Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.8 LAccepted-AOC 137 3 STREET NO 4 RAJINDER NAGAR DEHRADUN UK 248001 | DEHRADUN | DEHRADUN | UTTARAKHAND | 248001 | L1 | Accepted-AOC Being lowest and competitive | |
| 2 | L2₹27.4 L+₹1.6 L (6.03%)Rejected-AOC PLOT NO 10 9 OM VIHAR PHASE 1 A UTTAM NAGAR NEW DELHI 110059 | WEST DELHI | DELHI | 110059 | L2 | Rejected-AOC Neither lowest nor competitive | |
| 3 | L3₹30.0 L+₹4.1 L (15.8%)Rejected-AOC | L3 | Rejected-AOC Neither lowest nor competitive | |
| 4 | L4₹34.4 L+₹8.5 L (32.9%)Rejected-AOC | L4 | Rejected-AOC Neither lowest nor competitive | |
| 5 | L5₹38.3 L+₹12.5 L (48.2%)Rejected-AOC BARIYAWAN BARIYAWAN BARIYAWAN BARIYAWAN AMBEDKAR NAGAR UTTAR PRADESH 224210 | AMBEDKAR NAGAR | UTTAR PRADESH | 224210 | L5 | Rejected-AOC Neither lowest nor competitive |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
27 Jan 2021, 6:00 pmClosed
GE (Central) Delhi Cantt
GE (Central) Delhi Cantt
REPAIR/REPACEMENT OF OLD UNSERVICEABLE CFL/FTL FITTING WITH LED FITTING AND OTHER MISC E/M WORKS AT 105 TA BN 202 BD COY 2223 CEREMONAL BTY 5 HQ SIG GP 500 (I) SIG COY 1 WEC AND SIGNAL ENCLAVE AREA UNDER GE (CENTRAL) DE
2021_MES_408784_1
GE/C-69/2020-21
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
120 days
GE (Central) Delhi Cantt
As per NIT
9 documents required · 9 mandatory
₹500
GE (Central) Delhi Cantt
₹98,000
Yes
6 Mar 2021
1 Jan 2021
29 Jan 2021
1 Jan 2021
27 Jan 2021
15 Jan 2021
1 Jan 2021 - 15 Jan 2021
Amount
Supply and fix in replacement LED batten luminaire surface mounted, 4 feet system wattage of 22 Watts, > 2400 systems lumen outputwith lifetime of 50000 burning hours with 70% of its initial lumen maintained. CRI>80, Power Factor > 0.95, THD< 10%, colour temperature - 6500K, surge protection 2.5KV in CM, IP-20 protected, meets LED IS specifications, Class - 1, Short circuit and over circuit protection, voltage range - 150 to 270 Volts AC, temperature range 0 to 50 DegreeC and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire from ceiling rose to fitting fixed complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement LED batten luminaire surface mounted 2 feet system wattage of 10 watts and not less than 1000 lm with life time of 50000 burning hours with 70% of its initial lumen maintained. CRI > 80, power factor > 0.95, THD < 10%, color temperature > 6500 K , surge protection 2.5 KV in CM IP- 20 protected meets LED IS specifications, voltage range - 150 to 270 volts AC, temperature range 0 to 50 Degree C, system efficiancy at luminarie level ≥100 Lumens/watt and including connecting up with PVC sheathed 1.5 sqmm 3 core copper conductor flexible wire fixed complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement LED 9/10 watts bulkhead fitting with powder coated die cast aluminium housing with glass/ non yellowing polycarbonate cover, IP65 Protection, System level efficacy of the Luminary is > 90 lm/W with a life class of 50,000 burning hours at L70 criteria, Power Factor >0.95, driver with Voltage range 150-270V, Temperature range 0 to 50 Deg, Driver efficiency >85%, THD<10%, CRI>80, Color Temperature-6000K, Surge protection of 2.5 KV, including connecting up with necessary PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as specified and directed by Engr-in-charge.
S&F in replacement of decorative type wall mounted luminaire (Comet) with unbreakable poly carbonate materials suitable for 1x14 watt LED bulb B22 base complete all as specified and directed by Engineer in charge .
Supply and Fix in replacement in repair 45 W High efficient LED Street light fitting with pressure die cast LM6 Aluminum housing and has lenses specially designed for Street Lighting with polycarbonate cover. System level efficacy of the Luminarie is 100lm/W with a life class of 50,000 burning hours at L70. The color temperature is around 6500 K with a color rendering index of 70. The luminaire is IP:66 protected with IK05 impact resistance. It has an electronic driver complaint to IEC safety standards with a power factor>.0.9, voltage variation range 120-270V, THD<20%, High and low protection along with a surge protection of 4 KV including provision of 25 mm dia GI light grade pipe1.5 meter length bend to shape and necessary clamps etc for fixing the light fittings on pole fixed complete as specified and directed by Engr-in-charge.
Supply and Fixing in replacement LED bulb 9 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge .
Supply and Fixing in replacement LED bulb 14 watts, 900 lumens output, 6500K suitable for B-22 base complete all as specified and directed by Engineer in charge .
Supply and fix in replacement LED 2 X 2 ft backlite recses mounted fitting 36/40 Watts not less than 3200lm with Metallic CRCA powder coated body with high efficiency opal/PMMA diffuser with system efficacy > 80 lm/W, CRI>80, color temperature >5700k, IP 20, Power factor<0.95, THD<10%, 50000 burning hours , Ambient temperature 0 to 500 DegC, Driver should meet IEC complaint for safety, with voltage variation range of 150-270 V and surge protection of 2.5 KV including necessary fixing arrangementsfixed complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement surface ceiling mounted, LED down light fitting 12 watts with die cast aluminium housing and system wattage of 12W, system efficacy at luminary level ≥ 80 Lumens/watt, 50000 burning hours, 6500K color temperature with CRI >80, Power Factor > 0.90, Driver should meet IEC compliant for safety with multi stage high Isolate CC-CV operated driver with voltage variation range - 150 to 270 Volts AC, and surge protection of 2.5 KV, and including connecting up with PVC sheathed 3 core 1.5Sqmm copper conductor flexible wire fixed complete all as specified and directed by Engr-in-charge.
Supply and fix in replacement MCB DB SPN 12 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.
Supply and fix in replacement MCB DB SPN 8 way Horizontal, IP - 43 Protection double door 240 V AC 50Hz with for MCB SPN as incomer and DP/SP MCBs as out going with tinned copper bus bar ,neutral link earth link complete all as directed by Engineer -in- Charge.
Supply & fix in replacement factory made epoxy powder coated Load line Distribution Board TPN-4 ways with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including insulated 200 Amp copper bus bar, Isolated neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removeable gland plates with knockouts and suitable for one TPN- MCCB 125/160 Amp as incomer and 32 to 63 Amp SP MCBs outgoing complete all as specifiedby Engr-in-charge.
Supply and fix iin replacement MCCB 160 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge.
Supply and fix in replacement MCCB 125 Amps, FP 415 volts 16 KA 50 HZ with thermal magnetic setting complete all as specified and directed by Engineer in charge.
Supply and fix in replacement MCB DP 63 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge
Supply and fix in replacement MCB DP 40 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge
Supply and fix in replacement MCB SPN 40 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge
Supply and fix in repair MCB SP 6-32 Amps 240 volts 10 KA 50 HZ 'C' curve complete all as specified and directed by Engineer in charge
M&L in replacement sheet metal enclosure, single pole and neutral with a two pin and earth plug and socket 240 Volts grade 20 Amps complete with one single pole MCB 'C' series 20 A capacity complete all as specified and directed by Engineer in charge.
Taking down care fully copper/aluminium point wiring from wooden batten or conduits (light, fan, socket or power) complete incl fittings such as switches, sockets, ceiling roses, pendents, regulators, light fittings any type etc to be measured seperately) and making good disturbed surfaces of walls, floors etc complete all as specified and directed by Engineer in charge.
M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through Existing PVC conduit, including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty and fabricated branded modular metal flush box / M S Steel terminal boxes, concealed in walls with suitable modular inner and outer plate / 3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc , all as specified and as directed for the followings:- complete all as specified and directed by Engineer in charge.
One light/fan point controlled by one way switch
One bell / buzzer point controlled by one bell push
One light point controlled by two Nos two way switches
One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board.
One 3 pin 5 Amps socket outlet point controlled by one way switch on same board
All as per item No 21 but point wiring with 2.5 Sqmm single core copper cable and earth continuity wire with 2.5 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge.
M & L for Point wiring complete with 1.5 sqmm single core PVC insulated FRLS cable 1100 volts grade with multi stranded copper conductor drawn through and including non-metalic rigid PVC conduit medium grade ISI Marked and all conduit accessories concealed in wall/ceiling/fixed to roof/truss/columns etc and including provision of 1.5 sqmm PVC insulated copper cable FRLS as earth continuty, fabricated branded modular metal flush box / M S steel terminal boxes, concealed in walls with suitable modular inner and outer plate / 3 mm thick laminated top sheet cover for housing switches , socket out let and fan regulators etc , all as specified and as directed for the followings:- complete all as specified and directed by Engineer in charge.
One light/ fan point controlled by one way switch
One bell / buzzer point controlled by one bell push
One 3 pin 5 Amps socket outlet point controlled by one way switch on independent board.
One 3 pin 5 Amps socket outlet point controlled by one way switch on same board
All as per item No 23 but point wiring with 2.5 Sqmm single core copper cable and earth continuity wire with 2.5 Sqmm single core stranded copper cable for one three pin 15 socket outlet point on independent board complete all as specified and directed by Engineer in charge
M&L in replacement switch Modular type 6 Amps 1 Way,1 module, 230V AC complete all as specified and directed by Engineer in charge.
M&L in replacement Modular socket outlet 2/3 pin 6 Amp socket 2 module complete all as specified and directed by Engineer in charge.
M&L in replacement switch Modular type 16 Amps 1Way, 1 module with modular plate light marking 230V AC complete all as specified and directed by Engineer in charge.
M&L in replacement Modular socket outlet 2/3 pin 6/16 Amp universal socket 2 module complete all as specified and directed by Engineer in charge.
M&L in replacement modular stepped type electronic fan regulator 120W, 2 module all as specified and directed by Engineer in charge.
M&L in replacement switch piano flush button type single pole one way 6 Amps complete all as specified and directed by Engineer in charge.
M&L in replacement switch piano flush button type single pole Two way 6 Amps complete all as specified and directed by Engineer in charge.
M&L in replacement bell push single pole 6 Amps complete all as specified and directed by Engineer in charge,
M&L in replacement switch piano flush button type single pole 16 Amps complete all as specified and directed by Engineer in charge .
M&L in replacement socket outlet, 2 in 1, 3 pin 6 and 16 Amp single pole complete all as specified and directed by Engineer in charge.
M&L in replacement socket outlet 6 Amp flush button type complete all as specified and directed by Engineer in charge.
M&L in replacement regulator electronic switch/socket type 5 steps suitable for 1200/1400 mm sweep 230 volts all as specified and directed.
M&L in replacement bell electric (dingdong) 230 volt, SP all complete all as specified and directed by Engineer in charge .
M/L in replacement insulated body, angle holder (metal ring) with back plate complete all as specified and directed by Engineer in charge.
S&F ceiling rose surface PVC 65x50 mm type with three terminals complete all as specified and directed by Engineer in charge .
S&F plug top, 3 pin, 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge.
S&F socket 3 pin 20 amp earth metal clad (ISI marked) complete all as specified and directed by Engineer in charge .
S&F in repair Sub main wiring with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 20 mm dia non metallic rigid PVC conduit and conduit accessories concealed / surface of walls complete all as specified and directed.Note: Three runs of 4 sqmm cable shall be measured as one RM.
S&F in repair Sub main wiring with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 25 mm dia non metallic rigid PVC conduit and conduit accessories concealed / surface of walls complete all as specified and directed.. Note: Three runs of 4 sqmm cable shall be measured as one RM.
S&F in repair Sub main wiring with two runs of 6 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through existing conduit and conduit accessories on surface of walls complete all as specified and directed.
S&F in repair Sub main wiring with two runs of 10 Sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable with one run of 10 sqmm single core PVC insulated FRLS cable 1100 volts grade, multistranded copper conductor cable as earth continuity conductor, drawn through and including 25 mm dia non metallic rigid PVC conduit and conduit accessories on surface of walls complete all as specified and directed.
S&F PVC Gang box surface type heavy duty suitable for single switch 5 Amps complete all as specified and directed by Engr in charge .
S & F Gang box surface type heavy duty suitasble for 5 Amps switch and socket complete all as specified and directed by Engineer in charge.
S & F Gang box surface type heavy duty suitasble for 15 Amps switch and socket complete all as specified and directed by Engineer in charge.
M & L for in replacement only single core PVC insulated cable 1.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits, all as specified and directed by Engr-in-Charge.
M & L in replacement for only single core PVC insulated cable 2.5 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge.
M & L in replacement for only single core PVC insulated cable 4 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge.
M & L in replacement for only single core PVC insulated cable 10 Sqmm FRLS 1100 Volts with copper multi stranded conductor and drawing in existing concealed conduits , all as specified and directed by Engr-in-Charge.
Supply only hylum sheets 3 mm thick (ISI marked) of the following sizes :- Make :-As per sample.
Sheet 4" x 4" single cutting suitable for one piano switch
Sheet 4" x 4" two cuttings suitable for two piano switches
Sheet 4" x 7" three cuttings suitable for three piano switches
Sheet 4" x 7" one cutting for 6 Amp socket and two cuttings for piano switches
Sheet 8" x 10" incl cuttings for switches and sockets 6/16Amps as directed.
Sheet 10" x 12" incl cuttings for switches and sockets 6/16Amps as directed.
S & F in replacement of BER by BOO exhaust fan 300 mm sweep, metal type including provision of 3 core PVC insulated sheathed 1100 volts grade flexible cable with stranded copper conductor from ceiling rose to fan, length as per requirement at site complete all as specified and directed by Engineer in charge .
Supply and fixing Ventilating Fan 250 mm sweep, 1250 RPM, non metallic resin body, single phase 240 volts AC 50 Hz and connecting up complete including louvers and provision of copper cable 3 core of size 0.5 sqmm for connection from ceiling rose to fan complete all as specified and as directed.
Note :- Total amount of Sch of credit is Rs. 109691.50 as per Sch of credit. Net contract sum shall be total quoted amount of bidder (-) amount of Sch of credit.
LAMBA ENTERPRISES
Pall Associates
M/s S.G. BUILDERS
m/s VK construction company
New Era Engineers
somyaenterprises
DHAIRYAE ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .