Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.5 LAccepted-AOC | L1 | Accepted-AOC Being lowest bid. | |
| 2 | L2₹20.2 L+₹3.8 L (22.9%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bid. | |
| 3 | L3₹23.1 L+₹6.6 L (40.0%)Rejected-Finance H NO B III 95 MOHALLA GHARTHOLI MISSION ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-Finance Other than lowest bid. | |
| 4 | L4₹26.9 L+₹10.4 L (63.2%)Rejected-Finance | L4 | Rejected-Finance Other than lowest bid. |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
19 Dec 2022, 6:00 pmClosed
GE (SOUTH) MAMUN
GE (SOUTH) MAMUN PATHANKOT-145001
REPAIR/REPLACEMENT OF OLD BURNT WIRING AND E/M FITTINGS AND FIXCTURES, DBs, SUB MAIN WIRING IN OTM ACCN OF D-1 AND D-II ZONE AREA UNDER AGE E/M OF GE (SOUTH) MAMUN
2022_MES_564521_1
GE(S)/M-51/2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
GE (SOUTH) MAMUN
AS PER NIT
8 documents required · 8 mandatory
₹500
GE (SOUTH) MAMUN
₹80,000
Yes
7 Jan 2023
22 Nov 2022
26 Dec 2022
22 Nov 2022
19 Dec 2022
6 Dec 2022
Amount
Taking down carefully aluminium / copper point wiring (light / fan / socket or power) complete with all fitting, accessories such as swithes,sockets, bells, holders,tube light, bulk head, pendant ceiling roses & regulators and making good disturbed surfaces of walls, floors to match with existing specifications and keeping aside serviceable items for reuse and deposited to MES store yard and removing UNSV items from site, complete all as specified and directed.
M&L for point wiring for one light point / fan point / bell point controlled by one switch with 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (RYB) for phase, black for neutral and 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable as earth lead drawn in as earth continuity wire in green colour connected to common earth dolly and each terminal/joints fitted with thimble and including connected non metallic rigid PVC conduit not less than 20 mm dia including CI/MS terminal box of required size including 3mm thick plastic laminated top sheet cover fitted with brass screw and cup washer including cutting chases to walls and making good the disturbed surfaces to match with the existing specifications, complete all as specified and directed. Note : Including in ceiling portion surface conduit wiring shall be carried out.
All as per Srl item No. 2.00 here-in before but point wiring in existing PVC conduit pipe, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but with FRLS, multistranded copper conductor in PVC Casing and capping including necessary PVC accessories i.e. Tee, elbow, socket etc., complete all as specified and directed.
M&L for point wiring for one 2 way light point / fan point / bell point controlled by one switch with 1.5 Sqmm (red or yellow or blue colour) for phase, black for neutral PVC insulated unsheathed copper conductor single core multistranded FRLS cable and 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable as earth lead drawn in as earth continuity wire in green colour connected to common earth dolly and each terminal/joints fitted with thimble and including connected non metallic rigid PVC conduit not less than 20 mm dia including CI/MS terminal box of required size including 3mm thick plastic laminated top sheet cover fitted with brass screw and cup washer including cutting chases to walls and making good the disturbed surfaces to match with the existing specifications, complete all as specified and directed. Note : Including in ceiling portion surface conduit wiring shall be carried out.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board in existing conduit, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on independent board in PVC casing & caping including necessary PVC accessaries i.e Tee, elbow, socket etc., complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3 pin 5 Amps socket outlet on same board with other switch, complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 4 sqmm FRLS PVC insulated unsheathed multistranded copper conductor drawn in and including connected non metallic rigid PVC conduit including not less than 20mm dia medium duty including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 4.00 Sqmm multistandard PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for metal plug top AC & Geyser point using 4.0 Sqmm FRLS PVC insulated unsheathed copper conductor cable including non metallic rigid PVC concealed conduit not less than 20mm dia medium duty including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 2.50 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 4.0 Sqmm FRLS PVC insulated unsheathed copper conductor cable in existing non metallic rigid PVC concealed conduit including sunken steel boxes of required size including 3mm thick plastic laminated bakelite sheet cover including 4.00 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
All as per Srl item No. 2.00 here-in before but for one 3/5 pin 15Amps socket outlet on independent board using 4.0 Sqmm FRLS PVC insulated unsheathed multistandard copper conductor cable drwan in and including PVC casing caping (ISI Marked) including necessary accessaries such as tee, elbow, sockets etc.,including not less than 20mm dia medium duty including sunken steel boxes of required size dully engrouted in wall by cutting, chasing and making good the disturbed surfaces with 3mm thick plastic laminated bakelite sheet cover including 4.00 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable earth wire connecting to earth dolly complete all as specified and directed.
S&F Switch piano flush button, single pole, one way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F Switch piano flush button, single pole, two way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F bell push flush button, single pole, one way, 5/6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F Socket outlet, 5 Pin, 6Amps, multipurpose, flush type, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F Socket outlet, 3 Pin, 6 and 16 Amps, multipurpose, 2 in 1, flush type, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F Switch piano flush button, single pole, one way, 16 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F fan regulator stepped type electronic mini , hum free with polycarbonate body, suitable to control speed of fan from 0 to 100% and connecting electrically, complete all as specified and directed.
S&F fan regulator stepped type electronic delux with polycarbonate body, suitable to control speed of fan from 0 to 100% 5 to 8 step and connecting electrically, complete all as specified and directed.
M&L for modular point wiring for one light point / fan point / bell point controlled by one switch with 1.5 Sqmm (red or yellow or blue colour) black for neutral PVC insulated unsheathed copper conductor single core multistranded FRLS cable 1100 volts grade in and including connected non metallic rigid PVC conduit including not less than 20mm dia including conduit accessaries i.e Tee, elbow, bend tee junction boxes etc fixed concealed/recessed in wall or ceiling etc and 1.5 Sqmm PVC insulated unsheathed copper conductor single core multistranded FRLS (green colour) cable 1100 volts grade as earth lead drawn in as earth continuity wire in green colour connected to common earth dolly and each terminal/joints fitted with thimble and including connected non metallic rigid PVC conduit including CI/MS box of required size including inner & outer frame plate matching with surrounding with modular surken cover including cutting chases to walls and making good the disturbed surfaces to match with the existing specifications, complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but point wiring controlled by module one switch in existing PVC conduit pipe, complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but point wiring controlled by module two way switch , complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but added for one 5 pin 5 Amps socket outlet on independent board, controlled by 5 Amps one way switches complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but added for one 5 pin 5 Amps socket outlet on independent board, controlled by 5 Amps one way switches in existing conduit, complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but added for 5 pin 5 Amps socket outlet on same board, controlled by 5 Amps one way switches complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but added for one 5 pin 5 Amps socket outlet on same board, controlled by 5 Amps one way switches in existing conduit, complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but for one 15 Amps socket outlet using 4.00 sqmm FRLS PVC insulated multistranded copper conductor cable including 4.00 sqmm FRLS PVC insulated unsheathed multistranded copper conductor cable as earth wire, complete all as specified and directed.
All as per Srl item No. 22.00 here-in before but for one 15 Amps socket outlet using 4.00 sqmm FRLS PVC insulated multistranded copper conductor cable including 4.00 sqmm FRLS PVC insulated unsheathed multistranded copper conductor cable as earth wire in existing conduit, complete all as specified and directed.
S&F for one module switch, one way, 6 Amps, 2 module 240 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for one module switch, one way, 16 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F moduler bell push flush button, single pole, one way, 6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for one module switch, two way, 6 Amps, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for two module socket , 6 Amps, 230 Volts 2/3 pin AC with polycarbonate body, complete all as specified and directed.
S&F for two module socket , 6/16 Amps, 230 Volts 2/3 pin AC with polycarbonate body, complete all as specified and directed.
S&F for modular fan step reguator 120W, 240 Volts 2 module AC with polycarbonate body, complete all as specified and directed.
S&F ceiling rose, surface bakelite,2 to 3 terminals, 230 Volts AC with polycarbonate body, complete all as specified and directed.
S&F for lamp holder insulated body of PVC / polycarbonate type with back plate suitable for Angle/ batten fittings complete all as specified and directed.
S&F bell electric, heavy duty, Ding Dong type, 230 Volts AC, single pole, complete all as specified and directed.
S&F in replacement 20 Watt linear 4 feet long LED integrated batten made of epoxy powder coated white, high efficiency, long life LED package in integral module with lumen efficacy > 100 Lm/W and viewing angle of 120° to ensure better uniformity, complete with all accessories prewired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable of size 0.50 Sqmm 2 core all as required at site, complete all as specified and directed.
S&F in replacement 10 Watt linear 2 feet long LED integrated batten made of epoxy powder coated white, high efficiency, long life LED package in integral module with lumen efficacy > 100 Lm/W and viewing angle of 120° to ensure better uniformity, complete with all accessories prewired and connecting electrically to ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable of size 0.50 Sqmm 3 core all as required at site, complete all as specified and directed.
S & F in replacement of surface mounted LED Bulk Head luminaires 10 watts with ABS body & polycarbonate diffuser available in CCT 6000K IP 54 complete all as specified and directed.
S&F in replacement Recessed LED ceiling 36 Watt, luminaire of size 600mm x 600mm with white light window and built-in LED lamp with all accessories and making connection using 3 core, 0.50 Sqmm PVC insulated and overall sheathed flexible copper conductor cable and testing after fixing, complete all as specified and directed.
S & F in replacement energy efficient LED ceiling light 15 W of size 1x1 feet complete with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver 3 core flexible copper conductor cases of suitable size complete all as specified and directed.
S&F in replacement of building security light luminaire 30 Watt, IP 66, AC 230 volts made up of pressure dia cast iron housing complete making connection using PVC insulated and sheathed 3 core multi stranded copper conductor cable of size 0.50 Sqmm from ceiling rose including suitable size of bracket of light grade pipe for mounting of fitting along with clamps, nut bolts and washers complete all as specified and directed.
S & F in replacement of decorative wall bracket light white in colour made up of poly carbonate suitable for and including 9 watts retrofit LED lamp complete all as specified and directed.
S&F in replacement of decorative post of lantern 40 Watt 230 volts, 50Hz, mushroom or oval shaped in sothing opal/prismatic finish made up of polycarbonate, suitable for 40 watt LED, all accessories prewired complete all as specified and directed.
Note for srl item No 41 to 48 above 1. Driver shall be potted anti-vibration types. 2. LM-79 and LM-80 test report with 1 Lakh burning hours LED life from NABL lab shall be provided. 3. CRI (Colour Rendering Index) of fixture shall be > 70. 4. CCT (Colour Co-related Temperature of fixture shall be 5700K + 300 K. 5. System Lumen Efficacy shall be > 100 Lm/W. 6. 10 KV separate Surge Protection shall be provided as a part of fitting. 7. 5 years guarantee shall be provided by contractor supported by OEM covering all parts of luminaire. 8. Lenses shall be Modular Type. 9. PCB used shall be MC PCB type. 10. The defect liability period of LED light shall be 05 years from the certified date of completion & the contractor shall replace/repair the defective fitting within 07 days after handing over to contractor for replacement/repair. 11. CA No. shall be written on each fitting before installation. 12. The name of manufacturer to be embossed on the fitting. 13. The fittings shall have arrangement so that maintenance required, if any can be carried out from Top cover.
M & L for sheet metal enclosure MCB distribution board single pole and neutral with a two pin and earth plug and socket 20 amps 240 volts, complete with one single pole MCB of 20 amps complete all as specified and directed.
Supply & Fix sheet metal enclosure with DB's ( grouted in walls) single pole and neutral single door type for MCB's 02 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
Supply & Fix sheet metal enclosure with DB's ( grouted in walls) single pole and neutral double door type for MCB's 04 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
Supply & Fix sheet metal enclosure with DB's ( grouted in walls) single pole and neutral double door type for MCB's 08 ways with 200 Amps 240 volts rated bus bar complete all as specified and directed.
S&F of MCB single pole and neutral 63 Amps 240 volts B series complete all as specified and directed.
S&F of MCB single pole and neutral 40 Amps 240 volts B series complete all as specified and directed.
S&F of MCB single pole 6 to 32 Amps 240 volts B series complete all as specified and directed.
M&L for replacement of earthing complete with galvanised GI earth plate electrode of size 600x600x6mm thick, burried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level) with top edge of earth plate not less than 1.5 Mtr below normal ground level, connected to galvanised earth lead wire 4mm dia by means bolt, nuts, check nuts and washer made of galvanised iron or steel including earth work in any type of soil, charcoal dust and salt layers 15cm thick all around the earth plate as shown in electrical plate No. 03 of SSR Part-I 2009 including 20mm bore GI watering pipe 'medium grade' with funel and wire mesh and 15mm bore GI protection pipe 'light grade' from earth pit to main board including PCC pit in cement concrete 1:2:4 type B-2 (using 40mm graded stone aggregate) and including angle iron frame of size 40x40x3mm with hold fast embeded in PCC, RCC pit cover with suitable handle and earth work and removal of surplus soil to a distance not exc 50 Mtr, complete all as specified and directed.
M&L for submain wiring with two single core PVC insulated flexible FRLS copper conductor cable of size 6.0 Sqmm and one single core PVC insulated flexible copper conductor cable green colour of size 6.0 Sqmm as FRLS earth lead, drawn in existing surface/ recessed steel/ PVC conduit omplete all as specified and directed. Note :- Two run of cable with one run of earth wire and PVC conduit shall be measured and paid for as one unit.
M&L for submain wiring with two single core FRLS PVC insulated flexible copper conductor cable of size 6.0 Sqmm and one single core PVC insulated flexible copper conductor cable green colour of size 6.0 Sqmm as earth lead, drawn in and including concealed non metallic rigid PVC conduit, medium grade and making good the disturbed surfaces to match with existing specifications, including taking down exisating sub main wiring complete all as specified and directed. Note :- Two run of cable with one run of earth wire and PVC conduit shall be measured and paid for as one unit. Rate is inclusive of cutting chases for concealed conduit.
S&F in repair hylum sheet of size 5''x5'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 8''x5'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 10''x12'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair hylum sheet of size 8''x10'' including cutting for required shape for fixing of existing switches & sockets complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 4''x4'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 7''x4'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 9''x11'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair sunken steel box zinc oxide plated of size 7''x9'' including cutting the wall to required shape for fixing and making good the disturbed surfaces to match existing one complete all as specified and directed.
S&F in repair prewired VTPN distributed boards with provosion of MCCBs as incomer 63 A, 04 pole IP 54 04 ways (for incomming MCCBs and outgoing MCBs) with copper busbar for each phase with neutral bar, earth bar and cable ties for cable management fully insulated busbar & shrouded neutral bars with 63 Amps MCCB 16 KA 04 pole as incomerand SP MCB's of cap 6- 32 Amps as outgoing complete all as specified and directed. Note : Rate of MCCBs and MCBs , cutting, chases and grouting in wall are included
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soi complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed.
M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and directed.
M&L for brick protection sub class ‘B’ bricks old size laid dry flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed.
Supply, laying, testing and commisioning of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sqmm 3.5 core complete all as specified and directed.
All as per Srl item No. 73.00 here-in before but but for 16 sqmm 4.0 core , complete all as specified and directed.
All as per Srl item No. 73.00 here-in before but but for 10 sqmm 2 core , complete all as specified and directed.
All as per Srl item No. 73.00 here-in before but but for 6 sqmm 2 core , complete all as specified and directed.
S&F in replacement of old u/s service cable size 6 sqmm twin core multistranded fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed complete all as specified and directed.
S&F in replacement of old u/s service cable size 16 sqmm twin core multistranded fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed complete all as specified and directed.
KONARK ENTERPRISES
M/S HIMANSHU BUILDERS
KULBHUSHAN AGGARWAL
Bidder Name
KULBHUSHAN AGGARWAL
GOLDEN CONSTRUCTIONS
M/S HIMANSHU BUILDERS
KONARK ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .