Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 145 1 0 NEAR OLD LIC SHIV NAGAR VILLAGE TOWN MODIPURAM CITY MEERUT MEERUT UTTAR PRADESH 250110 INDIA | MEERUT | UTTAR PRADESH | 250110 | Admitted-Finance |
| 2 | Admitted-Finance 126 B I MESS ROAD RAI MARKET AMBALA CANTT AMBALA CANTT HARYANA 133001 | AMBALA | HARYANA | 133001 | Admitted-Finance |
| 3 | Admitted-Finance 00 JALESAR MAHAVIR GANJ 00 VILLAGE TOWN JALESAR CITY ETAH ETAH UTTAR PRADESH 207302 INDIA | ETAH | UTTAR PRADESH | 207302 | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹8,000
Closing Date
15 Feb 2021, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE ETC ALIGARH
LAL DIGGI ALIGARH
Construction of ICT bay (01 No 132 KV and 01 No 33 KV) for 40 MVA at 220 KV Substation Etah with other associated work under ETD Mainpuri
2021_UPTCL_549183_1
SHORT TERM ETC-110/2020-21
Open Tender
Electrical Works
Item Rate
20 days
ALIGARH
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SE ETC ALIGARH
₹8,000
3 Mar 2021
27 Jan 2021
16 Feb 2021
27 Jan 2021
15 Feb 2021
27 Jan 2021
120 days
Amount
Shifting of various equipments/materials from switchyard to open yard at 220 KV S/S Etah work including safe loading and unloading, shifting etc.
Erection of Substation Structures:- (a) Sorting and Stacking of Structures.
Erection of Main & Auxiliary structure lattice type ATM, BTM, BCT, ALP etc. consisting of column, beam, peak, mast etc. and auxiliary structure for installation of CTs, PTs, LAs, etc. The job consist of shifting of all material from store to site of erection, erection of structure as per drawing with the help of GI nut & bolt, flat & spring washer, matching the hole, cutting & matching of member if required including cost of all men and T & P excluding GI structure Nut & bolt to complete the work. Erection of Main & Auxiliary structure lattice type BCT, ALP etc. upon foundation and its proper tightening.
Making hole in part of GI main/auxiliary structure / cutting of GI angle drilling of hole existing/ defective structure /plate/Angle and grinding machine with all cost of men, T & P etc.
Erection of following Equipments/Panels as per technical specification, manual and instruction as per direction of supervising engineer.
145 KV SF-6 Circuit Breaker.
145 KV Current Transformer.
145 KV Bus Isolator.
145 KV Tandem Isolator.
145 KV Post Insulator for support.
120 KV Lighting Arrestors.
Erection and mounting of 145 KV CT Junction Box.
33 KV Vacuum Circuit Breaker
33 KV Current Transformer
33 KV Bus Isolator.
33 KV Lighting Arrestors.
33 KV Bus Post Insulator.
Erection and mounting of 36 KV CT Junction Box.
132 KV 40 MVA Control & Relay Panel
Earthing work:- Fabrication of 3 Meter long electrodes with 40 mm dia MS round bar having 150 mm long conical shape by digging cutting, straightening etc. and then placing it vertical inside the ground with Top 700mm below the ground level including shifting of MS round bar from storage place at the Sub-Station to switchyard.
Delta earthing of 120 KV / 33 KV LAs and neutral of Transformer by 40 mm dia 150 mm long conical shape its placing inside the ground in rectangular shape and connecting all 3/6 Nos electrodes with 75x10/50x6 mm MS flat laid on its edge and then this rectangle/triangle shape strictly as per drawing.
120 KV LA ( Rectangle shape by 06 electrodes) with 40 mm dia round bar.
40 MVA Transformer (Triangular shape by 03 electrodes) with 40 mm dia round bar.
33 KV LA ( Rectangle shape by 04 electrodes) with 40 mm dia round bar.
Earthing of equipments by cutting straightening, bending, laying 700 mm below ground and above ground of following size of MS flat for earthing of main and auxiliary structure equipments structure. Transformer body and its neutral point including welding with main earthmat and with object to be earthed, excavation of trenches, its back filling, to complete the work.
Laying MS Flat of size 75x10 mm
Laying MS Flat of size 50x6 mm
Painting of MS flat of different size after cleaning of rusted surface 1st coat of Red Oxide and 2 coat of Bus Green Paint to complete the work.
MS Flat of size 75x10 mm
MS Flat of size 50x6 mm
Bus Bar Stringing and Jumpering:- Opening of jumpers of various 33 KV bay from 33 Main bus bar and 33 KV LA & PT.
Dismantling of 33 KV Main Bus bar of single ACSR Tarantulla conductor per phase along with its fitting, insulator etc.
Stringing of various Single phase bus bar of 132 KV and 33 KV with different type conductor and different length of span as mentioned below. The work includes cutting & bending of conductor, fixing of single/ double bolted type tension fitting/suspension. Hoisting of disc insulator and shifting of material from store site to erection site and all other associated work to complete the work satisfactorily as per drawing and technical specification.
132 KV Bus for 40 MVA Transformer Bay for Zebra/Moose conductor.
33 KV Main Bus of twin ACSR Moose conductor .
Hoisting of 132 KV string under Beam to pass the jumper including hanging of disc insulator and suspension fitting complete with all work.
Jumpering, interconnection of equipment with specified conductor of various 132/33 KV equipments with Main/Transfer/Jack Bus Bar of ACC Tarantulla / ACSR Moose/Zebra/Panther conductor. The work includes cutting of conductor, bending in proper shape, clamping with the help of clamps and all other associated work to complete the work.
132 KV 40 MVA Transformer Bay.
40 MVA Transformer LV side of Twin Moose conductor.
Providing jumpers for various 33 KV bay from main bus to bus isolator twin Panther conductor.
33 KV LA/PT from Panther conductor.
Cable Laying and Termination work:- Laying of flowing sizes of control cable in the cable trench from control relay panel to various equipments/marshalling boxes/junction box etc. in switchyard as per cable schedule, their saddling at every 750mm distance with MS saddles of size 25x3mm size including carriage of cable drums form store to laying site and shifting back to the removing material store and all other associated work to complete the job satisfactorily as per technical specification.
2 Core x 2.5mm2
4 Core x 2.5mm2
6 Core x 2.5mm2
Termination of following size of cables as laid above as per cable schedule including making necessary holes in glands plates or box wherever required. Supply and fixing of cable glands of appropriate size, supply and providing ferrules and Nos. for each core. (The rates of termination of control cable include the all cores of cable at one end with lug).
2 Core x 2.5mm2
4 Core x 2.5mm2
6 Core x 2.5mm2
Supply portion:- Bolted type single Tension fitting for Zebra Conductor suitable for 1x10 No Disc insulator without buckle and hardware set as per technical specification.
Bolted Type single tension fitting for twin moose conductor suitable for 1x4 No Disc insulator without buckle and hardware set as per technical specification.
Bolted type single suspension fitting for single Zebra Conductor suitable for 1x10 No Disc insulator with hardware set as per technical specification.
3 Bolted Type PG clamp suitable for Panther to Panther conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Moose to Moose conductor complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Moose to Panther conductor complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Zebra to Panther conductor complete with HDG nut bolt & washer as per technical specification.
132 KV Bus Post clamp suitable for Panther conductor complete with hot dip galvanized nut bolts & washer as per technical specification.
33 KV Bus Post clamp suitable for Twin Panther conductor complete with hot dip galvanized nut bolts & washer as per technical specification.
Bimetallic terminal connector for 40 MVA T/F HV side bushing rod 30 mm dia made of aluminum alloy LM-6 suitable for ACSR single Panther conductor matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Bimetallic terminal connector for 40 MVA T/F LV side bushing rod 30 mm dia made of aluminum alloy LM-6 suitable for ACSR Twin Zebra conductor matching with bushing rod complete with hot dip galvanized nut & bolts as per technical specification.
Spacer for Twin Moose bundle conductor for 250 mm spacing as per technical specification.
Bimetallic 33 KV Isolator clamp for ASCR Twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
33 KV CT clamp suitable for ACSR Twin Moose conductor complete with hot dip galvanized nut, bolts and washer as per technical specification.
Supply of tinned copper bond size 15x550mm long made of 12 mm multi strand rope type 450 mm long should be joined together and cramped with copper lug (20mm hole) on both ends as per sample.
Supply of cable gland of different sizes
2C x 2.5 mm2 (16mm)
4C x 2.5 mm2 (19mm)
6C x 2.5 mm2 (22mm)
Providing & fixing new generation energy saving & environment friendly long life versatile pressure die-cast aluminum outdoor high beam flood light with power 120 W LED as light source & exclusively designed polycarbonate cover along with electronic driver complete fitting suitable for 220 Volt AC input supply of IS make of CGL/ Havells /Surya/ Philips/ Bajaj etc. brand and providing & fixing of junction box (Size 150x150x200m) having of 01 No. 6Amp. Single pole MCB (L&T, Havells/Schneider make) .
Laying dressing & termination of control cable for the gantry light with the help of clamps vertically on the Gantry & all other associated work required for completion of work.
Versha and Brothers
Hi-tech power transmission
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .