Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.4 LAccepted-AOC RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹31.6 L+₹1.2 L (3.93%)Rejected-Finance | L2 | Rejected-Finance BEING NOT LOWEST | |
| 3 | L3₹31.9 L+₹1.5 L (4.84%)Rejected-Finance WZ 1000 NANGAL RAYA PANKHA ROAD SOUTH WEST DELHI DELHI 110046 | DELHI | SOUTH WEST DELHI | DELHI | 110046 | L3 | Rejected-Finance BEING NOT LOWEST | |
| 4 | L4₹33.4 L+₹3.0 L (9.78%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | L4 | Rejected-Finance BEING NOT LOWEST | |
| 5 | L5₹33.5 L+₹3.1 L (10.2%)Rejected-Finance 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | L5 | Rejected-Finance BEING NOT LOWEST |
Tender Value
₹44.5 L
EMD Value
₹89,140
Closing Date
16 Oct 2023, 6:00 pmClosed
AJIT KUMAR,IDSE
GE U ELECTRIC SUPPLY
PROVISION OF LT XLPE CABLE ALONGWITH LT PANEL CONNECTED ACCESSORIES AT BRAR SQUARE , PROVN OF 03 X HIGH MAST LIGHTS FOR UNIT COMPLEX OF EETSU AND PROVISION OF ELECTRIC SUPPLY REQUIRED FOR OSG, DELHI AT CVD LOCATION UNDER GE (U) E/S DELHI CANTT
2023_MES_616183_1
GE ELECT/D-55/2023-2024
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE U ELECTRIC SUPPLY
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE U ELECTRIC SUPPLY
₹89,140
Yes
17 Nov 2023
18 Sept 2023
18 Oct 2023
18 Sept 2023
16 Oct 2023
4 Oct 2023
Amount
Excavation in trenches not exceeding 1.5 metre wide & not exceeding 1.5 meter in depth for foundation,laying of cable or pipe ( where provided for protection of cable or fixing with poles and stays) and getting out in any type of soil including trimming the sides and forming bottom surfaces to required levels complete all as specified and directed.
Removing surplus excavated soil to a distance n.exc. 50 metre and depositing where directed at a level n.exc.1.5 metre high from the starting point.
Returning, filling in trenches in soft/loose soil in layers n.exc. 25 cm after laying of cables including spreading, levelling, and well ramming complete all as specified and directed.
M&L for sand filling in trenches with clean dry unwashed sand free from sharp particles, gently punning around the cables complete all as specified and directed.
Supply and laying brick old size, sub class 'B' brunt bricks laid in trenches as cable cover across the cable in trenches complete all as specified and directed.
Supply and fixing of galvanized High mast light suitable for 8 lantern LED flood light Luminaries symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6 mm dia 7/19 gauge and double drum winch with luminaires mounting arm, pulley assembly, aviation obstruction light, lighting arrestor spike including earth work and RCC foundation as per height 16 Mtr with the following technical specification. Make of High mast:- Crompton greaves/Bajaj electric/ C&S Electric NOTE:-Technical and foundation drawings shall be submitted by the contractor/OEM for approval of accepting officer before commencement of work. (a) MAST STRUCTURE:- The high Mast shall be of continuously tapered, polygonal cross section polygon type (Minimum 16- Sides) of 15/16 Mtrs. in height presenting good visual appearance and shall be based on proven design to given assured performance, reliability and service. The Mast shall have an approximate top diameter of say 150 mm to 200 mm and bottom diameter of 350 mm to 450 mm, The weight of the Mast shall not exceed more than 1600 kgs, excluding weight of Luminaire, to maintain good elasticity of slender structure.
(b) MAST CONSTRUCTION :- The Mast shall be fabricated from special steel plates of BS EN 10025 grade, cut and folded to form polygonal section and shall be telescopically jointed and fillet welded. The welding shall be in accordance with BS: 5135. The procedural weld geometry and the workmanship shall be exhaustively tested by the radiography on the completed welded and certificates submitted. The Mast shall be delivered in only 2 sections without any circumferential welding at site, which shall be joined together by slip-stressed-fit method. The joining shall be with stressing equipment, thus forming the sleeve joint. No site welding or bolted the joint will be accepted. The overlap distance shall have full penetration of longitudinal welds. The base plate of the mast shall be at least 25 mm. thick. An adequate door opening min 1400mm x 300mm shall be provided at base of each mast such as to permit clear access to equipment like winches, cable pug and socket, etc. The opening shall be complete with a close fitting vandal resistant, weather-proof door provided with a heavy duty lock. For metal protection of the Mast, the entire fabricated Mast shall be hot dip galvanised internally and externally, having minimum average thickness of 65 microns.
(c) DYNAMIC LOADING:- The Mast structure shall be designed for an assumed maximum reaction arising from the maximum wind speed at Delhi and measured at a height of 10 Mtrs. above ground level . The design life of the Mast shall be min. 25 years. Wind excited oscillation shall be damped by the method of construction and adequate allowance made for the related stresses. The offered High Mast shall be a tested design.
(d) FOUNDATION:- The tenderer shall see the site closely and minutely with regard to the nature of the soil, average depth of decomposed garbage and debris at proposed Mast locations and the other site conditions before working out the type of foundation and specifications for the proposed High Mast. The tenderer shall be responsible for the design of the foundation and safe erection and installation of the High Mast in mechanically and structurally safe working condition for the design life of the Mast as per manufacture design The load bearing (safe) capacity of the soil shall be indicted by purchaser to decide the type of foundation and its specifications. The holding down bolts shall be at least 20 nos. of high tensile strength and shall be supplied complete with anchor plate of 6 mm thick for casting into the foundation. The ensure correct vertically and horizontality of bolt alignment. (Note : Cost of foundation as per specification of manufacturer shall be deemed to be included in the rate quoted by the contractor)
(e) LANTERN CARRIAGE:- The fabricated lantern carriages shall be provided for holding fittings and control gear provided on each High Mast. The lantern carriage shall be of special design and of durable steel tube construction designed to act as electric conduit with cable holes fully protected by grummets. The diameter of the lantern carriage shall be suitable so as to hold designed number of LED floodlight fittings, as specified in the tender design along with the control gear boxes and lantern. The lantern carriage shall be fabricated in three parts joined by bolted flanges with SS bolts with nuts to enable easy removal from the erected mast for replacement/ maintenance purpose. The carriage shall be supported/ suspended by three wire ropes for better stability. The lantern carriage Assembly shall not touch the lower surface of the Mast. The carriage design and fabrication shall be such that the lantern carriage will suit the lanterns and their control gear boxes to be used in the work. The Lantern Carriage shall be so installed that it does not cause any damage to the surface of the Mast and is provided with protective buffer arrangement. The complete Lantern carriage shall be hot dip galvanised after fabrication. The weather - proof cast aluminum junction boxes (IP-66) shall be provided on the Lantern carriage assembly from which the inter- connections will be made to the designed number of floodlight fittings and lanterns on the carriage.
(f) MECHANICAL ARRANGEMENT:- For installation and maintenance purpose, it will become necessary to raise or lower the lantern carriage assembly. To enable this, a suitable winch arrangement shall be provided in the base of the Mast, complete with top pulley, winch stainless steel wire ropes and winch driving power tool. (i) WINCH:- The winch shall be of completely self-sustaining type. the winches shall be of self- sustaining type by means of an oil bath and the lubrication shall be of recommended quality. Termination of the ropes of the winch shall be in such a way, that it does not involve distortion or twisting of the rope configuration. At least 6 turns of rope shall remain in tension on the drum even when the lantern carriage is fully lowered. the winch shall be designed to be installed or removed form the door opening at the base of the mast. The winch drums shall be grooved to ensure mechanically strong, stable and tidy rope lay with no chances of rope slippage or skippage. The winch shall be capable of operation by hand or by means of external power tool. Integrated power tool with worm is not acceptable. A test certificate shall be supplied along with each winch in support of the maximum load operated by the winch and for the safety of operation at the full load rotation. A handle shall also be provided for hand operation of the winches.
(ii) TOP PULLEY ASSEMBLY:- The top pulleys shall be of a diameter, appropriately large enough to accommodate the steel wire ropes and the multicore electric cable. The material of construction of the pulley blocks shall be non- corrosive and made of dia cast (LM-6) aluminum alloy. The pulley assembly shall be complete with self lubricating bearing and stainless steel spindle. (iii) STAINLESS STEEL WIRE ROPES:- Stainless steel wire shall be AISC 316 grade 7/ 19 construction 2 Nos ropes for winch and 3 Nos for lantern carriage, 6 mm dia having a breaking load capacity of 2350 kg complete with stainless steel thimbles. The end for connection to the winch drum shall be fitted with thimbles and the thimbles shall be secured by copper compression splices.
(g) CABLE AND CABLE CONNECTIONS :- The connections shall be made with flat core flexible round sheath power cables of appropriate rating as per the schedule. The base compartment of the High Mast shall have one terminal box for terminating the incomer cable. The maintenance cables equal to that within the Mast and fitted with travelling cable 5 core 4 sqmm flexible having plug socket shall be provided to energize lanterns while in lowering position by hooking up at the base compartment socket supply. Similarly, the provision shall be made for electric supply at the base compartment to enable operation of the external power tool for lowering or rising of the lantern carriage assembly. The trailing cables of the lantern carriage rings shall be terminated by means of metal cased plug and socket provided in the base compartment to enable flexibility.
(h) WINCH DRIVING POWER TOOL :- The electric driven tool shall be single speed, (1.2 Mt/min) reversible three phase & hand operated motor. The power tool shall be complete with very robust remote control switch such that the tool can be operated from safe distance of 5 Mtrs. There shall be and arrangement for self alignment off power tool which can be self supported during operation. Manual handle shall be provided for hand operation of the winches. The capacity rating and speed of the electric motor used in the power tool shall be specified by the tenderers. (j) LIGHTNING FINIAL & AVIATION OBSTRUCTION LIGHTS:- One number heavy duty hot dip galvanised lighting finial shall be provided for each mast. Suitable aviation obstruction lights of reliable design and reputed manufacturer shall be provided on top of each mast.
Supply, installing, testing and commissioning of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 500 Amps aluminium bus bar and with 250 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level.
S&F of LED flood light Fitting 210 watt LED, suitable for mounting on High Mast Light structure, IP-65 protection, single peice pressure die cast aluminium housing high grade powder coated finish with heat resistant toughned clear glass cover for lamp and control gear compartment with high voltage surge protection device up to 5 KV, with bolts,nuts & washers all as specified.
Supply, laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sqmm 3.5 core.
Supply, laying and testing cable XLPE insullated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core.
Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 40 to 80mm bore and making good both ends all specified and directed
Supply and laying GI tubes light grade ISI marked , galvanized, 40 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed .
Supply and laying GI tubes light grade ISI marked , galvanized, 50 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed .
Supply and laying GI tubes light grade ISI marked , galvanized, 80 mm bore laid in trenches or under floor or fixed with poles/walls for protection of electric cable all as directed .
Earthing complete with galvanised steel earth plate electrode 60 cm x60 cm x 6 mm thick buried directly in ground ,(Earth pit not less than 2.25 meter deep below ground level) with top edge of plate not less than 1.5 meter below normal ground level ,connected to and including galvanised iron earth strip 25x4 mm by means of nut, bolts, check nuts and washers of galvanised iron or steel and provision of charcoal dust and common salt packed all around the earth plate including necessary excavation and earth work in any type of soil and testing complete all as specified and directed and shown in electrical plate number 5 of MES SSR part-I(1991) (a) Excavation and earth work for drilling hole for electrode in any type of Soil. (b) PCC pit in cement concrete 1:2:4 type B-1, Pre cast RCC cover with suitable handle 40 mm thick in PCC 1:2:4 type B-1, reinforced with welded steel wire fabric weighing not less than1.87 Kg/ Sq meter. (c) Funnel with watering pipe of GI 20 mm nominal bore light grade and lugs etc complete all as specified and directed (d) 40 mm nominal bore medium grade GI protection pipe 5 meter long for protection of earthing lead complete all as specified and directed. (e) Requisite quantity of common salt and charcoal. (f) Testing of earthing.
Supply for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 185 sqmm 3.5 Core all as per IS , specified & directed by Engr-in-charge.
Supply for laying & testing of cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminum conductor of size 50 sqmm 3.5 Core all as per IS , specified & directed by Engr-in-charge.
(c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer
Supply, installing, testing and commissioning of factory made and tested Bus bar chamber outdoor type with canopy made out of 3.15 mm CRCA MS sheet, and 40x40x5mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front opening type, with apron for cable entry closing locking arrangement ,of size 450mm x 450mm x 300mm with 4 Nos 500 Amps aluminium bus bar and with 315 Amp MCCB, 4 pole, 36 KA, 415 Volt 50 Hz including excavation, earth work and platform for the Bus bar chamber with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed sotne aggregate on top and grouting bolts etc for Bus bar chamber. The platform shall be such that it is of a height 45 cm above the nearest road level.
M & L for earthing complete with galvanized Steel earth plate electrode 600 x 600 x 6.0 mm thick, buried directly in ground (earth pit not less than 2.25 meters below normal ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level surrounded from all sides by mixture of charcoal and common salt and electrode connected to and incl galvanized iron strip 32X6 mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel and earth wire protected by GI protection pipe light grade 40mm dia connected to main earth wire on pole or control board GI pipe light grade 20mm bore for watering funnel with wire mesh PCC chamber pit in PCC 1:3:6 type C-1 40mm thick Precast RCC -25 cover reincorced with 8 mm dia TMT bars @ 10 cm C/C on both sides and handle, excavation and earth work in any type of soil and removal upto 50m complete all as sprecified and shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion.
Supply and fix MCCB 63 Amp, 3 pole , 25 KA, 50 Hz with MCCB sheet metal enclosure mounted on wall with fastner and suitable size of nut and bolts etc complete all as specified and directed.
S&F on load change over switch with SS enclosure of capacity 200 Amps , 4 pole , 415 volt , 50 Hz mounted on wall with fastner and suitable size of nut and bolts etc complete all as specified and directed.
OUTGOING (i) MCCB 3 pole , LT 415 Volts, 50 Hz AC grade of 200 Amps rating 36 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 02 Nos. Make of MCCB/MCB-Legrand/Havells/L&T (ii) MCCB 3 pole , LT 415 Volts, 50 Hz AC grade of 63 Amps rating 16 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 04 Nos. Make of MCCB/MCB-Legrand/Havells/L&T
Supply and installing factory made and tested CPRI approved sheet metal enclosure indoor type, platform mounted, suitable for fixing 630 Amps MCCB 3 pole 415 volts , 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 1200 Amps rating installed on porcelain insulators. The enclosure shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron frame work, powder coated finish front and back opening type, with aprons for cable entry from bottom. (Loc :- Substation)
Supply and fix MCCB 3 pole , LT 415 Volts, 50 Hz AC grade of 630 Amps rating 50 KA rupturing capacitiy with adjustable Themal and Meganetic setting releases, - 01 Nos. (Loc :- Substation)
Supplying, laying, jointing testing and connecting of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, IS 7098 marked, suitable for LT 1100 Volt system, laid in trenches fixed to pole, including jointing & testing complete all as specified and directed of following sizes:- Note :- Excavation, earth work ,cable protection , sand fillings , cable joint shall be measured and paid separately under respective items of schedule.
25 Sqmm 4 core
50 Sqmm 3.5 core
240 Sqmm 3.5 core
M & L for Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.1 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as directed. Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 15 mm bore GI pipe light grade etc. (b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
M&L for Galvanised iron strip 32 x6 mm burried in ground.
Demolition of road, path, drain and concrete in ground floors, RCC/Brick wall (below or above ground level) complete all as specified and as directed.
M&L for providing cement concrete 1:2:4 type B-2 (using 40 mm grade crushed stone aggregate) 50 mm Thick complete all as specified and as directed by Engr in charge.
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge
Rajindera Enterprises
mayur enterprises
Commercial Traders
M P TYAGI ENGINEERS AND CONTRACTORS
Vijay Electricals
BB Engineer and Contractor
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .