| 1 | L1₹18.1 LAccepted-AOC NO 235 PSK ILLAM SANKARAN NAGAR CHINNAMMAN KOIL STREET AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹20.4 L+₹1.3 L (6.88%)Rejected-AOC NO 229 ANGAPPAN STREET MITTANAMALAI AVADI IAF CHENNAI 600 055 | CHENNAI | CHENNAI | TAMIL NADU | 600055 | L2 | Rejected-AOC Not being L1 |
Tender Value
Refer Docs
EMD Value
₹43,000
Closing Date
2 Jan 2023, 6:00 pmClosed
Garrison Engineer, Avadi
Garrison Engineer, Muthapudupet, Avadi, Chennai-55
REPAIR/ REPLACEMENT OF INTERNAL AND EXTERNAL ELECTRIFICATION AND REPAIR/ MAINT OF AIR CONDITIONERS, WATER COOLERS AT DQA(CV), CQA (HV), CQA (AVA), CQA(AVL) AND DGQA GUEST HOUSE UNDER GE AVADI
2022_MES_565525_1
8963
Open Tender
Civil Works
Item Rate
270 days
Garrison Engineer, Muthapudupet, Avadi, Chennai
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Garrison Engineer, Avadi
₹43,000
Yes
6 Feb 2023
26 Nov 2022
10 Jan 2023
26 Nov 2022
2 Jan 2023
12 Dec 2022
Amount
Taking down carefully old point wirings with PVC aluminium conductors cables in PVC / Steel conduits/ TW Batten complete ( for light , fan, sockets or power ) removing materials from site , taken as credit , and making good the disturbed surfaces , all as specified and as directed.
M & L for point wiring with 1.5 Sqmm (nominal area) PVC insulated,FRLSH unsheathed, multistrand, 1100 volts grade copper conductor cable single core, drawn through with and including non metallic PVC conduit 25mm dia and its accessories fixed on wall/ ceiling/ trusses /steel structure with suitable clamps , screws etc including one run of 1.5 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing, 1.6 mm thick MS terminal box finished to wall/steel structure with 3 mm thick laminated hylam sheet top cover all as specified for :-
One light point controlled by one switch
One switch socket outlet 3 pin 5 Amps on independent board.
M & L for pointing wiring with 4 Sqmm (nominal area) PVC insulated,FRLSH unsheathed, multistrand, 1100 volts grade copper conductor cable single core, drawn through with and including non metallic PVC conduit 25mm dia and its accessories fixed on wall/ ceiling/ trusses /steel structure with suitable clamps , screws etc including one run of 4 Sqmm PVC insulated copper conductor cable green in colour for continuous earthing, 1.6 mm thick MS terminal box finished to wall steel structure and with 3 mm thick laminated hylam sheet top cover all as specified for One 5 pin 5/15 amps socket point on independent board complete all as specified
S&F switch piano, flush type single pole, one way 6 Amps complete all as specified.
S&F switch socket outlet 2 in 1, 3 pin, 6 Amps flush type multi pin , flush type,complete all as specified.
S&F switch socket outlet 2 pin 1,3 pin 6 and 16 amps , multi pin , flush type,complete all as specified.
S&F electronic dimmers,450w,250V flush type complete all as specified.
Supply and Fixing Modular switch 1 way 6A, 1 module complete all as specified.
Supply and Fixing Modular Bell push 6A, 1 module complete all as specified.
Supply and Fixing Modular switch 1 way16A, 1 module complete all as specified.
Supply and Fixing Modular Socket, 6A - 2/3 pin combined 2 module complete all as specified.
Supply and Fixing Modular Socket, 6A/16A - 2/3 pin combined 2 module complete all as specified.
Supply and Fixing Modular fan step regulator , 120w, 2 module complete all as specified.
Supply and fixing MCB single pole 5-40 Amps, 230V complete all as specified.
Supply and fixing MCB SPN 40Amps, 230V complete all as specified.
Supply and fix Isolator triple pole 40A including taking down old fittingscomplete all as specified.
Supply and fix Isolator four pole 63A including taking down old fittings complete all as specified.
Supply and fix Isolator four pole 100A including taking down old fittings complete all as specified.
S&F Bell , ding-dong type , AC, 215 volts, 50 HZ including taking down old fittings complete all as specified.
Supply and fix Recess mounting LED edgelit ultra slim ceiling light 2X2 environmental friendly new generation aesthetically designed ultra modern recess mounting luminaire with high brightness SMD LEDs as light source, LED edge-lit luminaire suitable for armstrong/grid ceiling complete for low ceiling applications 36 Watt LED (2'X2') complete with electronic driver, suitable for operation on AC, single phase , 220/230V , 50 Hz , including provision of twin core 2.5 Sq.mm copper conductor PVC insulated , 1100 Volts grade cables not more than 5 m long and connecting up ceiling rose and fittings and testing , including taking down old fittings all as specified and as directed. Make :- Crompton Vector:- VI1LCTLRF-6-36 TL, Luker IRISIP651KM2240IP65, Havells STARTO2x2LR36WLED830MOI
Supply and fix Surface mounting LED ceiling light capacity 36W,CRCA powder coating housing with anti-glare diffuser,deep back lit type surface mounting LED luminaire (1' X 4') complete with electronic driver, suitable for operation on AC, single phase , 220/230V , 50 Hz , including provision of twin core 2.5 Sq.mm copper conductor PVC insulated , 1100 Volts grade cables not more than 5 m long and connecting up ceiling rose and fittings and testing , including taking down old fittings all as specified and as directed. Make :- Crompton SPAN LCTLRNE-40-TL (1x4), Luker 60W LT126OR 4 feet tube with reflecto, Havells PLUTONEO4x1PLR36WLED840S
S&F Surface and wall mounted LED tube light fitting, 36 W, batten type, extruded aluminium housing provided for efficient heat dissipation with polycarbonate diffuser and integrated electronic driver complete with all accessories , suitable for operation on AC, single phase 220 / 230 Volts , 50 Hz supply, and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting complete all as specified and as directed. Make :- Crompton CCS-100-40-65-SL-DP-NWH, Luker 36WLTH36WHWW, Havells LUMILINESMART36WLED865PCWH
Supply and fix LED square surface mounted LED panel, PDC aluminium housing and high translucent frosted plastic diffuser complete with electronic driver and LED tube suitable for AC single phase, 230V, 50Hz, including provision of three core flexible copper conductor PVC insulated 1100V grade cable connecting up ceiling rose to fitting terminal end and testing including taking down old fittings complete all as specified and as directed. Make :- Crompton LCDSP1N-S-18-NW, Luker 18WLNPSRS18, Havells PLUTO1X1PLS18WLED8575
Supply and fix surface and wall mounted Emergency energy saving LED tube light fitting , 20 W with back up supply 3 to 4 hrs, battern type, polycorbonate housing provided for efficient heat dissipation with polycorbonate diffuser and integrated electronic driver complete with all accessories, suitable for operation on AC, single phase 220 / 230 V, 50 Hz, including taking down old fittings complete all as specified and as directed. Make:- Luker 20WLTGT520WH or equivalent in Crompton/ Havells.
Supply and fix unserviceable 20W LED Class T8 tube with inbuilt driver and efficacy of 100 lumens/W including taking down old fittings complete all as specified and as directed. Make:- Crompto 1GT8-20-865-2, Luker LT1818T 18W, Havells- PHOTONULTRAE2,01213T855TL2WLED8655PC
Supply and fix single pole and neutral sheet metal enclosure with a two pin and earth plug and socket including taking down existing one complete with one 20 Amps double pole MCB.
Taking down the repair ceiling/exhaust/wall mounted/Air circulator fan of any size/ make including servicing / greasing/ oiling/ repairs and replacing the spares such as cater pin unserviceable/rusted nut bolts, split pins rubber wheel bearing washers, bush and bearings all as specified and as directed
Material and Labour for painting of ceiling fans of any sweep to obtain even, smooth & glossy finish, with synthetic enamel paint of approved colour by using paint spraying devices after filling cavities with filler after cleaning all dust etc., over fan surfaces; complete including writing SM/MES No. in synthetic enamel paint (Black colour) over the same surface where the existing No. was written etc., all as specified and as directed.
Material and Labour for rewinding of fan motor with super enameled copper winding wire of same gauge and weight after cutting and removing the existing burnt/heated up windings, including cleaning of rotor, stator and varnishing, heating and providing fresh insulating materials for Ceiling fan of 1200/1400 mm sweep including dismantling and reassembling.
All as per Item No. 29 herein before but for Exhaust fan 225 to 300mm sweep.
S&F in replacement of old/unserviceable capacitor of capacity 2.5 µfd for the fans in position as directed.
S&F in replacement of old/unserviceable capacitor of capacity 4 µfd for the fans in position as directed.
Supply and fix replacement of PVC canopy/Ceiling fan cap with fixing screws etc suitable for ceiling fan 1200/1400mm sweep etc., complete; all as specified and as directed.
Supply and fix replacement of ceiling fan blade with fixing accesories etc suitable for ceiling fan 1200/1400mm sweep etc., complete all as specified and as directed.
Supply and fix replacement of exhuast fan blade (metal body) with fixing accessories etc suitable for exhaust fan 300mm sweep etc., complete all as specified and as directed
Supply and fix replacement of exhuast fan louver (shutter) metal body with fixing accessories etc suitable for exhaust fan 300mm sweep etc., complete all as specified and as directed
Solar water heater 300LPH capacity maintenance, cleaning the solar panels and solar tubes, including replaced with minor spares such as washers, thermostat,& heating element
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out soft / loose soil for laying cables / pipes / erection of poles etc all as specified and as directed.
Removing excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as specified and as directed.
Returning, filling in, with soil obtained from excavation including spreading leveling watering well ramming in layers not exceeding 25 cm each all as specified and as directed.
Laying in trenches Fine seived excavated dry soil including spreading / leveling, cushioning for underground cables all as specified and as directed.
Supply and laying of common burnt clay building bricks, sub class B of size 230x115x75mm for cable protection all as specified and as directed.
Material and labour for XLPE insulated, armoured, heavy duty electric cable with aluminum conductor, 1100 volts grade, 3.5 / 4 of the following sizes cross-sectionl area including taking down of old unserviceable cable complete all as specified and as directed:- Note : Earth work including excavation ,returning Filling,removing,soil coushioning,brick covering for mechanical protection of cable etc will be measured and paid separately under respective items of schedule.
25 sq mm 4 core
70 sq mm 3.5 Core
185 sq mm 3.5 Core
Material and Labour for servicing of two pole structure including checking/ tightening/making free for operating of AB Switches, insulators, lightning arresters, changing of nut/bolts if required including painting of RYB paint/tape at strip including preparation of old painted surfaces ,removing dust and other deposited materials by scraping from HT pole of 11 Mtr long, painting of pole with one coat of black paint upto 1 Mtr from bottom and painting the rest of the pole including cross arms cable protection pipe clamps, bracket with one coat of aluminium paints complete all as specified and as directed.
Filtration of transformer oil of transformers step down 11 KV / 0-433 V indoor/outdoor type upto 500 KVA capacity installed at different sub stations/locations using filtration and heating equipment at site by re-circulating transformer oil heating, dehydration and improving di-electric strength of the oil to withstand 40 KV for one minute including testing of oil complete all as specified and as directed. Note: Transformer oil test kit shall be provided by the contractor at site for testing of oil.
Supply and filling Silica Gel from transformer breather of any type / model / capacity including taking down old unserviceable one complete all as specified and as directed.
Supply and filling/topping up new transformer oil conforming to IS Specification for transformer upto 500 KVAcapacity installed at various sub stations.
Material and Labour for painting outer surfaces of transformers of capacity above 100KVA, any type / make / model, pole or plinth mounted, installed at various sub stations with one coat of synthetic enamel paint of approved colour, after cleaning all surfaces including writing by paint SM / MES numbers, capacity, make, date of oil testing etc., complete all as specified and as directed.
Service charges for carrying out servicing and overhauling of under mentioned capacities HT VCB by drawing out the draw-out module of the breaker, carrying out complete cleaning with clean cloth & cleaning agent, lubrication of the mechanism & greasing with high temperature molly grease, testing for smoother ON/OFF operation, carrying out relay calibration of protection relay by secondary current injection methods to check trip time characteristic of relays, checking of healthiness of CTs & Pts. Checking of IR value of Interrupters, healthiness of Protection Tripping of Circuit breaker etc. Choking and servicing switchgear Interlocks and Safety Like Mechanical - 1. Positive Interlock, 2.Negative Interlock, 3. Spring Discharge Interlock, 4. Padlocks, 5. Key Interlocking 6. Safety Roll in Stop, 7. Safety Roll - out Stop,8. Rating Interference Interlock. Electrical - Interlock Switches) Checking of Electrical operations of the breaker for ON/OFF & Trip operation for Incomer and Outgoing including submission of service & test reports. Make: Crompton Greaves. Note: The servicing should be done by authorised service provider of manufacturer.
Vacum circuit breaker (VCB) 630 Amps to 1000 Amps
Taking down the old unserviceable lead acid battery, and supply and fix new lead acid battery of capacity 2V,100AH, model YRLA for sub station VCB all as specified and directed
Service charges for carrying out complete servincing of AB Switch by lubrication of the mechanism & greasing with petroleum jelly complete all as specified and as directed. Note: Minimum spares /lubricants and tools required for the job should be included in the coated rates.
Supply and laying Synthetic rubber insulated mat 2.5 mm thick for voltage 11 KV for electrical purpose as per IS 15652-2006 suitable for electrical shock safety of size 2mtrx1mtr including taking down old unserviceable one complete all as specified and as directed.
Supply and spreading Hard core of gauge broken stone or boulders not exceeding 63mm, deposited, spread and levelled in layers not exceeding 15cm thick watered and rammed to a true surfaces using broken stones etc complete all as specified and as directed.
Supply and fixing Horn Gap type Fuse unit, 11000 volts grade, mounted on polymer insulators and steel frame, single pole, fixed on DP structures including taking down old unserviceable one complete all as specified and as directed.
Material and labour for Loop type insulator (for stay assembly vitreous porcelain white, brown or green large size with over all dimentions 90mmx140mm clearance of hole 16 mm including taking down old unserviceable one complete all as specified and as directed.
Material and labour for Shackle type porcelain vitreous white, brown or green insulator in replacement having working pressure 11000 Volts of 150mm dia 150mm height including galvanized mild steel strip of size 38x5mm ,size 20mm dia insulator nuts, bolt and washers including taking down old unserviceable one complete all as specified and as directed.
Material and labour for Pin type porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000 Volts grade including taking down old unserviceable one complete all as specified and as directed.
Earthing complete with galvanised steel earth plate eletrode 60xm x 60cm x6 mm thick buried directly in ground (earth plate not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised iron earth strips 25x4mm by means of bolts, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregates with 40mm thick cover of RCC (1:2:4) reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x6mm and handle of 6mm dia MS bar made to shape, GI light grade 20mm bore pipe for watering of suitable length placed on top edge of earth plate, charcoal and common salt filling, with fixing arrangement, funnel, wire mesh and earth work in soft/loose soil, returning filling in and removal of surplus soil to a distance not exceeding 50 meterrs, complete all as per plate No-3, SSR-2009 Part-I and connecting to existing earth test point all as specified or indicated including testing on completion.
Material and Labour for preparation of old painted surfaces ,removing dust and other deposited materials by scraping from street light tubular pole of 7.5 Mtr long above ground level , painting of pole with one coat of black paint upto 1 Mtr from bottom and painting the rest of the pole with one coat of aluminium paint including cross arms cable protection pipe clamps etc , including writing the MES No with white paint over black band of paint at a level of 1.2 m above ground level on each pole complete all as specified and as directed.
Material and Labour for MCCB 160 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 36 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 36 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
Material and Labour for MCCB 125 amp ,4 pole 415 volts ,3 phase ,50 Hz AC with adjustable thermal setting & 16 KA breaking capacity with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993(Latest Version). The MCCB should have Ics= 75% Icu for short circuit breaking capacity of minimum 16 KA rms at 415 volts 50 Hz AC. The MCCBs shall have spreader links and barriers as standard feature of manufacturer including taking down old unserviceable one complete all as specified and as directed.
All as per item No 63 above but 100 amps capacity MCCB
All as per item No 63 above but 63 amps capacity MCCB
All as per item No 63 above but 40 amps capacity MCCB
Material and labour for LED Driver, AC, 85 to 265 Volts range, suitable for 35 watts street light including taking down the old one complete all as specified and as directed.
Supply and Fixing of LED street light fitting,230 V,AC, 35 W, LED, outdoor type,CCT not less 6000K high pressure die cast aluminium housing ,heat resistance toughened glass with frame IP 65/ 66 protection LED lumen efficacy not less then 120 lumen/watt, reflector lenses for uniform light distribution on each LED with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete fixed on existing / New bracket and making connections including taking down the old one complete all as specified and as directed . Make: Surya Cat part No: Pollux XL SLEUL60WIP66PLX XL, Bajaj Cat Part No: EDGE NXT LED ENXT P 60L WW CR PC SD, Crompton Product No: RAPTOR PRO-I CRP-409-60-57-SL-GL-NSG or Equvalent.
Supply and fixing post top lantern LED type 20W, 230V, AC out door type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete, including taking the old unserviceable fitting all as specified and as directed.
S&F Automatic street light timer switch three phase 5KW, 440V asper Swadeep make - 02EC 5KW 3P model as a pole mountable MS box enclosure consisting of Nature switch-02 as the controlling unit, Power Contactor & MCBs 20Amps (both Input-Output) of suitable power rating and copper wiring (min 10 sqmm) with proper lugs & terminal blocks, The SMC enclosure comes complete with openable door and mounting clamps, The MS box enclosure comes complete with openable door and mounting clamps, The MS box enclosure outdoor mountable confirming to IP54. Make :- Nature switch, Model Name/Number :- Swadeep 02EC5KW3P or equivalent
Supply and Fixing of pole mounted Sheet Moulded Compound(SMC) Box weather proof type with hinged type door off white color of size 250x250x155 mm comprising of 1 No MCB 6A and suitable size Aluminium busbar 3 rows with terminals,1 No bakelite base neutral link and 01 No earthing terminal bolt and nut and connecting up cables with aluminium terminal lugs complete fixed on pole with suitable clamps, bolts and nuts including taking down the old one complete all as specified and as directed.
Testing the leakage in system, arresting the leak by vacumising the system, dehydration and charging the refrigerent R-22 /R-32 in to the system including replacement of strainer and capillary tube made out of copper complete suitable for 1.5 Ton Window Air conditioner all as specified and as directed.
Testing the leakage in system, arresting the leak by vacumising the system, dehydration and charging the refrigerent R-22 /R-32 in to the system including replacement of strainer and capillary tube made out of copper complete suitable for 1.5 Ton Split Air conditioner all as specified and as directed.
Taking down the existing unserviceable compressor sealed unit by disconnecting the incoming / out going refrigerant lines and taken on credit and replacing with new compressor sealed unit, reconnecting refrigerant lines, detection of leakage and arresting the same by welding / brazing, flushing vacuuming and charging with gas of required quantity, after dehydration as per standard practice, compressor suitable for Split type AC, 1.5 ton capacity of any make / model complete all as specified and as directed.
All as per the item 3 above but 1.5Ton capacity Window Air conditioner
Taking down the existing unserviceble Condenser coil and taken on credit and replacing with new Condenser coil suitable for Split AC,1.5ton capacity of any make / model complete all as specified and as directed.
Taking down the existing unserviceble Cooling coil and taken on credit and replacing with new Cooling coil suitable for Split AC,1.5ton capacity of any make / model complete all as specified and as directed.
Taking down the existing unserviceble Condenser coil and taken on credit and replacing with new Condenser coil suitable for Window AC,1.5ton capacity of any make / model complete all as specified and as directed.
Taking down the existing unserviceble Cooling coil and taken on credit and replacing with new Cooling coil suitable for Window AC,1.5ton capacity of any make / model complete all as specified and as directed.
Removing and pump down the split AC of cap 1.5 Ton and refixing including shifting the same all as specified and as directed.
Taking down the existing unserviceble indoor unit fan motor and taken on credit and replacing with new indoor unit fan motor suitable for Split AC,1.5ton capacity of any make / model complete all as specified and as directed.
Taking down the existing unserviceble outdoor unit fan motor and taken on credit and replacing with new outdoor unit fan motor suitable for Split AC,1.5ton capacity of any make / model complete all as specified and as directed.
Dismandling and taking down unserviceable fan motor, Supply and fix new fan motor for 1.5 Ton window AC all as specified and as directed.
Taking down the existing window type AC, 1.5 ton capacity of any make / model from its position and cleaning the AC externally and servicing the AC including cleaning of condensor, filter, cooling coil, base bottom and fins, with soap water, checking of electrical wiring, ensure smooth functioning and re-install and reconnect the AC unit in its exising location after proper cleaning of the place and testing and commissioning complete all as specified and as directed.
Servicing the split type AC, any capacity of any make / model cleaning the AC externally and servicing the AC including cleaning of condensor coil without removing the outdoor unit,and filter, cooling coil base bottom and fins,with soap water, checking of electrical wiring, after proper cleaning of the AC and testing and commissioning complete all as specified and as directed.
S&F in replacement PCB suitable for 1.5 Ton AC as per site requirement all as directed
S& F in replacement of copper tubing set 1/4" and 1/2" suitable for Split AC incl PUF insulation and connected accessories complete all as directed
Supply and fix in replacement starting relay suitable for 1.5Ton A/C all as directed.
Supply and fix in replacement wiring kit suitable for 1.5 Ton A/C all as directed
Supply and fix in replacement running capacitor 36mfd 230/415 Volt all as directed .
All as per item No. 96 but 50 mfd 230/415 all as directed
Supply and fixi in replacement starting capacitor 80/100mfd 230/415 Volt
S&F Pvc drain pipe size 15mm / 20mm suitable for A C all as directed
S&F PUF insulation for copper tubing suitable for split AC all as directed
Supply and filling refrigerent R-22, suitable for Window AC/water cooler of any type all as directed
Supply and filling refrigerent R-32 suitable for Split AC/water cooler of any type all as directed
Taking down the existing unserviceble Over load Protector and taken on credit and replacing with new Over load Protector suitable for Window AC / Split AC,1.5 ton capacity of any make / model complete all as specified and as directed.
Taking down the existing unserviceble Thermostat switch and taken on credit and replacing with new Thermostat switch suitable for Window AC / Split AC,1.5ton capacity of any make / model complete all as specified and as directed.
Supply and fix unserviceable Remote control sensor and digital device complete set with remote suitable for split type AC, any capacity.
Supply and fix unserviceable Air filter suitable for window / Split type AC, 1.5 ton capacity.
Supply and fix unserviceable Front grill suitable for window type AC, 1.5 ton capacity.
Supply and fix unserviceable Oscillating motor / device to change direction of air flow suitable for split type AC, any capacity.
Supply and fix unserviceable Magnetic coil suitable for split type AC, any capacity.
Taking down the existing unserviceble GI bracket including all accessories and taken on credit and replacing with new GI bracket including all accessories suitable to fix out door unit of split type AC, of any make / model complete all as specified and as directed
Taking down the existing unserviceable compressor sealed unit by disconnecting the incoming / out going refrigerant lines and taken on credit and replacing with new compressor sealed unit, reconnecting refrigerant lines, detection of leakage and arresting the same by welding / brazing, flushing vacuuming and charging with gas of required quantity, after dehydration as per standard practice, compressor suitable for water cooler of capacity 80 ltrs any make / model complete all as specified and as directed.
All as per item No. 111 above but suitable for 120 ltr cap water cooler
All as per item No. 111 above but suitable for 150 ltr cap, water cooler.
Taking down the existing unserviceble copper condenser coil and taken on credit and replacing with new opper condenser coil cap 80 ltrs water cooler of any make / model complete all as specified and as directed.
All as per item No. 114 above but suitable for 120 ltr cap water cooler.
All as per item No. 114 above but suitable for 150 ltr cap, water cooler.
Taking down the existing unserviceble condenser fan motor and taken on credit and replacing with new condenser fan motor any cap water cooler of any make / model complete all as specified and as directed.
Cutting the suction / discharge tubes of the compressor line and Flushing, vacuuming and charging of water cooler of any make / model with refrigerant gas, after dehydration as per standard practice, including detection of leaks and arresting the same by welding / brazing complete of capacity 80 ltrs water cooler all as specified and as directed.
All as per item No. 118 above but suitable for 120 ltr cap water cooler.
All as per item No. 118 above but suitable for 150 ltr cap water cooler.
Taking down the existing unserviceable strainer and capillary tube and taken on credit and replacing with new strainer and capillary tube suitable for water cooler of any make / model / cap complete all as specified and as directed.
Taking down the existing unserviceable PVC water inlet pipe for replacement new PVC pipe, transparent, heavy duty 20mm dia water inlet pipe for water cooler complete all as specified and as directed.
Taking down the existing unserviceable PVC pipe as drain out pipe for replacement new PVC pipe, heavy duty 25mm dia drain out pipe laid on walls / floor for water cooler complete all as specified and as directed.
Supply and fix in replacement Starting Relay suitable for water cooler of any capacity all as directed
S&F in replacement running capacitor cap 30 Mfd suitable for water cooler of any capacity all as directed
S&F in replacement starting capacitor cap 60 to 80 Mfd suitable for water cooler of any capacity all as directed
All as per item No. 126 above but cap of 40 to 60 mfd .
S&F in replacement thermostate switch suitable for water cooler of capacity all as directed.
S&F in replacement OLP suitable for water cooler of any capacity all as directed.
Supply and fix in replacement new fan motor suitable for water cooler any capacity all as directed.
Supply and fix unserviceable chromiam coated brass bip Tap for water cooler 15mm size, straight type
Supply and fix unserviceable chromiam coated brass bip Tap for water cooler 15mm size, angle type with round disc
Supply and fix unserviceable drain tray (stainless Steel) for water cooler of any capacity
Supply and fix unserviceable 15 mm ball valves high pressure of PTMT with epoxy coated aluminium rod and high density plastic ball screwed for iron pipe and fixed and minium weight 142 gms.
Taking down the existing unserviceable compressor sealed unit by disconnecting the incoming / out going refrigerant lines and taken on credit and replacing with new compressor sealed unit, reconnecting refrigerant lines, detection of leakage and arresting the same by welding / brazing, flushing vacuuming and charging with gas of required quantity, after dehydration as per standard practice, compressor suitable for digital inverter refrigerator of any make / model and capacity complete all as specified and as directed.
Cutting the suction / discharge tubes of the compressor line and flushing, vacuuming and charging of refrigerator of any make / model with refrigerant gas (R-12/R-404), after dehydration as per standard practice, including detection of leaks and arresting the same by welding / brazing complete Cap of Refrigerator 180ltrs to 340 ltrs all as specified and as directed.
Taking down the existing unserviceable digital electronic circuit board and taken on credit and replacing with new digital electronic circuit board suitable for digital inverter refrigerator of any make / model and capacity complete all as specified and as directed.
Taking down the existing unserviceable strainer and capillary tube and taken on credit and replacing with new strainer and capillary tube suitable for refrigerator of any capacity any make / model complete all as specified and as directed.
Taking down the following existing spare parts and taken on credit and replacing with new spare parts suitable for refrigerators of any make / any capacity any model complete all as specified and as directed.
Magnetic door gasket suitable for refrigerator of any capacity
Freezer (cooling coil) suitable for refrigerator of any capacity
Freezer door set suitable for refrigerator of any capacity .
Thermostat switch with knob
Relay box type suitable for refrigerator of any capacity .
Relay open type suitable for refrigerator of any capacity .
Timer switch suitable for refrigerator of any capacity .
Blower motor suitable for refrigerator of any capacity .
Running capacitor 4 Mfd suitable for refrigerator.
Door lock with key in duplicte suitable for refrigerator of any capacity .
Pigmy lamp screw / pin type with holder suitable for refrigerator of any capacity .
Ice box tray suitable for refrigerator of any capacity .
Vegetable tray suitable for refrigerator of any capacity .
Bottle tray suitable for refrigerator of any capacity .
Shelves of inner panel suitable for refrigerator of any capacity .
Taking down the following existing spare parts and taken on credit and replacing with new spare parts suitable for voltage stabilizers of capacity 5 kVA / 4 kVA / 3 KVA of any make / model complete all as specified and as directed.
Main transformer
Transistorised electronic relay.
Electronic PC circuit plate having diodes, condensers etc.
High / low voltage cut-off relay
Time delay relay
Output terminal contacts
Socket outlet 5 pin 5 / 15 Amps
Disconnecting and dismantling of RO water purifier of capacity 25 LPH / 50 LPH etc.,and servicing / overhauling, cleaning of sand / carbon / micro filter / membrane filmtech, check water leakage in filters and pipe, re-installing, reconnecting, testing and commissioning for proper and smooth functioning complete all as specified and as directed. Note:- (a) Spares as required shall be measured and paid separately. (b) Taking down the following existing spare parts and taken on credit and replacing with new spare parts suitable for RO plant of capacity 25 LPH / 50 LPH complete all as specified and as directed.
Supply and fix Carbon granules filter
Supply and fix 5-5 membrane and housing assembly .
Supply and fix Pressure pump 48 V
Supply and fix Adaptor 48 V
Supply and fix Carbon black filter.
Supply and fix Micron filter
Material and labour for inspection of EOT crane of capacity 5.0/20 Ton located in CQA(HV) work shop area by the competent person authorised by Inspector of Factories and testing on load for proper function and safety all as per standard testing proceedure laid down and furnishing the test certificate in Triplicate all as specified and as directed. Note: (a) Load materials will be arranged by contractor , including transport. (b) All tools and tackles arranged by the contractor. (c) Necessary test certificate from factory inspector shall be produced by the contractor before making payment.
EOT crane of 5.0 / 20 Ton Capacity Maintenance including attending complaints , servicing , cleaning , greasing and oiling of Electrically operated over head travelling cranes double girder type Electric motor driven for longitudinal traverse, cross traverse, Hoist, microspeed in all motion (LT,CT and Hoist) Electric control panels, gantry rails, rope drum, brake, limit switches and ensure trouble free, smooth operation all as specified and as directed.
Note for BOQ Items No. 171:- (a) The scope of comprehensive maintenance comprises the following read in conjunction with particular specifications here-in-after and rate quoted is deemed to include for the same. (i) The repairs / servicing / maintenance works for EOT cranes including hoist hook universal type and shall be carried out by trained / skilled technicians and shall conform to standard engineering practice / code and as per the standard code / norms of Government and minor repairs. (ii) Attending to any breakdown within 24 hours and restoring the service. (iii) Insurance coverage for all technicians, workers involved in the works. (iv) Record / maintain register of all maintence carried out. (v) Adherence to safety rules and regulations in respect of EOT cranes. (vi) Adherence to security rules and regulations of the DGQA (HVF Estate) area .
(vi) Adherence to security rules and regulations of the DGQA (HVF Estate) area. (vii) A list of makes / brands of spares / materials to be incorporated in the works shall be got approved immediately after receiving the work order. (viii) All tools, instruments and plants required for carrying out the above works shall be provided by the contractor. (ix) All consumables like cotton waste, grease (but excluding wire rope compound, gear box oil, hydraulic gear oil, transformer oil which shall be measured separately) required for the maintenance of the EOT cranes shall be provided by the contractor.
Supply only Wire rope compound for EOT crane.
Supply only gear oil 90 / 140 W suitable for EOT crane.
Supply only Transformer oil 48 KV dielectric strength suitable for EOT crane.
muthu constructions
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .