| 1 | L1₹200.7 CrAccepted-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | L1 | Accepted-AOC L1 Accepted | |
| 2 | L2₹207.2 Cr+₹6.4 Cr (3.21%)Rejected-Finance 201 202 LALA 1 LANDMARK MG ROAD HYDERABAD HYDERABAD | L2 | Rejected-Finance L2 Rejected |
Tender Value
₹200.7 Cr
EMD Value
₹1.0 Cr
Closing Date
11 Oct 2021, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer Central Mumbai pwd ele Worli Mu
Executive Engineer Central Mumbai pwd ele Worli Mumbai
Supplying, Installation, Testing and Commissioning of Complete Electrical Installation including all building services with necessary allied building works for proposed 2 BasementG10 Storey Super Speciality Hospital 1200 Bedded at Sir JJ Group
2021_PWDM_711892_1
Est no.6160/JJH-1/11/21-22
Open Tender
Electrical Works
Item Rate
730 days
JJ subdivision Byculla Mumbai
Please refer Tender documents.
6 documents required · 6 mandatory
₹5,600
₹1.0 Cr
CE(Ele) office Bandhakam Bhavan
17 Nov 2022
10 Aug 2021
14 Oct 2021
10 Aug 2021
11 Oct 2021
10 Aug 2021
15 Sept 2021
120 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, erecting and commissioning of diesel generating set with alternator of 2000 kVA input continuous rating, 3 phase, 415 V, 50c/s 0.8 p. f. A.C a totally enclosed air cooled / liquid cooled multi-cylinder diesel engine developing suitable BHP at 1500 rpm with 10% overload for 1 hour in 12 hours, along with standard accessories, self-excited, self-regulated, screen protected alternator with static excitation system running at 1500 RPM as per IS 4722- 2001 with voltage regulation +/- 5 %. Both the engine and alternator direct coupled on a common fabricated steel base frame and mounted on anti-vibrating pads with standard control panel comprising of meters, switchgears, indicators connected with suitable wires/cables, the complete set enclosed in composite acoustic enclosure as fully assembled integral unit made of 16 SWG CRCA Sheet, sound absorbing material to restrict sound level upto 75 dB at 1.0 m, provided with first filling of oil, diesel day tank, exaust piping with support upto the terrace, control cabling etc. and obtaining necessary approval from Electrical inspector / MPCB as per specification.As per specification no. GEN-DG | 6 | Each | - | - |
| 2 | DG SYNCHRONIZING PANEL-1 (FORM4, TYPE6)
I/C 3200A, 4P, 50kA, EDO, LSIG ACB - 3 No
9000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 50kA. MCCB - 2 No
O/G 800A, 4P, 50kA, EDO, LSIG ACB - 8 No
O/G 1600A, 4P, 50kA, EDO, LSIG ACB - 1 No
O/G 3200A, 4P, 50kA, EDO, LSIG ACB - 3 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital voltmeter, Digital Ammeter, Digital MFM compatible for BMS control, CT for metering, CT for Sync Relay, control wiring, Under Voltage relay, Phase Sequence relay, Negative Phase protection Relay, reverse power relay, Over & under frequency relay, MP BASED GENERATOR CONTROL / SYNC RELAY, DC Voltmeter, DC Ammeter, AC power contractor, ON indicator lamp, Off indicator lamp, Push button, TNC switch, AM Switch, Digital Hooter, Annunciation window, Generator Master trip relay, Line voltage minitor, Battery changer.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
All incomer and outgoing shall be with automatic change over scheme, electrical & mechanical interlocking, auto/Manual on & off of DG Sets, breakers etc.
Synchronizing Relay like Woodward/Dief/Deepsea/PCCM or equivalent shall be provided for each DG set. Selection of Master DG Sets, operation(Opening/closing) of breakers as required and complete with interfacing with DG Set Controller 8 Channel temperature scanner for monitoring bearing and winding temperature, 16 window facia annunciator, Auto - manual selector switch for individual breaker & PLC. (Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 3 | DG SYNCHRONIZING PANEL-2 (FORM4, TYPE6)
I/C 3200A, 4P, 50kA, EDO, LSIG ACB - 3 No
9000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 50kA. MCCB - 2 No
O/G 800A, 4P, 50kA, EDO, LSIG ACB - 6 No
O/G 1000A, 4P, 50kA, EDO, LSIG ACB - 3 No
O/G 1250 4P, 50kA, EDO, LSIG ACB - 1 No
O/G 1600A 4P, 50kA, EDO, LSIG ACB - 3 No
O/G 3200A, 4P, 50kA, EDO, LSIG ACB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital voltmeter, Digital Ammeter, Digital MFM compatible for BMS control, CT for metering, CT for Sync Relay, control wiring, Under Voltage relay, Phase Sequence relay, Negative Phase protection Relay, reverse power relay, Over & under frequency relay, MP BASED GENERATOR CONTROL / SYNC RELAY, DC Voltmeter, DC Ammeter, AC power contractor, ON indicator lamp, Off indicator lamp, Push button, TNC switch, AM Switch, Digital Hooter, Annunciation window, Generator Master trip relay, Line voltage minitor, Battery changer.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
All incomer and outgoing shall be with automatic change over scheme, electrical & mechanical interlocking, auto/Manual on & off of DG Sets, breakers etc.
Synchronizing Relay like Woodward/Dief/Deepsea/PCCM or equivalent shall be provided for each DG set. Selection of Master DG Sets, operation(Opening/closing) of breakers as required and complete with interfacing with DG Set Controller 8 Channel temperature scanner for monitoring bearing and winding temperature, 16 window facia annunciator, Auto - manual selector switch for individual breaker & PLC. (Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 4 | Supply, Installation, Testing & Commissioning of METER-1 PANEL (FORM4, TYPE6), METER-2 PANEL (FORM4, TYPE6), METER-4 PANEL (FORM4, TYPE6) each with
I/C 800A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
1000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 36kA. MCCB - 4 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 3 | EACH | - | - |
| 5 | Supply, Installation, Testing & Commissioning of METER-3 PANEL (FORM4, TYPE6) each with
I/C 800A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
1000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 36kA. MCCB - 4 No
O/G 100A, FP, MP, 36kA. MCCB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 6 | Supply, Installation, Testing & Commissioning of METER-5 PANEL (FORM4, TYPE6) each with
I/C 800A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
1000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 36kA. MCCB - 2 No
O/G 160A, FP, MP, 36kA. MCCB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 7 | Supply, Installation, Testing & Commissioning of METER-6 PANEL (FORM4, TYPE6) each with
I/C 800A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
1000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 36kA. MCCB - 3 No
O/G 250A, FP, MP, 36kA. MCCB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 8 | Supply, Installation, Testing & Commissioning of METER-7 PANEL (FORM4, TYPE6) each with
I/C 3200A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
4000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 3200A, 4P, 36kA, EDO, LSIG ACB - 2 No
O/G 1600A, 4P, 36kA, EDO, LSIG ACB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 9 | Supply, Installation, Testing & Commissioning of METER-8 PANEL (FORM4, TYPE6) each with
I/C 800A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
1000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 400A, FP, MP, 36kA. MCCB - 3 No
O/G 100A, FP, MP, 36kA. MCCB - 2 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring.
(Refer Schedule B in DTP for Detailed Item Description) | 1 | EACH | - | - |
| 10 | Supply, Installation, Testing & Commissioning of METER-9 PANEL (FORM4, TYPE6) each with
I/C 1600A, 4P, 36kA, EDO, LSIG ACB - 2 No with Electrical & Mechanical Interlocking
2000A 4P AL BUSBAR. BUSBAR SHALL BE TIN PLATED WITH SILVER CONTACTS.
O/G 800A, 4P, 36kA, EDO, LSIG ACB - 2 No
O/G 630A, FP, MP, 36kA. MCCB - 1 No
O/G 400A, FP, MP, 36kA. MCCB - 1 No
All incomer shall have SPD Class 1+2 with 100A 4P MCCB , RYB phase indicator lamp with MCB, on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring, CT for APFC panel, CT for DG Sync panel.
All outgoing shall have on / off / trip indicator lamp, Digital MFM compatible for BMS control, CT for metering, control wiring. | 1 | EACH | - | - |
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
BOQ_1229795.xls
BOQ Document • 2.04 MB
81625259.pdf
Tender Document • 0.27 MB
NIC.pdf
Tender Document • 0.25 MB
6160dtp.pdf
Tender Document • 12.20 MB
81625262.html
Tender Document • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .