| 1 | L1₹26.8 CrAdmitted-Finance | ₹26.8 Cr | L1 | Admitted-Finance |
| 2 | L2₹32.5 CrAdmitted-Finance 1 CROOKED LANE ROOM NO 205 2 FLOOR KOLKATA 700069 WEST BENGAL PH 9167480150 | ₹32.5 Cr | L2 | Admitted-Finance |
| 3 | L3₹37.8 CrAdmitted-Finance | ₹37.8 Cr | L3 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not meeting the eligibility criteria being two classes below |
| Sl No | Description | Qty | Unit | KAKALI ENTERPRISE L3 | SHREYANSH TRADING AND CONSTRUCTIONS PRIVATE LIMITED L1 | Narayan Kumar Infrastructure Pvt Ltd L2 |
|---|---|---|---|---|---|---|
| 1.00Schedule "A" Part – I to Schedule "A" Part – XX NOTE: Schedule "A" Part – I to Part – XVIII are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only and for Items of Part XIX & XX Bidders shall insert unit Rate of each items of work in Green coloured field under Column - 6 only. | ||||||
| 2.00 | Lump Sum price worked out by the contractor for "BUILDINGS & STRUCTURES", for the lumpsum price of Rs. 18,39,48,621.00 inserted by MES as listed in Schedule 'A' Part - I | 1 | Each Job | 24,00,00,000 ₹24 Cr | 15,09,93,956.51 ₹15.1 Cr | 22,19,33,000 ₹22.2 Cr |
| 3.00 | Price worked out by the contractor for "EARTHWORK AND SITE CLEARANCE ", against the price of Rs. 12,08,942.97 inserted by MES as listed in Schedule 'A' Part - II | 1 | Each Job | 21,76,095 ₹21.8 L | 10,44,247.79 ₹10.4 L | 15,59,049 ₹15.6 L |
| 4.00 | Price worked out by the contractor for "INTERNAL WATER SUPPLY", against the price of Rs. 16,28,147.69 inserted by MES as listed in Schedule 'A' Part - III | 1 | Each Job | 32,81,516 ₹32.8 L | 17,29,351.35 ₹17.3 L | 20,95,654 ₹21.0 L |
| 5.00 | Price worked out by the contractor for "INTERNAL ELECTRIC SUPPLY", against the price of Rs. 70,72,286.03 inserted by MES as listed in Schedule 'A' Part - IV | 1 | Each Job | 81,23,909 ₹81.2 L | 92,31,523.8 ₹92.3 L | 63,00,199 ₹63.0 L |
| 6.00 | Price worked out by the contractor for "EXTERNAL WATER SUPPLY", against the price of Rs. 2,71,612.96 inserted by MES as listed in Schedule 'A' Part - V | 1 | Each Job | 6,22,792 ₹6.2 L | 3,39,380.53 ₹3.4 L | 3,45,772 ₹3.5 L |
| 7.00 | Price worked out by the contractor for "EXTERNAL ELECTRIC SUPPLY ", against the price of Rs. 11,56,483.35 inserted by MES as listed in Schedule 'A' Part - VI | 1 | Each Job | 14,56,193 ₹14.6 L | 14,29,314.16 ₹14.3 L | 15,68,185 ₹15.7 L |
| 8.00 | Price worked out by the contractor for "SEWAGE DISPOSAL", against the price of Rs. 3,14,620.40 inserted by MES as listed in Schedule 'A' Part - VII | 1 | Each Job | 9,95,624 ₹10.0 L | 4,11,172.57 ₹4.1 L | 4,05,860 ₹4.1 L |
| 9.00 | Price worked out by the contractor for "AREA DRAINAGE", against the price of Rs. 4,91,284.85 inserted by MES as listed in Schedule 'A' Part - VIII | 1 | Each Job | 12,25,770 ₹12.3 L | 5,87,389.38 ₹5.9 L | 6,34,794 ₹6.3 L |
| 10.00 | Price worked out by the contractor for "ROAD/ PATH/ CULVERT ", against the price of Rs. 28,39,921.00 inserted by MES as listed in Schedule 'A' Part - IX | 1 | Each Job | 73,83,794 ₹73.8 L | 36,09,181.42 ₹36.1 L | 36,62,392 ₹36.6 L |
Tender Value
₹25.5 Cr
EMD Value
₹15 L
Closing Date
14 Sept 2023, 9:00 amClosed
CHIEF ENGINEER COAST GUARD VISAKHAPATNAM
Office of HQ Chief Engineer (CG) Visakhapatnam
As per BOQ
2023_MES_583047_3
CE (CG) /VIZ/KOL(MNK)/TOKEN-25 OF 2022-23
Open Tender
Civil Works
690 days
KOLKATA
As per tender documents
8 documents required · 8 mandatory
₹3,000
Garrison Engineer I CG and N Kolkata
₹15 L
Yes
3 Oct 2023
18 Aug 2023
19 Sept 2023
18 Aug 2023
14 Sept 2023
1 Sept 2023
Amount
Schedule "A" Part – I to Schedule "A" Part – XX NOTE: Schedule "A" Part – I to Part – XVIII are prepriced by MES. Bidders shall insert their Lumpsum amount in Green coloured field under Column - 6 only and for Items of Part XIX & XX Bidders shall insert unit Rate of each items of work in Green coloured field under Column - 6 only.
Lump Sum price worked out by the contractor for "BUILDINGS & STRUCTURES", for the lumpsum price of Rs. 18,39,48,621.00 inserted by MES as listed in Schedule 'A' Part - I
Price worked out by the contractor for "EARTHWORK AND SITE CLEARANCE ", against the price of Rs. 12,08,942.97 inserted by MES as listed in Schedule 'A' Part - II
Price worked out by the contractor for "INTERNAL WATER SUPPLY", against the price of Rs. 16,28,147.69 inserted by MES as listed in Schedule 'A' Part - III
Price worked out by the contractor for "INTERNAL ELECTRIC SUPPLY", against the price of Rs. 70,72,286.03 inserted by MES as listed in Schedule 'A' Part - IV
Price worked out by the contractor for "EXTERNAL WATER SUPPLY", against the price of Rs. 2,71,612.96 inserted by MES as listed in Schedule 'A' Part - V
Price worked out by the contractor for "EXTERNAL ELECTRIC SUPPLY ", against the price of Rs. 11,56,483.35 inserted by MES as listed in Schedule 'A' Part - VI
Price worked out by the contractor for "SEWAGE DISPOSAL", against the price of Rs. 3,14,620.40 inserted by MES as listed in Schedule 'A' Part - VII
Price worked out by the contractor for "AREA DRAINAGE", against the price of Rs. 4,91,284.85 inserted by MES as listed in Schedule 'A' Part - VIII
Price worked out by the contractor for "ROAD/ PATH/ CULVERT ", against the price of Rs. 28,39,921.00 inserted by MES as listed in Schedule 'A' Part - IX
Price worked out by the contractor for "CHAIN LINK FENCING", against the price of Rs. 68,920.18 inserted by MES as listed in Schedule 'A' Part - X
Price worked out by the contractor for "FIRE FIGHTING EXTERNAL", against the price of Rs. 5,01,718.72 inserted by MES as listed in Schedule 'A' Part - XI
Price worked out by the contractor for "FIRE FIGHTING INTERNAL", against the price of Rs. 20,47,753.10 inserted by MES as listed in Schedule 'A' Part - XII
Price worked out by the contractor for "LIGHTNING PROTECTION", against the price of Rs. 55,363.80 inserted by MES as listed in Schedule 'A' Part - XIII
Price worked out by the contractor for "HOT WATER SUPPLY", against the price of Rs.7,87,217.60 inserted by MES as listed in Schedule 'A' Part - XIV
Price worked out by the contractor for "TELEPHONE/ LAN/ TV CONDUIT", against the price of Rs. 1,08,467.00 inserted by MES as listed in Schedule 'A' Part - XV
Price worked out by the contractor for "DG SET", against the price of Rs. 19,414.40 inserted by MES as listed in Schedule 'A' Part - XVI
Price worked out by the contractor for "LIFT", against the price of Rs. 2,57,265.00 inserted by MES as listed in Schedule 'A' Part - XVII
Price worked out by the contractor for "PILE WORK", against the price of Rs. 4,15,48,543.60 inserted by MES as listed in Schedule 'A' Part - XVIII
Schedule "A" Part - XIX [Miscellaneous Items]
INTERNAL WATER SUPPLY
Item No.1 :S&F two way bib cock 15mm bore with flange cast copper alloy chromium plated fancy type screwed for iron popes brass ferrul etc. complete all as specified and as directed.
Item No.2 :M&L wall mixer CP 15 mm dia for mixing hot & cold water including tap screwed down for pipe and fixed to wall complete all as specified and as directed.
INTERNAL ELECTRIFICATION
Item No.3 : S & F LED bulb 9 Watt lumen not less than 770 Lumen commplete all as specified and directed
Item No.4: S&F modular metal box 8 way
Item No.5 :S&F modular metal box 12 way
Item No 6.S&F modular white cover plate with frame 12 way
Item No 7: Design, Supply and Commission integrate and maintain the Advanced Metering Infrastructure (AMI) comprising of following for Single Phase Meter:- (a) Supply, installation, commissioning of Smart Meters of different makes (not more than 33% of a particular make to ensure interchangeability at a later date as per BIS 16444 with communication technology including GPRS/RF Mesh or Canopy/Hubrid (RF + GPRS)/Any other advanced technology as per CEA/TRAI regulations. (b) Supply/Planning/Setup/tuning of RF Mesh communication infrastructure including Network Management (NMS) & Head End System for the project area. AMI Software and associated equipment's should be capable of handling at lease 152 Number of Meters of different makes as per BIS 16444 with 25% expansion without any additional infrastructure and cost implication to MES. (c) Supply and setup of Meter Data Management (MDM) (d) Integration of different devices of different makes/equipment/software's covered in scope of this project with each other as per functional requiremtns, including water charges, furniture and license fee.system. (e) Integration/Interface of the AMI system with application systems like Metering/Billing/collection. Interface has to be provided in the proposed solution to upload and process meter date from these systems. (f) Server for Housing and management of supplied software application with standby server. (g) Planning, deployment & tuning of communication system including Cellular network (if required) to meet the performance requirements. (h) Business Intelligence, Analystics and Reporting. (j) Training and knowledge transfer. (k) All expenditure including periodic charges of telecom operator from installation till completion.
Item No 8: Supply, Installation of 400A, 4P MCCB capacity End Feed Unit for existing Rising Main, made of 1.6mm GI enclosure with C&S make 25kA, 4P TM release MCCB
Item No 9: Supply, Installation of 63A Tap off box with 63A, 4P,25 KA MCCB capacity TPN Tap off box for existing Rising Main, made of 1.6mm GI enclosure with C&S make 4P, 25 kA TM Release MCCB
Item No 10: S & F blank plate PVC in lieu of MCB, piano switch,Socket etc
Item No 11: Supply ,Installation of 400A, 4P, 15kA Straight Length Compact Air Insulateddesign systemRising Main,aluminiumconductor (3 phases +100 %Neutral +50% integral GI earth) 4 Nos Al bus bars having current density of 130A / Sq. CM at nominal current ratings and 2 nos. of suitable externalaluminiumearthing strips, System voltage 415 Volt, AC supply,IP 54, rated frequency 50 / 60Hz, made of 1.6 mm thick sheet GI enclosure duly painted with powder coating (RAL-7032), with provision of tapping at every floor etc. Compliance standard:IEC-61439 (Part 1&6) & IS- 8623 (Part 1&2),Independent
EXTERNAL WATER SUPPLY
ITEM NO.12:- M&L for 100 mm dia ductile iron pipes with flanged ends centrifugally cast Class K-9, with necessary gaskets, nut bolts and other accesories in any length, laid in trenches complete all as specified and directed by Engr-In-Charge.
ITEM NO.13:- All as per item No 12 above but for 150 mm dia all as specified and as directed.
ITEM NO.14:- M&L for DI specials like Bends (any type, radius and angle) tapers any type (straight, bend, increasing, decreasing or double socket etc) Tee pieces single branch "Y" junction, double branch, cross (all sockets or socket and spigot) collars, caps and plugs for DI pipe upto 100mm bore as directed by Engr-in-Charge.
ITEM NO.15:- S&F MS Flange suitable for 80mm bore steel water tubing including with necessary GI Nuts bolts and gaskets complete including welding/threading to the pipe complete all as specified and directed.
ITEM NO.16:- Supply and fix for 100 mm dia D.I. resilient (soft) seated gate valve with pocket less body, ss stem (AISI 410), epdm coated di wedge 100% vaccum tight design with toroidal sealing rings & over 250 micron epoxy coating in PN16 designed to BS:5163/IS:14846 non-rising stem type with hand wheel operation complete all as specified and as directed.
ITEM NO.17:- Supply and fix CI foot valve conforming to IS 4038, 150 mm (4") dia all as specified and as directed.
ITEM NO.18:- Supply and fix 100 mm (4") dia DI resilient seated non-return valve, flanged end in swing type design with EPDM door and with over 250 micron epoxy coating including all necessary items complete all as specified and as directed.
ITEM NO.19:- Supply and fix Air release valve, 50 mm (2") dia with all necessary fittings all as specified and as directed.
ITEM NO.20:- Construction of brick masonry (full brick thick wall ) valve chamber, of 1050x1050x950mm size of internal diomension, PCC work with (1:4:8) type D2 . 150mm thick (using 40mm grade stone aggregate) for foundation complete with 3.00mm thick MS sheet cover and frame of MS angle iron 40x40x5mm with locking arrangement and painting with one coat of red oxide primer and two coats of synthetic enamel paint all as specified shall be plastering to internal and exposed surfaces of the chamber, in CM(1:4) 15mm thick and PCC coping (1:2:4) type B-1, 50mm thick all as specified.
ITEM NO.22:- Supply, installation, testing and commisioning of Horizontal Centrifugal Pumping set split case type with side suction and side discharge, suitable for operation on 2850/2900 RPM, comprising of , centrifugal pump capable of delivering 4.6 LPS at 80 Meter Head, 2850/2900 RPM directly coupled with TEFC squireel cage induction motor 3 Phase, 415 Volts, 50 Hz AC supply IP 55 Protection, of HP/Wattage sutable to drive the pump, suitable for operation at up to 50 degree centigrade, Class "F" insulation, with temperature rise limited to Class "B" confirming to IS: 325, complete pump and motor assembled with base plate , coupling, coupling guard and foundation as per OEM's specifications cpmplete with suction pipe in suitable size and specifications as per OEM recommendations upto 3 meters in lenght, header and foot valve etc . Casing shall have axial suction and top centre line delivery. Impellers shall be of enclosed type. Shaft shall be supported with antifriction bearing, grease lubricated all as specified and as directed.
ITEM NO.23:- Supply, fix, installation and testing Altoch dosing system model ADS-PRO 153120 AP with necessary fitting arrangement to waterline. Item description: 1. Receptable for power-free-automatic water sanitiser/ conditioning treatment station with proportional dosing arrangement with following attachments:- (a) Water inlet valve (b) Overflow valve (Rubber guard included) (c) Outlet valve for standalone gravity flow (d) Outlet valve for automated flow (e) Drain valve (f) Level controller (g) Level guage (h) Detachable grouting bas with rubber buffer (j) Custom cover synchronous fixing arrangement (k) Material of construction : Non-metallic thermoplastic (l) Maximum Temperature : 45.C (m) Capacity : 100 litres (n) Shape : Cylindrical (p) Compatibility : Stequa 411 AE Refill/Prefill-Total refill
2. Custom cover for power-free automatic water sanitiser / conditioning treatment station with proportional dosing arrangement with following attachments: Refill Cavity Lids (13) In-built Level Switch & Processor ½ inch Processor Outlet & Processor Inlet connections Flexible Connecting Duct Material of construction: Non-metallic Maximum Temperature: 45°C Shape: Circular Compatibility: Stequa 411 AE Refill / Prefil - Total refill Note: Necessary cutting/fabrication work deemed included in the rate.
ITEM NO. 24 :- Supply only STEQUA 411 AE REFILL Item description : Chlorine tablets contained in plastic cylindrical sealed disposable sanitiser refill for disinfecion of drinking water with arrangement for controlled release of disinfectant in water, suitable for operation through recommended dosing system. (a) Replacement indication: Visual & weight variation (b) Water contact orifice design : Sealed when dry, exposed upon immersion. (c) Operation type: Non contace, Non inhalatory (d) Cylinder Dia : 2.5 inches +/- 0.5 inches (e) Cylinder height : Minimum 10.00 inches +/- 0.5 inches (Note: 01 Set consists of 25 Pcs)
ITEM NO. 25 :- Supply, installation, design, testing and commissioning floor mounted indoor panel cubical type of suitable size . The Panel made out of 2mm thick MS CRCA sheet and suitable size angle iron structure ,CPRI approved/Type tested compartmentalized, type of size as required including locking arrangement and powder coated paint after 7 tank cleaning process , fixed in floor with MS angle iron suitable size frame structure and grouted with PCC M-15 (Nominal mix) using 20mm graded stone aggregate with and including suitable size copper FRLS/HRFR copper wired connection, brass glands for cable entry etc complete all as specified and as directed and as following specification : - INCOMER (i) MCCB 125 Amp 4 pole 25 KA with microprocessor based release - 01 No OUTGOING (i) MCCB 63 Amps 4 pole 16 KA with microprocessor based release - 04 Nos (ii) Automatic Star Delta Starter suitable for pump mentioned at item No 19 - 04 Nos (iii) MCB TPN 32 Amps 'C' Series - 01 No (iii) MCB DP10 Amps 'C' Series - 02 Nos (iv) 200 Amps capacity copper bus bar of suitable size and required length (equal size for phase and neutral) and fixed on 04 Nos SMC/DMC/porcelain insulators - 04 Set. (v) Digital ammeter 0-200 amps -01 No with suitable CTs (vi) Digital voltmeter of 0-500 volts-01 No (vii) LED indicator lamp RYB (set of 3)- 02 set. complete all as specified and as directed
ITEM NO. 26 :- S&F PVC insulated 3 core cable flat flexible suitable for centrifugal pump set 1100 volts grade with standard copper conductor cable of size 10 sqmm complete all as specified and directed.
EXTERNAL ELECTRIC SUPPLY
ITEM NO. 27 :- Supply, install, testing and commissioning of Extended type Vacuum Circuit breaker (VCB) with common busbar for 04 Nos outgoing VCBs and suitable to integrate with existing VCB, 250 MVA as incomer complete with one metering module (CVCM) with necessary CTs and PT, comprising the following :- (Complete unit is to be installed inside sub stn, protection accessories , Enclosure : Metal Clad, IP-54 Protection. Protection Relay : Self Powered Alfa pneumatic LCD display type. Internal arc tested for 1 sec , Fully compartmentalized sheet steel enclosure with automatic safety shutters , GI foundation bolts with provision of cable terminating facilities with powder coated smooth glossy finish and installing with multi function meter for KW, KWH, KVAR, Voltage, Current, Frequency, PF etc measurement with necessary CTs and PTs are as per follows:-. (a) Rated Voltage - 12 KV (b) Rated Frequency - 50 Hz. (c) Rated continuous current rating - 400 Amps. (d) Rated Interrupting Current - 21 KA. (e) Rated making current for VCBs- 52 KA. (f) Rated making current for Isolators - 62 KA. (g) Rated short time current for 3 sec - 26.3 KA (h) Operating duty - 0 - 0.3 sec - CO 3 min - CO (i) Power frequency withstand voltage - 28 KV (j) Impulse withstand voltage - 75 KV (k) Bus bar rating - 120% of continuous current. (l) Operation: Spring closing mechanism - DC motor operated with 24 volt supply , Breaker Closing - Manual & Electrical through TNC switch. (m) Shunt Trip coil - 24 V DC
(n) Safety Interlock Locking facility - Required. (o) Breaker panel indication - ON (Red) OFF (Green) (p) Accessories : Mechanical counter ,Space Heater with Thermostat , Fuse and ON/OFF Switch, Aux relays for remote trip/indication for PC interface etc , cubicle illumination lamp LED 9 watt retrofit type 230 V AC , T-N Switch , Anti pumping contractor etc. (q) Mimic Diagram : An operating mimic diagram shall be provided on the front side of each cubicle. (r) Note :- Circuit breaker complete will be obtained directly from the OEM and not from the authorised system assemblers of OEM. The installations, calibration and testing of SF-6 circuit breakers will be conducted in the presence of authorised representative of OEM by the Contractor. (s) Battery bank with charger for VCB is included in the item rate and rating of battery as described by OEM. Note:All VCB will be connected through same busbar and it should have provision of connection to other VCB also.
ITEM NO. 28 M&L for provsion of integration of VCB set (as mentioned at Item No 01 above) to the existing VCB with suitable size of bus bar links, gaskets, nut bolts all other necessary accessories including all fabrication in existing VCB all as specified and as directed.
ITEM NO. 29 :-Supply and installation Compact Secondary Substation (CSS) comprising to following parameters: - (a) Sheet steel housing with corrosion resistance and all side openable hinged door and lock and key arrangements. (b) Steel parts are tested as per IS 6988. (c) Engineered for smooth air flow for natural cooling. (d) No access to High voltage parts. (e) GI strip earthing for all LV and HV equipments as per laid down policy. (f) Separate earthing for lightening protection and lightening spike etc. (g) Separation steel sheet wall for RMU/Transformer/LT panel (h) Heave lifting lugs with all equipments load. (j) Slopped roof. (k) Necessary danger plates outside of the CSS. (l) Necessary HT and LT cable/Earth strips opening.
(m) RMU commissioning of SF-6 insulated Ring Main Unit taps incoming, three outgoing (isolators) and one metering module (CVCM) with necessary CTs and PT, comprising the following :-(Complete unit is to be installed inside CSS, protection accessories , Enclosure : Metal Clad, IP-54 Protection. Protection Relay : Self Powered Alfa numeric LCD display type. Internal arc tested for 1 sec , Fully compartmentalized sheet steel enclosure with automatic safety shutters , GI foundation bolts with provision of cable terminating facilities with powder coated smooth glossy finish and as per follows:- Rated Voltage - 12 KV , Rated Frequency - 50 Hz., Rated continuous current rating - 630 Amps., Rated Interrupting Current - 21 KA., Rated making current for VCBs- 52 KA., Rated making current for Isolators - 62 KA., Rated short time current for 3 sec - 26.3 KA , Operating duty - 0 - 0.3 sec - CO 3 min - CO, Impulse withstand voltage - 75 KV, Bus bar rating - 120% of continuous current., Operation: Spring closing mechanism - DC motor operated with 24 volt supply , Breaker Closing - Manual & Electrical through TNC switch, Shunt Trip coil - 24 V DC Safety Interlock Locking facility - Required.,Breaker panel indication - ON (Red) OFF (Green), Accessories : Mechanical counter ,Space Heater with Thermostat , Fuse and ON/OFF Switch, Aux relays for remote trip/indication for PC interface etc , cubicle illumination lamp LED 9 watt retrofit type 230 V AC , T-N Switch , Anti pumping contactor etc., Mimic Diagram : An operating mimic diagram shall be provided on the front side of each cubicle. Note :- Circuit breaker complete will be obtained directly from the OEM and not from the authorised system assemblers of OEM. The installations, calibration and testing of SF-6 circuit breakers will be conducted in the presence of authorised representative of OEM by the Contractor.Battery bank with charger for RMU is included in the item rate and rating of battery as described by OEM.
(n) Transformers 400 KVA copper wounded dry rasine cast distribution type 6 KV/433V, 3 phase, 4 wire LT output, 50 Hz, AN, Dn11, suitable for indoor installation, with offload tap changer with steps ±2.5% up to ±7.5% on HT side all technical specification comprising to IS 1180 (Part-I&II), with all necessary standard fittings and accessories complete after necessary testing after completion with the following specifications: -
Standard KVA rating: - 400 KVA,Primer Voltage: - 6KV/433V AC, Secondary Voltage: - 433 V AC,Neutral earthing should be solidly earth system,Frequency: - 50 Hz with ±3% tolerance,Vector Group: - DYn11,Percentage impedance: - 5% at 75 deg C (subject to IS tolerance),Average temperature rise shall not exceed to 65deg C and max temperature rise of the windings shall not exceed to 115 DegC.,The core shall be of High grade Cold Rolled Grain oriented (CRGO) annealed steel lamination, having low loss and good grain properties, coated with "C" class grade insulations, bolted together firmly to the frames to prevent vibrations and noise.,HV and LV coils should be with electrolytic copper windings, with "C" class grade insulation on HV windings and necessary spacers and air duct for cooling.,The losses at the rated voltage should be within the specified limit as per IS-1180,The transformer enclosure should be with robust construction and shall be built of electrical welded MS sheet wire mesh or perforated sheet for ventilation, with lifting lugs, pulling lugs, top cover fixing bolts, rollers and enclosure base channels.
ITEM NO. 30 Supply and installation Compact Secondary Substation (CSS) comprising to following parameters: - (a) Sheet steel housing with corrosion resistance and all side openable hinged door and lock and key arrangements. (b) Steel parts are tested as per IS 6988. (c) Engineered for smooth air flow for natural cooling. (d) No access to High voltage parts. (e) GI strip earthing for all LV and HV equipments as per laid down policy. (f) Separate earthing for lightening protection and lightening spike etc. (g) Separation steel sheet wall for RMU/Transformer/LT panel (h) Heave lifting lugs with all equipments load. (j) Slopped roof. (k) Necessary danger plates outside of the CSS. (l) Necessary HT and LT cable/Earth strips opening.
(m) RMU commissioning of SF-6 insulated Ring Main Unit taps incoming, three outgoing (isolators) and one metering module (CVCM) with necessary CTs and PT, comprising the following :-(Complete unit is to be installed inside CSS, protection accessories , Enclosure : Metal Clad, IP-54 Protection. Protection Relay : Self Powered Alfa numeric LCD display type. Internal arc tested for 1 sec , Fully compartmentalized sheet steel enclosure with automatic safety shutters , GI foundation bolts with provision of cable terminating facilities with powder coated smooth glossy finish and as per follows:- Rated Voltage - 12 KV , Rated Frequency - 50 Hz., Rated continuous current rating - 630 Amps., Rated Interrupting Current - 21 KA., Rated making current for VCBs- 52 KA., Rated making current for Isolators - 62 KA., Rated short time current for 3 sec - 26.3 KA , Operating duty - 0 - 0.3 sec - CO 3 min - CO, Impulse withstand voltage - 75 KV, Bus bar rating - 120% of continuous current., Operation: Spring closing mechanism - DC motor operated with 24 volt supply , Breaker Closing - Manual & Electrical through TNC switch, Shunt Trip coil - 24 V DC Safety Interlock Locking facility - Required.,Breaker panel indication - ON (Red) OFF (Green), Accessories : Mechanical counter ,Space Heater with Thermostat , Fuse and ON/OFF Switch, Aux relays for remote trip/indication for PC interface etc , cubicle illumination lamp LED 9 watt retrofit type 230 V AC , T-N Switch , Anti pumping contractor etc., Mimic Diagram : An operating mimic diagram shall be provided on the front side of each cubicle. Note :- Circuit breaker complete will be obtained directly from the OEM and not from the authorised system assemblers of OEM. The installations, calibration and testing of SF-6 circuit breakers will be conducted in the presence of authorised representative of OEM by the Contractor.Battery bank with charger for RMU is included in the item rate and rating of battery as described by OEM.
(n) Transformers 250 KVA copper wounded dry rasine cast distribution type 6 KV/433V, 3 phase, 4 wire LT output, 50 Hz, AN, DYn11, suitable for indoor installation, with offload tap changer with steps ±2.5% up to ±7.5% on HT side all technical specification comprising to IS 1180 (Part-I&II), with all necessary standard fittings and accessories complete after necessary testing after completion with the following specifications: -
Standard KVA rating: - 250 KVA,Primer Voltage: - 6KV/433V AC, Secondary Voltage: - 433 V AC,Neutral earthing should be solidly earth system,Frequency: - 50 Hz with ±3% tolerance,Vector Group: - DYn11,Percentage impedance: - 5% at 75 deg C (subject to IS tolerance),Average temperature rise shall not exceed to 65deg C and max temperature rise of the windings shall not exceed to 115 DegC.,The core shall be of High grade Cold Rolled Grain oriented (CRGO) annealed steel lamination, having low loss and good grain properties, coated with "C" class grade insulations, bolted together firmly to the frames to prevent vibrations and noise.,HV and LV coils should be with electrolytic copper windings, with "C" class grade insulation on HV windings and necessary spacers and air duct for cooling.,The losses at the rated voltage should be within the specified limit as per IS-1180,The transformer enclosure should be with robust construction and shall be built of electrical welded MS sheet wire mesh or perforated sheet for ventilation, with lifting lugs, pulling lugs, top cover fixing bolts, rollers and enclosure base channels.
ITEM NO. 31 :-S & F Cast Iron Route marker for HT Cable line as per IE rules including foundation work all as specified and as directed
ITEM NO. 32:-Supply, installation, design, testing and commissioning floor mounted indoor panel double door cubical type of suitable size . The Panel made out of 2mm thick MS CRCA sheet and suitable size angle iron structure ,CPRI approved/Type tested compartmentalized, type of size as required including locking arrangement and powder coated paint after 7 tank cleaning process , fixed in floor with MS angle iron suitable size frame structure and grouted with PCC M-15 (Nominal mix) using 20mm graded stone aggregate with and including suitable size copper FRLS/HRFR copper wired connection, brass glands for cable entry etc complete all as specified and as directed and as following specification : -
INCOMER (i) MCCB 400 Amp 4 pole 36 KA with microprocessor based release - 01 No OUTGOING (i) MCCB 160 Amp 4 pole 25 KA with microprocessor based release - 05 Nos(ii) MCCB 63 Amp 4 pole 25 KA with microprocessor based release - 01 No(iii) 600 Amps capacity copper bus bar of suitable size and required length (equal size for phase and neutral) and fixed on 04 Nos SMC/DMC/porcelain insulators - 04 Set. (iv) Digital ammeter 0-100 amps -01 No with suitable CTs(v) Digital voltmeter of 0-500 volts-01 No (vi) LED indicator lamp RYB (set of 3)- 02 set. complete all as specified and as directed
ITEM NO. 33 :-Supply, installation, design, testing and commissioning wall mounted double door indoor panel cubical type of suitable size . The Panel made out of 2 mm thick MS CRCA sheet and suitable size angle iron structure ,CPRI approved/Type tested compartmentalized, type of size as required including locking arrangement and powder coated paint after 7 tank cleaning process , fixed in wall and including suitable size copper FRLS/HRFR copper wired connection, brass glands for cable entry etc complete all as specified and as directed and as following specification:-
INCOMER (i) MCCB 63 Amp 4 pole 25 KA with microprocessor based release - 01 No OUTGOING (i) MCCB 40 Amp 4 pole 16 KA with microprocessor based release - 09 Nos (ii) MCB DP 10 Amps-01 No (iii) 100 Amps capacity copper bus bar of suitable size and required length (equal size for phase and neutral) and fixed on 04 Nos SMC/DMC/porcelain insulators - 04 Set. (iv) Digital ammeter 0-100 amps -01 No with suitable CTs (v) Digital voltmeter of 0-500 volts-01 No (vi) LED indicator lamp RYB (Set of 3)- 02 set. complete all as specified and as directed
ITEM NO. 34 :-Supply & laying bricks (sub class-'B') laid in trenches as LT cable protection with width equal to the length of bricks complete all as specified and as directed.
ITEM NO. 35 :-Supply and Fix Octagonal/Conical pole, 7M in length, single section, with Top dia 70mm, Bottom dia 130/135mm, thickness 3mm, base plate size (225X225X16)mm, with 4X20mm nut bolts, Hot deep galvanized 65micron, BSEN 10025-S355J0 or equivalent grade steel and base plate as per IS 2062, maximum wind speed resistance 169KM/Hr, with Base PCC foundation of size 300x300x1200mm duly bolts grouting 04 Nos all as directed by the Eng-in-Charge.
ITEM NO. 36 :-Supply and fix outdoor type cable junction box made of PVC complete with knockout for cable entry and 04 nos connectors, and 01 no of 5A SP MCB all as specified and as directed.
ITEM NO. 37 :-Supply and Fixing LED street light fittings on poles /walls and including necessary GI brackets made with 40 mm dia light grade GI pipe with necessary clamps and nuts bolts suitably bended and up to 1.40 M length all as conforming to the following parameters: (i) System watt/Lumens: - Max-36 watts/total system lumen not less than 3600 lm (ii) Housing: - High pressure die cast aluminium. (iii) IP Rating: - IP 65 (iv) Front cover: - Toughened Clear Glass (v) Mounting: - Suitable for pole mounting with bracket arm 40-50mm dia, Mounting height- 5.50m to 6.50 m from GL. (vi) Finish: - Epoxy powder coated with any additional treatment for smooth and anti corrosive finish. (vii) Lamp: - High bright LED with Lens (viii) System Efficacy (lm/W) of the luminaries: - Not less than 100 lm/watt.
(ix) Colour temperature (K): - Not less than 5700 (x) Colour Rendering Index (CRI): - Not less than 74 (xi) Life: - Not less than 50000 Hrs of operation (xii) Optics: - Spread (Beam angle along the driveway) - 120°, Through (Beam angle across the driveway)- 60°, Beam pattern- Asymmetrical driveway (xiii) Control gear: - inbuilt electronic driver with APFC, PF not less than 0.90 and THD less than 20 % with operating voltage 140-270V AC, 50 Hz (xiv) Surge protection: - inbuilt surge protection minimum 5KV (xv) Heat Sink: - As per OEM's design (xvi) (a). Bidder has to compulsorily submit the LM-79 and LM-80 and third party NABL accredited lab test report conforming of technical specifications and consolidated lab report for the offered LED has to be structured in the same sequence.
ITEM NO. 38 :-Supply and fix LED bollard light in 9 W in warm white colour with IP 65 protection with all fittings complete all as specified and as directed.
ITEM NO. 39 :-M&L for twin LED aviation obstruction light luminaire, integral LED aviation light comprising of aluminium housing with polycarbonate enclosure complete all as specified and directed.
ITEM NO. 40 Supply, laying & testing PVC insulated, PVC sheathed electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm, 3 core, 1100 Volts grade (for street lights) all as specified and as directed.
EARTHING
Item No.41::- Earthing complete with Galvanised steel earth plate electrode 600 X 600 X 6 mm thick burried directly in ground [earth pit not less than 2.25 m deep below ground level] with top edge of plate not less than 1.50 m below normal ground level connected to 32 X 6mm GI Strip [Earth Lead] and GI pipe 50 mm, Medium Grade for earthing lead protection to the extent of maximum 7.5m, Earth Plate Electrode surrounded by 150mm thick packed layers of Charcoal and Common Salt filled in alternate layers, connected to the plate by means of GI Bolts & Nuts complete all as per Electrical plate No.44: 3 of SSR Part – I, connected to panel / DB including testing on completion including main earthing, Charcoal, Common Salt, PCC [1:2:4, Type B1] Pit with RCC 1:2:4, Type B1 Cover, 50 mm thick with 6 Nos, 8 mm dia TMT bars in both ways, MS frame made with 40 X 40 X 6 mm Angle Iron, MS Funnel with 20 mm bore, medium grade GI Watering pipe, wire mesh, earth work excavation, return filling, removal of surplus soil etc. complete all as specified and directed.
ROAD / PATH / CULVERT
ITEM NO. 42 :-M & L for applying evenly a tack coat with bitumen emulsion RS-1 @ 5 Kg per 10 Sqm with sprayer over existing black top surface etc complete all as specified and directed. (Make: HINCOL or equivalent)
ITEM NO. 43 :-M & L for surface dressing to existing black top surfaces applying evenly a tack coat with bitumen emulsion RS-1 @ 3 Kg per 10 Sqm with sprayer sprayer over premix bituminous macadam surfaces complete all as specified and directed. (Make: HINCOL or equivalent)
ITEM NO. 44 :-M & L for thermoplastic road marking paint, white or golden yellow, conforming to BS-3262 applied on road/pavement as in lines, dashes, arrows, letters etc, 10/15 cm in width & of thickness not less than 2mm, with and including combination of retro-reflective glass beads 250-300 gm/ Sqm all as per manufacturer's instructions complete all as specified & directed.
ITEM NO. 45 :- S & F Solar road studs aluminium alloy shell size 125x125x25mm with protection glass on two sides Model No. SE - SRLS 7501 of Shakti or equivalent, including preparation of road surface fixed with adhesive complete all as specified & fixing as per manufacturer instruction.
SEWAGE DISPOSAL
ITEM NO. 46 :- M & L for RCPC Manhole cover (32'') 25 MT (800 mm x 165 mm ) .
CHAINLINK FENCING
ITEM NO. 47: S&F PVC coated chain link fencing and complete allas specified and directed by GE. The mess size of chain link fencing shall be 50mmX50mm, the bare size of chainlink wire shall be 4mm and after PVC coating the resulting diameter shall not be less than 5.5mm. The PVC coating shall be made of virgin PVC granule i.e. it should not be recycled. The colour of PVC coating shall be approved by GE.
TELEPHONE /LAN/ TV
ITEM NO.48:- S & F of TV socket outlet one module complete all as specified and as directed.
ITEM NO.49:- &L cable TV Splitter 4 way O/G with 1-way I/C compete including mounting inside PVC box of suitable size flushed to wall all as specified and as directed.
ITEM NO.50:- MM & L coaxial cables with electrolytic grade solid bare copper conductor, gas injected physical polythylene foam insulation, with laminated aluminium tape and AI wire braid, jelly flooded and PVC jacketing in Black colour drawn in conduit and connecting and testing complete for type RG-59 cable all as specified and as directed. Note : PVC conduit and accessories shall be measured and paid separetly.
EXTERNAL FIRE FIGHTING
ITEM NO.51:-Supply, Installation, Testing and Commissioning of Electric Driven Main Fire suitable for auto operation & consisting of following: complete in all respect as required. Horizontal Split casing type, centrifugal, multistage, pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq. cm. at highest and farthest outlet at specified flow of 2280 LPM at 70 Mtr. head confirming to IS 1520-1980.Suitable HP squirrel cage induction motor, TEFC synchronous speed 1450 RPM (with permissible slip), suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-' F' insulation, confirming to IS-325-1978Common base frame fabricated out of M.S channel of suitable size, flexible coupling, coupling guard, foundation bolts and pressure gauge with valve etc. Suitable cement concrete foundation (minimum 6" above from ground floor) duly plastered, with anti vibration pads etc. complete as per manufacturer's design & standards and as per detailed specifications. Make- Lubi,/Wilo/Grundfoss/Kirloskar
ITEM NO.52:-Supply, Installation, Testing and Commissioning of Electric Driven Sprinkler Pump suitable for auto operation & consisting of following: complete in all respect as required. Horizontal Split casing type, centrifugal, multistage, pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq. cm. at highest and farthest outlet at specified flow of 2280 LPM at 70 Mtr. head confirming to IS 1520-1980.Suitable HP squirrel cage induction motor, TEFC synchronous speed 1450 RPM (with permissible slip), suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-' F' insulation, confirming to IS-325-1978Common base frame fabricated out of M.S channel of suitable size, flexible coupling, coupling guard, foundation bolts and pressure gauge with valve etc. Suitable cement concrete foundation (minimum 6" above from ground floor) duly plastered, with anti vibration pads etc. complete as per manufacturer's design & standards and as per detailed specifications. Make- Lubi,/Wilo/Grundfoss/Kirloskar
ITEM NO.53:- Supply, Installation, Testing and Commissioning of Diesel Engine Driven Sprinkler Pump suitable for auto operation and consisting of following: complete in all respect as required. Horizontal Split casing type, centrifugal, multistage pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal to ensure a minimum pressure of 3.5 kg/sq.cm. at highest and farthest outlet at specified flow of 2850 LPM at 100 Mtr. head confirming to IS 1520-1980.Suitable HP 1500 RPM, 4 stroke, cold starting type Diesel Engine with Heat Exchanger confirming to relevant BIS & IS Standards, complete with all required accessories / system, fuel oil filter, lubricant oil pump with filter, 2 Nos. starting batteries of 180 AH capacity each with suitable angle iron stand, engine starting panel having all the controls meters, gauges, tachometer, hour meters, starting switch with keys for manual starting, auto starting mechanism, 24 Volts electric starting equipment, Diesel Tank for 8 hrs continuous running of diesel engine, having minimum capacity of 200 Ltrs. (tank made out of 3mm thick M.S. Sheet with filling Cap, drain Cock, diesel indicator duly mounted on M.S. angle) exhaust pipe extended upto 1 mtr. outside pump house, duly insulated with 50 mm. thick glass wool with 1.0 mm. thick aluminium sheet cladding, exhaust residential silencer, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required
ITEM NO.54: Suitable HP 1500 RPM, 4 stroke, cold starting type Diesel Engine with Heat Exchanger confirming to relevant BIS & IS Standards, complete with all required accessories / system, fuel oil filter, lubricant oil pump with filter, 2 Nos. starting batteries of 180 AH capacity each with suitable angle iron stand, engine starting panel having all the controls meters, gauges, tachometer, hour meters, starting switch with keys for manual starting, auto starting mechanism, 24 Volts electric starting equipment, Diesel Tank for 8 hrs continuous running of diesel engine, having minimum capacity of 200 Ltrs. (tank made out of 3mm thick M.S. Sheet with filling Cap, drain Cock, diesel indicator duly mounted on M.S. angle) exhaust pipe extended upto 1 mtr. outside pump house, duly insulated with 50 mm. thick glass wool with 1.0 mm. thick aluminium sheet cladding, exhaust residential silencer, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required.M.S. fabricated Common base frame, flexible coupling, coupling guard, foundation bolts and pressure gauge with valve etc. Suitable cement concrete foundation (minimum 6" above from ground floor) duly plastered, with anti vibration pads etc. complete as per manufacturer's design & standards and as per detailed specifications. Make- Lubi/Wilo/Grundfoss/Kirloskar
ITEM NO.55:- Supplying, Installation, Testing and Commissioning of Electric Driven Pressurization Pump (Jockey Pump) suitable for auto operation and consisting of following: complete in all respects as required.Horizontal type, centrifugal end suction type pump of cast iron body and bronze impeller with stainless steel shaft, mechanical seal, gland packing and flow of 180 LPM at 70 Mtr. head confirming to IS:1520-1980.Suitable HP squirrel cage induction motor TEFC type 2900 RPM suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 class of protection for enclosure, horizontal foot mounted type with Class -'F' insulation, confirming to IS:325-1978.Common base frame fabricated out of M.S channel of suitable size, flexible coupling, coupling guard, foundation bolts and pressure gauge with valve etc. Suitable cement concrete foundation (minimum 6" above from ground floor) duly plastered, with anti vibration pads etc. complete as per manufacturer's design & standards and as per detailed specifications. Make- Lubi/Wilo/Grundfoss/Kirloskar
ITEM NO.56:- Supply and laying multistrand single core cable of size 95 sqmm all as specified and as directed. Make: Gloster/Polycab/Havells/Mescab/KEI
ITEM NO.57:- Supply and laying multistrand 3 core cable of size 10 sqmm all as specified and as directed. Make: Gloster/Polycab/Havells/Mescab/KEI
ITEM NO.58:- S& F CI foot valve 200 mm with GM working parts as per IS-4038 including all connecting fittings with gasket completa all as specified and as directed.
ITEM NO.59:- S& F CI foot valve 100 mm with GM working parts as per IS-4038 including all connecting fittings with gasket completa all as specified and as directed.
ITEM NO.60:-Supply and fix 150 mm (6") dia DI resilient seated non-return valve, flanged end in swing type design with EPDM door and with over 250 micron epoxy coating including all necessary items complete all as specified and as directed.
ITEM NO.61:- All as per item No 60 above but for 100 mm (4") dia complete all as specified and directed by Engr-In-Charge.
ITEM NO.62:- All as per item No 60 above but for 80 mm (3") dia complete all as specified and directed by Engr-In-Charge.
ITEM NO.63:- Supply and fix for 150 mm dia D.I. resilient (soft) seated gate valve with pocket less body, ss stem (AISI 410), EPDM coated di wedge 100% vaccum tight design with toroidal sealing rings & over 250 micron epoxy coating in PN16 designed to BS:5163/IS:14846 non-rising stem type with hand wheel operation complete all as specified and as directed.
ITEM NO.64:- All as per item No 63 above but for 100 mm dia complete all as specified and directed by Engr-In-Charge.
ITEM NO.65:- All as per item No 63 above but for 80 mm dia complete all as specified and directed by Engr-In-Charge.
ITEM NO.66:- M&L for 150 mm dia ductile iron pipes with flanged ends centrifugally cast Class K-9, with necessary gaskets, nut bolts and other accesories in any length, laid in trenches complete all as specified and directed by Engr-In-Charge.
ITEM NO.67:- Construction of brick masonry (full brick thick wall) valve chamber, of 1050x1050x950mm size of internal dimension, PCC work with (1:4:8) type D2 150mm thick (using 40mm grade stone aggregate) for foundation complete with 1.60mm thick MS sheet cover and frame of MS angle iron 40x40x5mm with locking arrangement and painting with one coat of red oxide primer and two coats of synthetic enamel paint all as specified shall be plastering to internal and exposed surfaces of the chamber, in CM(1:4) 15mm thick and PCC coping (1:2:4) type B-1, 50 mm thick all as specified.
ITEM NO.68:- Supply, installation, design, testing and commissioning floor mounted indoor panel cubical type of suitable size . The Panel made out of 2mm thick MS CRCA sheet and suitable size angle iron structure ,CPRI approved/Type tested compartmentalized, type of size as required including locking arrangement and powder coated paint after 7 tank cleaning process , fixed in floor with MS angle iron suitable size frame structure and grouted with PCC M-15 (Nominal mix) using 20mm graded stone aggregate with and including suitable size copper FRLS/HRFR copper wired connection, brass glands for cable entry etc complete all as specified and as directed and as following specification : - INCOMER (i) MCCB 400 Amp 4 pole 36 KA with microprocessor based release - 01 No OUTGOING (i) MCCB 250 Amps 4 pole 25 KA with microprocessor based release - 02 Nos (ii) MCCB 63 Amps 4 pole 25 KA with microprocessor based release - 01 No (iii) Digital soft starter suitable for pump mentioned at item No 1 & 2 - 02 Nos (iv) DOL/ Fully Automatic Star Delta Starter suitable for pump mentioned at item No 4 - 01 Nos(v) 600 Amps capacity copper bus bar of suitable size and required length (equal size for phase and neutral) and fixed on 04 Nos SMC/DMC/porcelain insulators - 04 Set. (vi) Digital ammeter 0-100 amps -01 No with suitable CTs (vii) Digital voltmeter of 0-500 volts-01 No (viii) LED indicator lamp RYB (set of 3)- 02 set. complete all as specified and as directed.Note: The panel shall have necessary control circuits interlinked with main fire detection panel for automatic starting and stop facility for the main fire pumps, sprinkler pumps. The jockey pump shall be provided with auto start and stop pneumatic/electrtonic controls so as to maintain 6kg/sqmm pressure all the time in the fire pumps for working under pre set conditions as desired. Main fire pump and sprinkler pums shall have auto start and manual stop facility with suitable star delta auto starters having electrical interlocking arrangements and pneumatic/electronic time relays of suitable current ratings and single phasing preventors all as specified and as directed.
INTERNAL FIRE FIGHTING
ITEM NO.70- Supply and fix Addressable manual call point break glass type with alarm LED complete all as specified and as directed.
ITEM NO.71:- Supply and fix Control Console complete all as specified and as directed.
ITEM NO.72:-Supply , installtion, testing & commissioning of cable for fire detection and alarm system with 2 core annealed tinned copper conductor PVC sheathed,flexible, unarmoured 2 core cable 1.5 sqmm as per specifications in existing conduit complete as required complete all as specified and as directed.
ITEM NO.73:- Supply and fix for 100 mm dia D.I. resilient (soft) seated gate valve with pocket less body, ss stem (AISI 410), epdm coated di wedge 100% vaccum tight design with toroidal sealing rings & over 250 micron epoxy coating in PN16 designed to BS:5163/IS:14846 non-rising stem type with hand wheel operation complete all as specified and as directed.
ITEM NO.74:-Supply and fix 100 mm dia DI resilient seated non-return valve, flanged end in swing type design with EPDM door and with over 250 micron epoxy coating including all necessary items including taking down old unserviceable one complete all as specified and as directed.
ITEM NO.75:- Supply only of fire extinguiser ISI marked CO2 type Fire Extinguisher 3.0 KG capacity conforming to IS : 15683 :2006 (old IS : 2878) made from seamless cylinder conforming to IS : 7285 duly approved by chief controller of explosive , Nagpur fitted with ISI Marked Controlled valve conforming to IS : 3224 , high pressure 1 mtr long discharge hose and horn complete with initial gas charged with carrying handle and wall mounting bracket, , suitable for operating between 30 degree centrigrade to + 55 degree centigrate, Fire Rating Class - 138 all as specified and as directed.
ITEM NO.76:- Supply only of stored pressure fire extinguiser ISI marked powder type Fire Extinguisher 4 KG capacity suitable for Class "A", "B", "C" Fire consisting with discharge hose and nozzle of welded cylinder, squeeze lever discharge valve fitted with pressure indicating guage, internal discharge tube, discharge nozzle suspension bracket conforming to IS : 15683 :2006 (old IS : 2878) duly charged with ISI Marked Mono Ammoniumphosphate base ABC powder conforming to IS : 14609 and pressurized with Nitrogen Gas, suitable for operating between 30 degree centrigrade to + 55 degree centigrate, Fire Rating Class - 1A & 13B all as specified and as directed.
ITEM NO.77:- Supply only of Fire Extinguisher of lSl Marked Water Stored Pressure type Fire Extinguisher 9 Itrs. capacity consisting of welded cylinder, squeeze lever discharge valve fitted with pressure indicating guage with internal discharge tube, discharge nozzle suspension bracket, conforming to lS: 15683:2006 (old IS : 6234) duly charged wiih purged water and pressurized with Nitrogen Gas, suitable for operating between + 50 degree Centigrade to +55 degree Centigrade, Fire Rating Class - 3A all as specified and as directed.
ITEM NO.78:- Supply only of Fire Extinguisher Mechanical Foam type ISI Marked Foam (AFFF) type Fire Extinguisher 9 ltrs capacity fitted with Forged Brass squeeze lever discharge valve, conforming to IS : 15683 :2006, complete with initial refill consisting of ISI Marked CO gas cartridge of 60 gms capacity conforming to IS 4947 and ISI Marked AFFF conforming to IS : 4989, suitable for operating between + 50 degree centrigrade , Fire Rating Class - 3A & 34B all as specified and as directed.
ITEM NO.79:- Supply only of stored pressure fire extinguiser ISI marked powder type Fire Extinguisher 9 KG capacity suitable for Class "A", "B", "C" Fire consisting with discharge hose and nozzle of welded cylinder, squeeze lever discharge valve fitted with pressure indicating guage, internal discharge tube, discharge nozzle suspension bracket conforming to IS : 15683 :2006 (old IS : 2878) duly charged with ISI Marked Mono Ammoniumphosphate base ABC powder conforming to IS : 14609 and pressurized with Nitrogen Gas, suitable for operating between 30 degree centrigrade to + 55 degree centigrate, Fire Rating Class - 1A & 13B all as specified and as directed.
ITEM NO.80:-Supply and fix fire bucket with sand as per IS:2546 with nomenclature written on it, provided with suitable size of stand all as specified and as directed.
ITEM NO.81:- S&F auto-illuminated (glow-in-dark) sign board with red colour background with appropriate symbol, made up of acrylic sheet for fire escape in minimum 15 cm x 30 cm size to be pasted on wall with high quality adhesive or to be hanged with s.s. hook-chain system all as specified and as directed.
ITEM NO.82:- S &F MS ERW pipe heavy grade 15 mm Bore including tee, bend and all connection accesorries as per specified and as directed
ITEM NO.83:- Supply and fix 150 mm dia DI resilient seated non-return valve, flanged end in swing type design with EPDM door and with over 250 micron epoxy coating including all necessary items including taking down old unserviceable one complete all as specified and as directed.
DG SET
ITEM NO. 84 :- Supplying, installing, commissioning & testing of Silent engine generating set of capacity 160 kVA with accoustic enclosure as per new CPCB-II norms of emmission control, 415 volts, 3 phase 0.8 power factor 50 Hz, 1500 RPM self excited self regulated brushless AC generator including accoustic enclosure suitable for ambient condition and conforming to condition under IS 4722, BS 5514/ 2613 /5000 with suitable AMF Panel as per manufacturer's recommendations complete all as specified and directed with the following :- (A) Alternator :- Standard design alternator rated at 160 kVA net output at site after considering de-rating as per site conditions at 0.8 (lag) power factor AC, 3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self excited self regulated screen protected drip proof IP 23 enclosure brushless design with winding in pole faces, insulating class 'H' and voltage regulation of +/- 1% at rated voltage from no load to full load. The alternator shall be conforming to BS 2613/5000 and shall be imposition to generate supply with frequency regulation with in +/- 1% tolerance. The alternator will be suitable for tropical climate and shall generally conform to BS - 2613/5000/ IS – 4722.The Alternator shall be:- i) Insulation class - 'H‘ ii) Temperature rise Class - 'H‘ iii) Excitation : Self Excited iv) Regulation performance: The voltage is kept constant with +/- 1%, manual voltage adjustment within +/- 5% v) Frequency regulation +/- 1%.
(B) Diesel Engine: - Adequate capacity of Diesel engine as approved by the accepting officer basing on manufacturers technical details water cooled to drive independently above alternator and after considering de-rating as per site conditions after generating and reducing power consumed by accessories directly coupled through flexible coupling multi cylinder multi stroke direct injection, cold starting 1500 RPM, as per relevant ISI/BS - 5514 with an overload capacity of 10% for half an hour in 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operation salient features of accessories shall be as under :- i) Fly wheel with housing ii) Cooling system :- Moulded radiator with fan & belts iii) Cooling Water pump : - Centrifugal type belt driven iv) Exhaust System :- Exhaust System complete with exhaust piping with ERW MS pipe upto & outside and 1meter away from the enclosure, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclosure. Exhaust gas turbo charger type. Exhaust manifold Silencer : Residual type Bellows v) Fuel System :- Fuel injection system with fuel injectors, fuel injection solenoid switch controlled by electronic governor for 1% speed /frequency regulation, Fuel filters, Fuel hoses. vi) Lub oil System :(a)Lubricating oil filter (b) Lubricating oil pump vi) Air Intake System : (a) Air intake Manifold - Air cleaner dry type vii) Governor :- Electronic Governor viii) Starting System :- Electric Self starter with maintenance free battery including battery charging alternator.
vii) Batteries :- Batteries of maintenance free of capacity as recommended by the manufacturer complete with copper conductor multi stranded leads of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electrolyte all as specified and Starter gear ring Start and stop push button, Ignition key / Switch Handling and operation : Salient features of accessories shall be as under: Radiator with blower fan Corrosion inhibitor coolant, Paper element filters for fuel, lub oil and by pass, Electronic governor controlled direct fuel injection system Fly wheel housing and fly wheel viii) Generator Monitoring Panel : - Comprising of all standard items as mentioned under this schedule or asper standard practice iginiton key switch and start / stop arrangement, indications for Engine parametes, hour run meter, RPM meter, Engine oil pressure indicator, water/coolent temparature indicator, Battary volt display. ix) Safety Controls : - Engine low lube oil pressure high water temparature and over speeding of engine xii) Coupling arrangement : - Flexible coupling, fly wheel to suit flexible coupling x) Accessories :- AVM Pads built in enclosure and for entire unit on platform. xi) Base Frame : - Should be provided as OEM norms xv) Fuel Tank :- HR sheet top and bottom with caliberated level indicating arrangement, stop cock, drain plug, fuel pump of suitable capacity complete on a common base out side the accoustic enclosure.
(C) CONTROL PANEL :- The standard microprocessor based control panel shall be fabricated made out of CRCA sheet and powder coated in side and out side and shall display as follows:- (i) Voltage of all Three phases, (ii) Current of all Three phases, (iii) Frequency, (iv) Bus bar Chamber with aluminium busbar of cap 300 Amps - 04 Nos, (v) C.T. 100/5 Amps - 03 Nos. (vi) MCCB TPN, of appropriate capacity - 01 No .
D) Accoustic Enclosure:- Manufactured by OEM suitable for 160 KVA DG Set (i) NAL approved as per CPCB (ii) It Should be as per latest rules and regulations of Ministry of Environment and Forest and Pollution control board (iii) The generating set battaries and control panel should be inside the enclosure. (iv) Fuel tank should be out side the enclosure in the sub station building. (v) Construction Details/specification are as follows: a) Outer body :- CRCA Sheet of 1.6mm thick b) Doors :- CRCA sheet of 1.6 mm thick c) Sound Insulation :- As per OEM Norms vi) The accoustic should be composite in construction and fully assembled integral unit vii) The batteries should be placed inside the enclosure beside the DG Set on a suitable insulated platform viii) The DG Set should be provided with external Emergency stop push button. ix) The enclosure should be suitably illuminated by LED Lamp fittings. x) The noise level should be 75 dba at 1m under free field conditions. xi) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Gen set Green. The base frame should be painted with epoxy based black shade. (E) ENGINE INSTRUMENTS PANEL :- All relevant Para meter shall be conventionally displayed on complete panel there by providing easy monitoring of lubricant oil pressure, coolant temperature, battery charging ammeter, RPM and Watt Hour meter, Fuel Level, starting button/switch etc.
ITEM NO.85: M&L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to galvanised iron or steel earth lead MS flat 32 x 6 mm by means of nuts, bolts, check nuts and washers of galvanised iron or steel, earth wire protected by galvanised iron pipe 50 mm dia (light grade) and connected to main switch board or main control panel as directed and as specified including concrete pit in PCC (1:3:6) type C1 pre-cast RCC cover slab 5 cm thick of size as shown reinforced with 8 mm dia TMT / deformed bars 100 mm c/c both ways including one handle made of 12 mm dia MS bars of length 500 mm, funnel, wiremesh 20 mm bore galvanised iron pipe medium grade for watering, charcoal and salt in alternate layers including necessary earth work complete all as shown in elect plate No. 3 of SSR Part I, all as directed by Engineer-in-Charge.
ITEM NO.87: Supply, installation, design, testing and commissioning floor mounted outdoor feeder panel Board cubical type . The Panel made out of 3 mm thick MS CRCA sheet and angle iron structure of suitable size ,CPRI approved/Type Tested compartmentalized, type of size as required including locking arrangement and powder coated paint after 7 tank cleaning process fixed in floor with MS angle iron frame structure and grouted with PCC M-15 (Nominal mix) using 20mm graded stone aggregate with and including suitable size copper FRLS/HRFR copper wired connection, brass glands for cable entry etc suitable for:- INCOMING : 200 Amp MCCB 415 Volt, 50Hz, AC, 4 pole, 36 KA, with microporcessor based control - 01 No OUTGOING: (i) MCCB 160 Amp, 415V, AC, 50Hz, 4 pole, 25 KA, with thermal magnetic release - 02 No (ii) MCCB 125 Amp, 415V, AC, 50Hz, 4 pole, 25 KA, with thermal magnetic release - 01 No (iii) MCCB 40 Amp, 415V, AC, 50Hz, 4 pole, 25 KA, with with thermal magnetic release control - 03 Nos (iv) 300 Amps capacitor copper bus bar of suitable size and required length (equal for phase & neutral) and fixed on 04 Nos SMC/DMC/Porcelane insulators- 04 set (v) Digital time switch-01 No (vi) Contactor 40 Amp- 01 No (vii) Digital Ammeter 0-200 Amps-01 No with suitable CTs (viii) Digital Voltmeter 0-500 Volts - 01 No (ix) LED indicator lamp RYB (set of 3) - 02 set complete all as specified and as directed.
ITEM NO. 88 :- Design, supply, installation, testing and commissioning, of electrically operated, automatic passenger lift of capacity to carry 08 passengers (544 Kg) at a speed of 1.5 metre/sec, suitable to serve for G+16 floors (17 Floor, 17 Stops) with AC Variable Frequency Regenerative(Closed loop) control drive, equipped with low noise Gearless machine, installed in machine room on roof top complete with all standard accessories and control panel, Full collective Group operation with or without attendant, centre opening doors with door drive automatic operation, stainless steel landing doors. Automatic Rescue Device (ARD), 3D infrared sensor in full height of door, built in announcing system with intercom (in machine room and near ground floor and in car), stainless steel car enclosure complete all as specified and directed with the following :-
(a) Controller Type : Micro Processor controlled Drive VR regenerative (Closed Loop) ACD3-MR (b) Drive : VF Regenerative (Closed Loop) (c) AC Power Supply : 400/415 Volts (3 Phase 4 wire system) (d) Operation : Full Collective Group Operation (e) Car Group : One car (f) Machine PM (Permanent Magnet) Gearless (Located above shaft in machine room) (g) Traction media : Polyurethane coated steel belts /Steel wire ropes. (h) Car Finish: Stainless steel cool breeze or equivalent design approved by GE for Rear Middle. Rear Corner, side, Front & False ceiling panels.rails. (j) False ceiling type : Stainless steel # 4 (Hairline) along with fitment of car lights LED light fittings. (k) Ventilation : Axial flow fan. (l) Hand Rails : Stainless steel mirror finish handrails on rear sides in car panels. (m) Flooring : Aluminium Chequered Plate with granite flooring (n) Car Door / Land Doors Finish : Stainless steel # 4 (Hairline). (o) Car Dimensions (internal) (W x D x H - mm) : 1300 x 1100 x 2200 mm. (p) Car and Hoist way Door type : Central Opening Doors.
(q) Door Opening (WxH-mm) : (800x2000) mm. (r) Door operator : DC door operator. (s) Car operating panel : Square flush painted buttons in stainless steel # 4 (Hairline). (t) Car position indicator : Dot matrix (Red LED) scrolling display. (u) Hall fixtures : 16 segment display hall button. (v) Hall fixtures face plate : Pan type in Stainless steel # 4 (Hairline). (w) Hall button arrangement : Hall button with FPI. (x) Automatic Rescue Device with maintenance free batteries (ARD). (y) Standard Features : Anti nuisance car cell protection, overload device, nudging, independent service belt inspection device. Emergency Fireman's service. Emergency car light unit, Infrared curtain protection, door time protection, emergency alarm button, extra door time of lobby and parking, door open/close button, manual rescue operation, belt inspection drive and auto fan cut off. (z) Intercom arrangement between ground floor machine room and car. (aa) One hour fire rating for all landing doors. (ab) Voice Synthesizer. Note: As per architectural drawing lift shaft for both 08 passengers lifts are not side by side.
ITEM NO. 89 :- Design, supply, installation, testing and commissioning, electrically operated, automatic passenger lift of capacity to carry 13 passengers (884 Kg) at a speed of 1.5 metre/sec, suitable to serve for G+16 floors (17 Floors and 17 Stops) with AC Variable Frequency Regenerative(Closed loop) control drive, equipped with low noise Gearless machine, installed in machine room on roof top complete with all standard accessories and control panel with or without attendant, centre opening doors with door drive automatic operation, stainless steel landing doors. Automatic Rescue Device (ARD), 3D infrared sensor in full height of door, built in announcing system with intercom (in machine room and near ground floor and in car), stainless steel car enclosure complete all as specified and directed with the following :-
(a) Controller Type : Micro Processor controlled Drive VR Regenerative (Closed Loop) ACD3-MR (b) Drive : VF Regenerative (Closed Loop) (c )AC Power Supply : 400/415 Volts (3 Phase 4 wire system) (d) Operation : Full Collective (e) Car Group :One car (f) Machine PM (Permanent Magnet) Gearless (Located above shaft in machine room) (g) Traction media : Polyurethane coated steel belts /Steel wire ropes. (h) Car Finish: Stainless steel cool breeze or equivalent design approved by GE for Rear Middle. Rear Corner, side, Front & False ceiling panels. Mirror : Full size mirror to be provided at the rear side of car inside above hand rails. (j) False ceiling type : Stainless steel # 4 (Hairline) along with fitment of car lights LED light fittings. (k) Ventilation : Axial flow fan. (l) Hand Rails : Stainless steel mirror finish handrails on rear sides in car panels. (m) Flooring : Aluminium Chequered Plate with granite flooring (n) Car Door / Land Doors Finish : Stainless steel # 4 (Hairline).
PILE WORK
ITEM NO. 91: M&L Chiselling/ chipping/ breaking the laitenance concrete of pile upto cutoff level upt to the receipt of dense concrete and dresing the pile head so as to recieve the form work etc using suitable tools and plants and exposing the pile reinforcement including removal of debris from site complete for 600mm dia piles all as specified and directed.
ITEM NO.92: M&L Carrying out initial load testing on 600mm dia pile on following tests all as per IS comnplete all as specified and directed including necessary anchoring and support piles suitable load/ size to be casted as required:
(a) Compression Test
(b) Pull out Test
(c) Lateral Test
ITEM NO.93: M&L Carrying out routine load testing on 600mm dia pile of following tests all as per IS complete all as specified and as directed :
(a) Compression Test
(b) Pull out Test
(c) Lateral Test
ITEM NO.94: M&L Carrying out Pile Integrity testing on 600mm dia piles all as per IS complete all as specified and as directed
ITEM NO.95: M&L pile capacity by conducting dynamic load test by pile driving analyzer (PDA) all as per IS complete all as specified and as directed
SCHEDULE 'A' PART -XX (COMPREHENSIVE MAINTENANCE OF LIFT WORK)
(a) AMC on 1st year after expiry of defects liability period ( for 2 Lifts x 12 Months)
(b) AMC on 2nd year after expiry of defects liability period ( for 2 Lifts x 12 Months)
(c) AMC on 3rd year after expiry of defects liability period ( for 2 Lifts x 12 Months)
Notes for Serial Item Nos -95 above :- (i) The rate quoted are deemed to include all/any charges related to renewal of lift license and lift insurance from State Govt/Other Agency.(ii) The rate is inclusive of all items as required at site including any spares to keep the lift operated all the time.(iii) The Maintenance of the lifts should be done through the OEM.(iv) The contractor should attend the complaint/breakdown immediately.(v) Maintenance of the lift should be done as per manufacturer instructions
Narayan Kumar Infrastructure Pvt Ltd
KAKALI ENTERPRISE
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid