CWE, HQ 133 WORKS ENGRS
HQ 133 WORKS ENGRS
PROVN OF ELECTRIC SUPPLY AND ALIIED INFRA AT RANI HILLS POST CHOWKIBAL AND PROVN OF TRANSFORMER AND ALLIED INFRA IN AOR OF 28 INF DIV UNDER GE 874 EWS
2022_MES_529579_2
CWEK-13/2022-23
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE 874 EWS
Class B Category b iii
7 documents required · 7 mandatory
₹1,000
GE 874 EWS
₹1.8 L
HQ 133 WORKS ENGRS
14 Oct 2022
23 Aug 2022
24 Sept 2022
23 Aug 2022
17 Sept 2022
3 Sept 2022
23 Aug 2022 - 29 Aug 2022
30 Aug 2022
Amount
Excavation in trenches not exc. 1.5 mtr wide and not exc 1.5 m in depth for laying of underground cable, electric pole, in hard/dense soil and getting out, complete all as specified and directed.
Returning filling, including spreading, leveling , watering and well ramming in layers not exceeding 25 cm in hard/dense soil, complete all as specified and directed.
Removal of excavated material i.e soil to a distance not exc. 50m and depositing where directed at a level not exceeding 1.5 mtr above starting point complete all as specified and directed.
Sand cushioning to underground cables 8 cm below the cable before laying and 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I. Note :- 1. Dry fine sand of best available quality shall be used. 2. Punned thickness shall be measured and paid.
M & L Sub class ‘B brick, old size, brick covering laid dry, flat, transversally along the length of cable on sand cushioning, with width equal to the length of the brick, complete all as specified and directed.
M & L for PCC 1:4:8 Type D-2 (using 40mm graded aggregate) as in foundation of poles, filling and mass concrete complete all as specified and as directed by the Engineer-in-Charge.
M & L for Plain cement concrete 1:3:6, type C-2, (using 40 mm graded crushed stone aggregates) as in copings and the like including weathering, slightly rounded or chamfered angles and throating and including necessary form work complete all as specified and directed.
S & F for 80mm bore `Light grade` GI tubing ISI marked with cutting as required and bend to shape for fixing with electric poles as cable protection fixed on pole or laid in trenches under floor,duct etc with fixing clamps,nuts bolts etc complete all as specified and as directed.
S & F for 50mm bore `Light grade` GI tubing ISI marked with cutting as required and bend to shape for fixing with electric poles as cable protection fixed on pole or laid in trenches under floor,duct etc with fixing clamps,nuts bolts etc complete all as specified and as directed.
S & F for 40mm bore `Light grade` GI tubing ISI marked with cutting as required and bend to shape for fixing with electric poles as cable protection fixed on pole or laid in trenches under floor,duct etc with fixing clamps,nuts bolts etc complete all as specified and as directed.
Supply , installation, testing and commissioning outdoor type, Step down transformer, 33 KV/415 Volts, (at Full load) AC 3 Phase 50 HZ, 400 KVA Capacity core type , double copper wound, oil immersed , naturally cooled, oil natural Air Natural (ON AN) with external cooling tubes, delta connected on primary side (HV) and star connnected on secondary side (LV) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having taping at ±2.5% & ± 5% on HV side to be charged by means of hands operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measurement by resistence method after continuous full load run on an ambient temp of 40 degree celsius.The transformer shall be IS-2026 marked complete all as specified and directed.
Supply and installation of silent Diesel Engine driven generating set suitable for DG Set of Capacity 25 KVA 415 volts, three phase , engine as per IS:10001/ 10002 and Alternator as per IS: 13364 complete with foundation (as per OEM design), control panel with necessary meter and sound proof canopy as per CPCB norms of capacity upto 25 KVA complete all as specified and directed. Note :- Rate Including transportation as both the DGs are to be installed at top of the Rani Hill, Zuneracy and Bump post.
Supply, installation and testing of Voltage stabilizer for automatic operation,three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ±2.5% and speed of correction 8 Volts per second and of capacity 15 KVA Stabilizer complete all as specified and directed by Engr-in-Charge. Note :- Rate Including transportation as both the transforemers are to be installed at top of the Rani Hill, Zuneracy and Bomp post
Supply , installation, testing and commissioning outdoor type, Step down transformer, 11 KV/415 Volts, (at Full load) AC 3 Phase 50 HZ, 250 KVA Capacity core type , double copper wound, oil immersed , naturally cooled, oil natural Air Natural (ON AN) with external cooling tubes, delta connected on primary side (HV) and star connnected on secondary side (LV) in accordance with vector group DYN-11 with neutral brought out on secondary side (LV side) and having taping at ±2.5% & ± 5% on HV side to be charged by means of hands operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measurement by resistence method after continuous full load run on an ambient temp of 40 degree celsius.The transformer shall be IS-2026 marked complete all as specified and directed.
Supply, installation, testing and commissioning of Air-break , gang operated, triple pole switch, outdoor, horizonal mounting type (ISI marked),mechanically operated,mounted on insulators including 200 amp rating complete with fuse mounts,fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level,with locking arrnagments including Godrej pattern 65mm pad locks with two keys,complete suitable for HT 33 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed by Engr-in-Charge.
Supply, installation, testing and commissioning of Air-break , gang operated, triple pole switch, outdoor, horizonal mounting type (ISI marked), mechanically operated, mounted on insulators including 200 amp rating complete with fuse mounts,fuse carriers and HT fuse elements and frame work with operating mechanism worked from ground level,with locking arrnagments including Godrej pattern 65mm pad locks with two keys,complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed by Engr-in-Charge.
Supply and fixing of steel tubular swaged poles erected truly vertical or planted as strut complete with 300x300x6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap,bolts,nuts & screws,poles made out of ERW MS tubing conforming to IS-2713 Part-11 type 410 SP-55 (11.0 metres long) including drilling of holes of reqd size foe fixing of cross arm, painting the exposed surfaces of pole with two coats of aluminium paint over one coat of red oxide zinc chrome primer and with black & bitumenous paint externally for portition embedded in concrete, making five black & red bands at lower portition of pole each 300 mm wide alternately,and making pole NO.with black paint at suitable height complete all specified and directed.
Supply and fixing of steel tubular swaged poles erected truly vertical or planted as strut complete with 300x300x6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap,bolts,nuts & screws,poles made out of ERW MS tubing conforming to IS-2713 Part-11 type 410 SP-31 (9.0 metres long) including drilling of holes of reqd size foe fixing of cross arm, painting the exposed surfaces of pole with two coats of aluminium paint over one coat of red oxide zinc chrome primer and with black & bitumenous paint externally for portition embedded in concrete, making five black & red bands at lower portition of pole each 300 mm wide alternately,and making pole NO.with black paint at suitable height complete all specified and directed.
Supply, installation,testing and commissioning, of AC 33KV Trivector meter in Poly Carbonate Body, Accuracy Class 0.5s as per IS -14697 and ISI-5959 for communication, DLMS compliance with feature of Non Programmable CT at the site. Backlit LCD Display (Measures kWH, kVAH ,V ,I, kW, 6 months history of Energy, Load Survey,TOD, Tamper detection & logging, power on/off Events, Having Galvancially isolated Optical & RS232 Port (As per ISI-5959) suitable to measure instantaneous parameters of Rating - /1A with dispaly in absence of power. Default PT ratio * : 33 KV/110V & CTR : 1. Meter shall be supplied with Meter Box , including necessary connections , Along with any additional accessories required, all specifications duly approved by GE, complete all as specified and directed. Make : HPL/L&T/SECURE
Supply, installation,testing and commissioning, of AC 11KV Trivector meter in Poly Carbonate Body, Accuracy Class 0.5s as per IS -14697 and ISI-5959 for communication, DLMS compliance with feature of Non Programmable CT at the site. Backlit LCD Display (Measures kWH, kVAH ,V ,I, kW, 6 months history of Energy, Load Survey,TOD, Tamper detection & logging, power on/off Events, Having Galvancially isolated Optical & RS232 Port (As per ISI-5959) suitable to measure instantaneous parameters of Rating - /1A with dispaly in absence of power. Default PT ratio * : 11 KV/110V & CTR : 1. Meter shall be supplied with Meter Box , including necessary connections , Along with any additional accessories required, all specifications duly approved by GE, complete all as specified and directed. Make : HPL/L&T/SECURE
Supply, installation, testing and commissioning ,factory made and tested (prototype having been CPRI type test certified),outdoor LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50Hz AC supply system, having bus bar chamber with insulated aluminium bus bar of 300 Amps rating, installed on porcelain insulator.The bus bar should be covered with colour coded (depending on the phase) heat shrink sleeve.The Panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry,with two layers of Sheet Metal cover (should have one set of doors on inside and one set of doors outside) capable of withstanding snow and rain at installation site with maintainance proof design,with double door shutter and locking arrangment (including provn of 65 mm Godrej (Freedom) lock with 2 key, having one chamber with door for each MCCB,having two empty chambers for future use,internal wiring 2.5 Sqmm with PVC insulated,soild copper conductor ,FRLS cables, IS-694 marked of adequate size including the provision of space to accommodation the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/Brick Masonry Trenches/duts of 30cm x 30 cm with sand cushioning till top and RCC/Cast iron lid cover for the trenches. The scope of work includes the followings:-
(a) Incoming (i) On load Panel Mounted 100A Changover,2 input and 1 output - 01 Nos (ii) MCCB 4pole, 415 volts AC grade,100 Amps rating and 36 KA rupturing capacity complete with microprocessor based OL protection - 01 No E15 (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar.The space shall be closed with a bolted door. (b) Outgoing (i) MCCB 4 Pole 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 02 Nos (ii) (From the above MCCBs) MCB SPN 32 A, C curve - 06 (iii) Three Phase Digital Panel Ammeter with three display to display all phase symulteneously - 02 Nos (iv) Indicator lamp RYGB Make Havelles - 01 set (v) Platform for the panel with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate,15cm thick in foundation,brick work in CM 1:6 with sub 'B' old size brick,rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6 type C-1 (using 20mm graded crushed stone aggregate on top and grouting bolts etc for panel.The platform shall be height 45cm above the nearest road/ground/floor level. Note :- (i) All out going feeders shall be connected by cable throught suitable size gland plate/glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supplying and install ON LOAD change over switch 415 V in sheet metal enclosures 3 pole of capacity 40-200 Amp fix on wall complete all as specified and directed.
Supply and fix switch fuse unit TPN 500 Volts, 3 phase with HRC fuses suitable for interior mounting in panel of capacity 40-200 Amp complete all as specified and directed.
S&F RCBO, four pole Three phase and Neutral 420 Volts , 50 H 63 Amps, 30mA complete all as specified and as directed.
S&F Sheet metal enclosure factory made for DBs Triple pole and neutral Single door 415 volts 6 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces all as specified and directed.
S&F Sheet metal enclosure factory made for DBs Triple pole and neutral Single door 415 volts 4 way with 200 Amps rated bus bar fixed on walls, including dressing and connecting both incoming and outgoing cable termination with proper taping, lagging testing and commissioning and making good of wall, surfaces complete all as specified and directed.
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of TPN 40-100 Amp and current carrying capacity in the DB complete with connection testing and commissioning all as specified and directed by Engr-in-Charge.
S&F Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of Single Pole and Neutal (SPN) 40-63 Amp and current carrying capacity in the MCB DB complete with connection testing and commissioning..
LT End termination heat shrinkable type Joint 1100 V Grade suitable for XLPE cable of normal size 4 Core 16 to 50 Sqmm complete all as directed.
M & L for Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 33 KV Voltage grade, complete all as specified and as directed by the Engineer-in-Charge
M & L for Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11 KV Voltage grade, complete all as specified and as directed by the Engineer-in-Charge
M & L for pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut,100mm height 65mm dia for 1100 volts grade, , complete all as specified and as directed.
M & L of shackle type, porcelain (or polymer insulator if required) , vitreous,white brown or green insulators for working pressure in 1100 volts , Height in 75 mm and Max 90 mm dia, Galvanised steel fittings Section of straps in 31 x 3 mm and 12 mm dia of bolts, complete all as specified and directed.
M & L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts and washer made out of 25x3mm flat iron for LT/HT poles /transformer/ pillar box etc with voltage and danger indicated in Hindi and English for HT,25X20cm size, , complete all as specified and as directed by the Engineer-in-Charge
M & L for Aluminium Conductor Steel Reinforced, of 6/1/3.0 mm (Ferret) , including stretching, fixing and binding to insulator on OH/LT line service feeders with aluminium binding wire or aluminium tapes which shall not be included in weight of conductor, complete all as specified and directed.
M & L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive two coat of aluminium paint over one coat of red oxide primer, complete all as specified and directed.
M & L for stay assembly complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately), Diameter of stay rod in 20 mm, complete all as specified and as directed.
M & L for XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 33000 volts, Earthed grade cross sectional area 120 sq mm, 3 core, ISI marked complete all as specified and as directed.
M & L for XLPE insulated , screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts, Earthed grade cross sectional area 70 sq mm, 3 core,ISI marked complete all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 3.5 Core 240 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 3.5 Core 185 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 3.5 Core 150 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 3.5 Core 70 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 3.5 Core 50 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 4 Core 25 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 4 Core 16 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 2 Core 10 Sqmm, ISI marked complete, all as specified and as directed.
Supply and laying in cable, XLPE insulated , armoured electric cable (heavy duty) 1100 Volts grade laid in trenches,passing throught pipes,fixed on walls complete with stranded aluminium conductor of size 2 Core 6 Sqmm, ISI marked complete, all as specified and as directed.
M & L for Cable Jointing Kit for 33 KV (Earthed) Grade cable for Outdoor termination, Heat shrink type, joint complete with jointing material and accessories suitable for 3 Core XLPE Armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified and directed.
M & L for Cable Jointing Kit for 11 KV (Earthed) Grade cable for Outdoor termination, Heat shrink type, joint complete with jointing material and accessories suitable for 3 Core XLPE Armoured aluminium conductor cable of size 50 Sqmm to 95 Sqmm complete all as specified and directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60x60cmx 6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate,with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4,funnel with wire gauge of (0.68) 8 mesh per liner inch,80mm thick RCC pit cover 320 mmx320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM,JALLI and charcoal dust and common salt all as shown in electrical plate No.3 of MES SSR Part-1 and specified including provision of earth wire protected by 40 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore medium graded GI pipe,and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/LT panel etc.and testing on completeion complete all as spec ified and directed. NOTE: The quoted rate of earthing shall be deemed to included cost of 7.5m long galvanised earth strip 32x6 mm and protection pipe of 40 mm bore medium graded ,GI light graded 20mm bore watering pipe
M & L for Earthing complete with galvanised steel earth plate electrode 60x60cmx 6.0mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 25x4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate,with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4,funnel with wire gauge of (0.68) 8 mesh per liner inch,80mm thick RCC pit cover 320 mmx320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM,JALLI and charcoal dust and common salt all as shown in electrical plate No.3 of MES SSR Part-1 and specified including provision of earth wire protected by 40 mm dia medium grade GI pipe and watering pipe shall be 20 mm bore medium graded GI pipe,and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/LT panel etc.and testing on completeion complete all as spec ified and directed. NOTE: The quoted rate of earthing shall be deemed to included cost of 7.5m long galvanised earth strip 25x4 mm and protection pipe of 40 mm bore medium graded ,GI light graded 20mm bore watering pipe
Earthing complete with galvanised earth plate electrode 600mm x 600mmx 6mm thick buried directly in ground vertically ( earth pit of depth not less than 2.25m below ground level ) with top edge of the earth plate not less than 1.5m below normal ground level, connecting with 4.00 mm galvanized steel wire earth lead by means of bolts, nuts, checks nut and washers made out of galvanized iron and earth wire protected by galvanized steel pipe 15mm dia (light grade) including provn of concrete pit in PCC 1:2:4 type B-1 (using 20 mm graded mechanically crushed stone aggregate), 40mm thick RCC cover slab 1:2:4 tpye B1 reinforced with XPM ( weight not less than 4kg/sqm ) and frame made of angle iron of section 40x40x6mm with lugs, 02 Nos handle of 6mm dia mild steel bar made to shape, 20mm dia GI pipe (light grade) for watering perforated at bottom 1.75m long placed on top edge of earth plate, charcoal and salt filling in alternate layer, test point made out of phopsphorus/ Bronze with fixing arrangement , funnel wire mesh and earth work in soft/loose soil, returning filling, removal of surplus soil all as shown in electrical plate No.3 of SSR Part-I and connection to earth test point complete, all as specified including testing on completion. Note : Item of earthing include cost of 7.5m long GI earth wire 4mm dia, ,earth work in soft/ loose soil, returning filling and removal, GI protection pipe, GI watering pipe, funnel, wire wesh, RCC cover, etc .
M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion,, complete all as specified and as directed by the Engineer-in-Charge
M&L for Construction of shed for suitable for 25 KVA DG Set including steps,plinth protection, cable duct complete all as specified and directed as shown on drawing NO CESZ/TD-1110/2011 sheet 1/2 and 2/2 Dated 01/12/2011
M&L for Construction of shed for suitable for 250 KVA Transformer including steps,plinth protection, cable duct complete all as specified and directed as shown on drawing NO CESZ/TD-1110/2011 sheet 1/2 and 2/2 Dated 01/12/2011
M&L for Construction of shed for suitable for 400 KVA Transformer including steps,plinth protection, cable duct complete all as specified and directed as shown on drawing NO CESZ/TD-1110/2011 sheet 1/2 and 2/2 Dated 01/12/2011. Note : Please reference Note No 12 of drawing No CESZ/TD-1110/2011 sheet 1/2 and 2/2 Dated 01/12/2011
ALCO ENGINEERSPVT LTD
M/S Razdan Buildersand suppliers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .