Tender Value
₹9 L
EMD Value
₹18,000
Closing Date
20 Jan 2020, 6:00 pmClosed
AGE (I) Manauri Allahabad
AGE (I) Manauri Allahabad-212212
REPAIR/REPLACEMENT OF DBS AND CONNECTED ITEMS INCLUDING EARTHING IN DOMESTIC AREA AT 24ED AF STATION MANAURI
2019_MES_288509_1
8735/E8
Open Tender
Electrical and Maintenance Works
Item Rate
182 days
AGE (I) Manauri
As per tender documents
6 documents required · 6 mandatory
₹500
AGE (I) Manauri
₹18,000
Yes
27 Feb 2020
12 Dec 2019
23 Jan 2020
12 Dec 2019
20 Jan 2020
4 Jan 2020
Amount
Excavating in trenches, not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for wall foundation etc or for manholes etc not exceeding 10 Sqm area on plan and not exceeding 1.5 metre in depth and getting out in soft/loose soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers each not exceeding 25 cm thick in soft/loose soil.
Removing excavated surplus soil to a distance not exceeding 50 metre and depositing where directed at level not exceeding 1.5 metre above the starting point.
M&L for Sand cushioning in trenches with clean dry unsheathed gently punning around cable for protection complete. Note : Only punned thickness shall be measured for payment
M&L for brick, old sub class 'B' well burnt, laid dry flat in trenches for protection of cable over LT cable, complete all as specified and directed.
Cutting /boring to pilinth protection/ hard standing / road etc in suitable depth to across the GI pipe size upto 80 MM dia of bore for drawn through XLPE under ground cable for giving mechanical protection to cable complete all as directed. Note ; Quoted rate shall be included the cost of required material for repairing to disturbed surface all as per exisiting.
Supply and laying galvainesd steel tubing light grade 40 mm dia of bore fixed with pole/ surface of wall / laid in trench etc as site using 02 Nos clamp made out by GI strip in size 25x4 mm with nut bolt and washer etc all as directed.
Supply and laying galvainesd steel tubing light grade 80 mm dia of bore fixed with pole/ surface of wall / laid in trench etc as site using 02 Nos clamp made out by GI strip in size 25x4 mm with nut bolt and washer etc all as directed.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 25 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 35 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 50 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 70 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 95 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
Supply, laying, jointing, thembling, glanding & testing of underground LT cables XLPE insulated, PVC sheathed, aluminium conductors, multistranded, armoured heavy duty 1100 Volt grade cross sectional area 120 Sqmm 3.5 core laid in trenches/ducts/along poles/through pipe under road etc with new aluminium lugs including taking out of old cable. Note :- Excavation, earth work, sand cushioning, protection cover and pipe shall be measured and paid for separately under respective items of this schedule.
S&F in replacement timer switch (FM series) suitable for 16A/250 V AC supply, FM/1 quartz daily 240V AC base/din mounting including making connection complete all as specified and as directed. Make : L&T Model- J648B1 or equivelent in Seimens/ Schneider/ C&S
Supply & fixing, conneting to automatic street light control switch rating 25 Amp per phase max load 8 KW , circuit wiring 10 sq.mm with Infrared Sensor based nature switch & voltage monitoring system light lux level oprated, required illuminance level for switching on is < 30 lux and for switching off >10 lux. the sensor should also have part light operation facility of min 4 hrs to 12 hrs complete all as specified and directed. Make : model - Swadeep-02EC8KW3P or equivelent as specified in List of makes.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, triple pole and neutral, 4 ways, 415 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 12 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 8 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement factory made sheet metal enclosure distribution boards, (protection class IP-43) double door, verticle type suitable for mounting MCCBs/ RCCBs/ MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, Single pole and neutral, 4 ways, 240 volts. Note :- MCCBs/ RCCBs/ MCBs shall be measured and paid for separately under respective item of this schedule.
S&F in replacement MCCB, four pole, 415 Volt ,40 Amp rating, 16 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F in replacement MCCB, four pole, 415 Volt ,63 Amp rating, 16 KA ultimate breaking capacity fixed in DBs catered herein before.
S&F in replacement RCCB, double pole, 240 Volt , HPI, 40 Amp rating, 30 mA, 2 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement RCCB, double pole, 240 Volt , HPI, 63 Amp rating, 30 mA, 2 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement RCCB, four pole, 415 Volt , HPI, 63 Amp rating, 30 mA, 4 nos of 17.5mm modules for earth leakage protection fixed in DBs catered herein before.
S&F in replacement MCB, tripple pole and neutral, 415 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, single pole and neutral, 240 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
S&F in replacement MCB, single pole, 240 volts, 32 Amps rating, 10KA, "C" series fixed in DBs catered herein before.
Supply fixing conneting to automatic street light control transfer switch rating 160 Amp 415 volts 50 HZs conforming to IEC 947-6-1 closing current 3.0 A / 230 volts triping current 0.5 A / 230 volt complete including taking out old control switch all as specified and directed. Make : L&T / Seimens/ Legrand
Supply fixing conneting to automatic street light control transfer switch rating 63 Amp 415 volts 50 HZs conforming to IEC 947-6-1 closing current 3.0 A / 230 volts triping current 0.5 A / 230 volt complete including taking out old control switch all as specified and directed. Make : L&T / Seimens/ Legrand
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 1.5 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 2.5 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated muilticore strandard copper single & multi flexible round cable size 4.0 Sqmm 3 core ISI marked 660/1100 Volt conforming to IS:694-1990 complete.
Supply & fixed in replacement PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 10 Sqmm 2 core 1100 Volt complete.
Supply & fixed in replacement PVC insulated sheathed aluminium conductor armoured cable with inner sheathing for service connection size 6 Sqmm 2 core 1100 Volt complete.
Earthing complete with galvanised mild steel earth electrode plate 600 X 600 X 6 mm thick buried directly and vertically in ground connected to galvanised iron earth strip 32x6mm size by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth strip protected by galvanised iron 40 mm bore medium grade pipe with all fittings from the earth electrode fixed along pole with and including 25 x 6mm flat iron clamp, bolts, nuts and washers and watering pipe shall be 20 mm bore GI medium grade from top of the earth electrode to bottom of the earth pit including all excavation and earth work in any type of soil and removal of surplus soil upto 50 metre, PCC pit with pre-cast RCC cover with handle, charcoal/salt, funnel , CI frame etc complete all as directed. Notes :-(i) The concrete pit shall be made in PCC 1:3:6 type C-1, 40mm thick precast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate with suitable MS handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. Reinforcement in RCC cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be adjusted through deviation order. (iii) Item includes cost of 7.5 metre earth strips. Any variation in length shall be adjusted through deviation order. (iv) Plate electrode shall be surrounded by adequate quantity of charcoal dust & salt to a packed thickness of 15 cm on all sides.
Earth continuity conductor or main earthing lead 32x6mm GI strip laid in pipe or fixed on wall or any other position including jointing by tinned copper/brass nuts, bolts and washers in adition brazing at every joint (beyong 7.5 metre)
Supply and fixed in replacement of flood light fitting LED 115/120 W equipped with IP66 protection with mounting bracket not bolt washer to be fix on pole/ wall etc all as site making all connection using suitable three core flexible copper cable drawn through in flexible conduit pipe from control box to light fittings complete all as directed. Note :- (i) Fitting shall be of Bajaj (AMAZE) cat No BJFL 120 W LED 1 WW (warm white) or Crompton cat Part No LFLN-120-CDL/60 (Pluto) or philips cat part No BVP122 LED 115 CW HE AK 55° FG XTFCL S4 or equivalent model of make Wipro. Light fitting of other make of higher capacity may be used without any price adjustment. (ii) Cable from MCB to fitting shall be included in unit rate quoted by contractor.
M&L for painting to external surface of old painted steel tubular pole upto 11 Mtr long in varrious location using aluminium paint in two coats (one as finishing) by spray gun after removing/ cleaning/ scraping etc to old fadded paint incl cross arm, support all as per site , making alternating strip in 30 CM width each upto 1.5 Mtrs above normal ground level and marking pole No etc all sign complete all as directed. Note : Paint colour shall be approved by Deptt.
M&L for painting to external surface of old painted PCC pole upto 11 Mtr long in varrious location using aluminium paint in two coats (one as finishing) by spray gun after removing/ cleaning/ scraping etc to old fadded paint incl cross arm, support all as per site , making alternating strip in 30 CM width each upto 1.5 Mtrs above normal ground level and marking pole No etc all sign complete all as directed. Note : Paint colour shall be approved by Deptt.
Taking up / bending / jumfering/ titing in permissible sag etc to downed existing run of over head line in 4 run for phase , neutral with earthing wire and safe guard in any specification all as site, mouting on existing poles and jumfering with isulators using puller , testing ,re-charging etc in varroius location, including trimming/pruning/dressing the tree branches and cleaning or creepers from poles complete all as directed. Note:- (i) Tree branches upto three metre from external conductor shall be trimmed/cut. ( ii) All runs of OH line (HT/LT) for phase , neutral with earthing wire and safe guard shall be measured as one unit length.
Note :- Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material. The contract amount shall be arrived at after deduction of Schedule of Credit from the total quoted amount in BOQ.
M/S Garg Sons
M/S VIJAY SINGH
M/S A M ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .