sound proof enclosure with residential silencer (CPCB IV approved) the sound less than 75 db at a distance of 1 meter from canopy in free field zone.
PCC / RCC foundation complete as per manufacturers own design/ Or as per directions of Engineer-in- charge.
Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty/test certificates, schematic diagrams of control panels.
Other items : List of tools and two years normal maintenance spares as per manufacturers recommended lists, duly priced, item wise.
Notes :
(i) Contractor will satisfactorily conduct load test of DG set for 12 hours including run on 10% overload for 1 hour. | - | - | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.51 MB
Tender86307.pdf
Tender Documents • 1.02 MB
BOQ_849135.xls
BOQ • 1.10 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .