| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹12.5 LAccepted-AOC 7A BENTINCK STREET KOLKATA 700 001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹12.9 L+₹47,021 (3.77%)Rejected-Finance | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹14.6 L+₹2.2 L (17.4%)Rejected-Finance 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L3 | Rejected-Finance 3rd lowest bidder | |
| 4 | L4₹17.0 L+₹4.5 L (36.4%)Rejected-Finance GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | L4 | Rejected-Finance 4th lowest biddr |
Tender Value
Refer Docs
EMD Value
₹34,000
Closing Date
17 Jan 2022, 6:00 pmClosed
EE_I Kol. South Health El. Divn., P.W.Dte
75 D H Road Kidderpore Kol_23
Supply, Installation, Testing and Commissioning of Fire Detection system of (Gplus3) Storied Old Building of Bangur Institute of Neurosciences at 52 1A, Sambhunath Pandit Street, Kolkata-700025.
2021_WBPWD_358107_1
WBPWD/KSHED/Q49/21-22
Open Tender
FIRE FIGHTING ORG
Item Rate
60 days
Kolkata
Please refer Tender documents.
2 documents required · 2 mandatory
₹34,000
O/o Exe Engr, Kol. South Health El. Divn., P.W.Dte
4 May 2023
28 Dec 2021
20 Jan 2022
28 Dec 2021
17 Jan 2022
7 Jan 2022
6 Jan 2022
Amount
Supply, Installation, Testing & Commissioning of Analog Addressable Intelligent multi sensor detector (VDS / UL / FM / ULC approved) with inbuilt optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photo thermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/ Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward/ Secutron/ Securiton/ Apollo/ Morley/ Eaton).
Supplying, installation, testing and commissioning of Addressable Heat Detector (Fixed temperature cum rate of rise) ( VDS / UL / FM / ULC approved ) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended standards ) without any additional cost). (Approved Make: Esser/ Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward/ Secutron/ Securiton/ Apollo / Morley/ System Sensor /Eaton).
Supply, Installation, Testing & Commissioning of Addressable Manual Call Point (VDS / UL / FM / ULC approved) soft addressable type within built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton).
Supply, Installation, Testing & Commissioning of Addressable Loop Powered Hooter (sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward /Secutron/ Securiton/ Apollo / Morley / Eaton).
Supplying, installation, testing and commissioning of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/ Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward / Secutron/ Securiton/ Apollo / Morley /Eaton).
Supply, Installation, Testing & Commissioning of Power supply 230V AC to 24V DC with all other accessories (Make: Reputed).
Supply, Installation, Testing & Commissioning of Addressable transponder / Monitor Modules (VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / Eaton)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (Make. RR Kabel/ Havells /Polycab) in prelaid PVC rigid conduit pipe.
Supply & Drawing 20 mm NB PVC rigid conduit pipe (Make: Precision) on wall incl. necy. Bend, elbow etc.
Dismantling of existing damaged F.D.A. system from different location of this building.
Supply, Installation, Testing & Commissioning of Microprocessor based Intelligent, addressable expandable and fully networkable fire alarm control panel ( VDS / UL /ERTL / LPCB / FM approved ) suitable for the devices as stated in the previous items of this BOQ along with 20% spare capacity with each loop loading not exceeding 80% of the full capacity of detectors and devices taken together, complying to IS 2189:2008 or its latest amendments, and with minimum 600 character alpha - numeric liquid crystal display. The panel shall be soft addressable type and shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards.
The panel shall have in built rectifier, provision for external & internal printer (if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emergency condition, with integral battery charger complete in all respect as required.
The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 bus. The FACP shall have provision for interfacing with the public address system, remote computer and BMS interface. The system must be preloaded with licensed software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer/ Edward/ Secutron/ Securiton/ Apollo / Morley / Eaton)
NOTE: The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm & Signalling Code 5. Local Statutory Regulations. 6. Manufacturer Recommendation. 7. A single panel is to be installed for the whole installation. 8. The license software for programming FACP should be provided in separate storage media e.g. Pen drive, DVD etc along with source code.
TESTS: 1. The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
Terms and condition:
1) The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM become applicable to the products to be delivered and installed by them.
2) Documents that authenticate such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
3) If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liability period 1 (One) Year
MAM ENTERPRISE
ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD
GLYPTIC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .