| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.4 LAccepted-AOC 2 EVEREST VIHAR PT T N MISHRA MARG NIRMAN NAGAR JAIPUR 302019 | JAIPUR | RAJASTHAN | 302019 | L1 | Accepted-AOC Being lowest and reasonable | |
| 2 | L2₹22.5 L+₹2.9 L (14.6%)Rejected-Finance 30 INDUSTRIAL AREA KOKAR RANCHI 834004 JHARKHAND | RANCHI | JHARKHAND | 834004 | L2 | Rejected-Finance NOT LOWEST | |
| 3 | Rejected-Technical | - | Rejected-Technical being not enlisted in appropriate category | |
| 4 | Rejected-Technical 27 2ND FLOOR CITY CENTRE CLUB ROAD RANCHI 834001 JHARKHAND | RANCHI | JHARKHAND | 834001 | - | Rejected-Technical being not enlisted in appropriate category | |
| 5 | Rejected-Technical | - | Rejected-Technical being not enlisted in appropriate category |
Tender Value
Refer Docs
EMD Value
₹36,000
Closing Date
18 Feb 2021, 6:00 pmClosed
CWE Ranchi
HQ CWE RANCHI MES DIPATOLI CANTT PO RMCH RANCHI - 834009
REPAIR/MAINT OF TRANSFORMERS AND HT UG CABLE IN MAHAR AREA AT DIPATOLI MIL STN UNDER GE DIPATOLI
2021_MES_413080_1
80599/1333/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Dipatoli Cantt
Class E category b(iii)
7 documents required · 7 mandatory
₹500
Yes
GE Dipatoli
₹36,000
Yes
8 Apr 2021
19 Jan 2021
20 Feb 2021
19 Jan 2021
18 Feb 2021
4 Feb 2021
Amount
M &L for overhauling/Servicing/preventive maintenence of 33 KV VCB, 400 Amp indoor door type cleaning isolating contacts ,moving parts removing dust particles from bus bar chamber spout gear mechanism and moving parts,repair to motor charge spring mechanism including greasing of the moving parts,cleaning of the moving/Stationary contact with CTC,Removing of moisture by means of hot air blower,renewal of gaskets,nuts/bolts etc entire trolly components and replacement of all unserviceable spares as required at site and all as directed ,inserting in trolley,testing commissioning and putting on the supply on load complete and as per under mention scope complete all as specified and as directed at site. (i) Examination of auxiliary switches, indicating devices and interlocks to ensure that they are in good order physically. (ii) Check fixed and moving contacts. (iii) Physical checking of Epoxy Housing (iv) Check close & trip coil (v) Checking of control circuit & tighten the connection if any. (vi) Test shall be carried out closing & opening timing test for all three poles (vii) Test shall be carried out IR test with megger- using 5 Kv Meggar (viii) Test shall be carried out contact resistance Kit for all three poles (ix) Caliberation & testing of relay for closing, tripping with necessary current setting as required at site.
M&L Post type 33kV Polymer insulator with FRP as per requirement complete all as specified and directed .
S&F connect lightening arrestor non linear pole type MCOV 33 KV, normal discharge capacity 65 KA and impulse current with all fittings suitable for 33 KV electric working pressure including strap bolts and nuts and washers etc complete all as specified and as directed. Make - BHEL / Jaipuria/ Rashtriya/ MEI/National
M&L for servicing and renewal/replacement of defective parts of oil type transformer capacity 25 KVA to 250 KVA 11/.433 kV Indoor/out door type of any make by disconnecting of HT bus bar connection and providing electric power to user by alternative arrangement, opening of doors etc complete cleaning of the inside compartment,core and coils by vacuum cleaner incl lead supports,tap changer terminal boards,bushing and other insulated surface be wiped clean with dry cloth and all connections must be checked for tightening after cleaning up to the satisfaction of Engr-in- Charge. The transformer must be meggred and connecting all connection and necessary testing complete with under mentioned scope of work. defective part measured and paid under respective item as supply only, however fixing charges included. (i) Cleaning of transformer from inside/out side. (ii) Testing the transformer for IR values (iii) Checking/servicing/calibration of WTI for healthiness (iv) Magnetic balance test (v) IR Value check before and after the work (vi) Voltage ratio test at 440 V. (vii) DC logic test (viii) Commissioning of transformer after completion of work. Note :- (i) Test results obtained shall be recorded and produced to the Engr-in- Charge. (ii) All measuring equipments and T&P required shall be arranged by the contractor. (iii) Any item/activity not listed/covered here above and required during/completing the overhauling work will have to be arranged by contractor himself. (iv) The rate quoted shall be deemed to include for disconnection of transformer HV/LV terminations for testing work and re-connections after completion of repair work.
Dismantling of HT bushing of transformer including metal and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer from 25kVA to 250 kVA complete all as specified and as directed.
Dismantling of LT bushing of transformer including metal and rubber parts and replacing with new bushes complete with new metal and rubber parts of any size and shape required for transformer from 25kVA to 250 kVAcomplete all as specified and as directed.
Supply and Fix for incorporated to the repair of transformer off load tap changer switch of existing model / type of transformer of capacity 25 to 250 kVA complete all as specified and as directed..
M&L for dehydration/centrifuging of transformer oil minimum 3 cycles to achieve dielectric strength 50 kV in 2.5 mm gap electrode with centrifuging machine at site and testing of transformer oil before and after de- hydration complete all as specified and as directed at site.
M&L for topping up/replacement of transformer chamber and conservator with new transformer oil upto a required level ( 60 KV di-electric strength in 2.5 mm gap electrode to with stand for one minute) in any type and capacity of transformer complete all as specified and directed at site.
M&L for high voltage coil of transformer including double paper insulated conductor of existing gauge and all insulating material,varnished etc complete all as specified and as directed
M&L for low voltage coil of transformer including double paper insulated conductor of existing gauge and all insulating material,varnished etc complete all as specified and directed .Matting with vaccum impregnation and baking of coil suitable for 250 KVA transformer complete all as specified and as directed.
Supply and fix in replacement of silica gel complete all as specified and as directed .
Attending any breakdown immiediately of 25 kVA to 250 kVA transformer by OEM service engineer to check and repair /replace any spares related break down and make the power transformer serviceable with in 48 Hours complete all as specified and directed at site. Note : (i) Spares will be paid separately under relative items. (ii) Checking of all electrical connection for its proper tightness. (iii) Proper care shall be taken to isolate the supply and it shall be ensured that repairs are carried out on No LIVE switch gears. (iv) Each switch gear/Load break switch/breaker shall be counted as a separate unit for the purpose of measurement. (v) A sum of Rs.500.00/Hr will be recovered from contractor in case of not attending the break down by service engineer and not rectified defect with in 24 Hrs
S&F air break switch (GOD) vertical/horizontal, double break type triple pole mechanically operated mounted on double insulartors and steel frame with operating mechanism linked with ground level operating GI rod 25mm dia medium grade. GOD suitable for current rating upto 400 amps and suitable for HT 11 KV including connecting complete with locking arrangement complete all as specified and as directed. Make - BHEL / Jaipuria/ Rashtriya/ MEI/National
S&F horn gap fuse unit assembly triple pole outdoor type suitable for HT 11 KV upto 400 Amps complete all as specified and as directed. Make - BHEL / Jaipuria/ Rashtriya/ MEI/National
S&F lightening arrestor non linear, pole type 11 KV discharge capacity 65 KA, with all fittings suitable for 11 KV electric working pressure including strap, bolts, nuts and washers etc complete all as specified and as directed. Make - BHEL / Jaipuria/ Rashtriya/ MEI/National
Dismantling cross-arms of MS, channel or angle sections & earth wire etc complete and setting aside for re-use with in 50 m distance.
Supply, fixing and fabricating tray holding cross arms, FI clamps support U clamps strips and back plates fabrication from structural steel section incl nut bolts washer bars etc of required size and thickness for supporting of cable tray by welding incl bending or welding cold or hot,drilling holes for bolt in any shape or size indicated or included of one coat primer coat under one finishing coat of black paint complete to support the cables all as specified.
M&L for Disc type porcelain vitreous white, brown or green insulator of size 145 mm height 255 mm dia incl galvanized mild strip ,washer, nut ,bolt etc suitable for 11000 volt HT Line all as specified and directed at site.
M&L Pin type, 11kV polymer insulator 24mm FRP complete all as specified and directed .
M&L Post type 11kV polymer insulator 24mm FRP complete all as specified and directed .
M&L for GI stay assembly set comprising of 16 mm dia 380 mm iron stay bow 1800 mm long stay rod 20 mm dia 300x300x6mm stay plate thimble GI stay wire 7/8 SWG of required length ,incl,loop insulator,earth work and PCC complete withh all accessories as shown in electrical plate No.1 all as specified and directed at site.
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 sqmm complete all as specified and directed .
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 sqmm complete all as specified and directed .
Material & Labour cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 sqmm to 120 sqmm complete all as specified and directed .
S & F Cable route indicator / Marker made up of PCC Block in cement mortar 1:3:6 (20 mm graded aggregrate) of size 900 x 300x 100 mm thick with "DANGER / 11 KV CABLE /MES or DANGER/ 11 KV HT JOINT/ MES" embossing on cable route Indicator / Marker including painting as per approved colour and buried in ground 45 Cms including necessary earth work (as required/ ordered at site) complete all as specified and as directed.
Taking down or up UG HT Cable including cable cover laid in trenches/ cable duct or connection to HT panel /GOD and removing from site and transporting to store for safe custody for reuse or for issue under Sch of Credit all as specified and directed at site including patrolling the complete length and inspecting for any punctures,blow holes,damages and meggering all the cables ,removing the damaged portion all as directed by EIC at site
Relaying the HT cable obtain from item No. 27 any capacity any size complete all as specified and directed at site.
Supplying, laying or fixing, jointing and testing 11 KV (E) system , Crossed linked polyethylene ( XLPE) insulated, screened , PVC bedded, galvanised steel strip or wire armoured, electric power cables( heavy duty) ISI-7098 Mark, with aluminium conductor multi stranded of size 95 Sqmm 3 core , laid in trenches/ laid under floor or fixed naked with walls / on poles etc. complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks and pipe shall be measured and paid separately under appropriate items
Supplying, laying or fixing, jointing and testing 11 KV (E) system , Crossed linked polyethylene ( XLPE) insulated, screened , PVC bedded, galvanised steel strip or wire armoured, electric power cables( heavy duty) ISI-7098 Mark, with aluminium conductor multi stranded of size 120 Sqmm 3 core , laid in trenches/ laid under floor or fixed naked with walls / on poles etc. complete all as specified and directed. Note :- Excavation, earth work, sand cushioning, protection bricks and pipe shall be measured and paid separately under appropriate items
Excavation in trenches not exc. 1.5 m wide and not exec 1.5 mtr in deep for foundation etc.or for shafts,wells, cesspits, mainholes, pierholes etc.in any type of soil for laying of cable, pipe etc and getting out and levelling of bottom surface to required level all as specified and directed
Material and labour for river washed and screened ,dry sand for filling in trenches/sub stations below and around underground cables for cushioning of cables etc complete all as specified. Note :- Punned thickness shall only be considered for payment
Returning filling including leveling,watering and well ramming soil in layers not exceeding 1.5 m above the starting level complete all as specified and directed.
Removing the excavated materials not exceeding 50 m and depositing where directed at level not exceeding 1.5 m above the starting level complete all as specified and directed.
Supplying and laying unreinforced precast cement concrete cable covers, Class HV, Type- 1, Flat, size 300 mm x 180 mm x 40 mm in trenches for cable protection, embossed with "HT ELECTRIC" on the top surface complete all as specified and as directed.
Relaying the HT cable cover obtain from ser item No.27 any type, any size complete all as specified and directed .
M&L Danger notice plate of 1.6 mm thick mild steel sheet ,vitreous enamelled white,with letters, figures and conventional skulll and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size for HT, 25 x 20 cm complete all as specified and directed
Boring/Drilling ( horizontally) manually or mechanically by pneumatic tools under existing road ( maximum 10 M in width) suitable for passing GI tubing of 40 to 80 mm bore complete all as specified.
Supply and laying in replacement of GI pipe 100 mm bore, Light grade (for cable protection ) ISI marked all as directed .
M & L Cement Concrete PCC 1:3:6 type C-1 (using 20 mm graded stone aggregate) as in coping of pole etc including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified
M& L for Brickwork with straight or curved on plan with subclass ‘B’ bricks, exc 6 m mean radius built in CM 1:6 complete all as specified and as directed.
M & L for Rendering 10mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 finished even and smooth without using extra cement complete all as specified and as directed
M&L for cutting of tree branches including cutting of trunk branches & stacking of serviceable material and disposal of unserviceable materials to a distance not exc 50 mtr & clearing site all as specified and directed at site. Note : up to 50 mtr length to be measured as one span
Raj Construction
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .