Executive Engineer ED-II JPDCL Jammu
Office of the Executive Engineer ED-II JPDCL Jammu
Rate contract for creation of 250KVA, 400KVA, 630KVA Substations at different locations within jurisdiction of Electric Division-II Jammu during the FY 2022-23 (Key material like Poles and Distribution Transformer shall be provided by the Department)
2022_PDD_178257_1
Enit 13A of 2022 dated 07-07-2022
Open Tender
Electrical Works
Lump-sum
60 days
Within Jurisdiction of the XEN ED- II JPDCL Jammu
Please refer Tender documents.
3 documents required · 3 mandatory
₹1,000
Executive Engineer ED II JPDCL Jammu
₹28,500
13 Sept 2022
8 Jul 2022
23 Jul 2022
8 Jul 2022
22 Jul 2022
8 Jul 2022
8 Jul 2022 - 22 Jul 2022
Amount
Creation of 11/0.433kV, 250KVA , 3-phase Distribution Substation
Installation, Testing & commissioning of 11/0.433 KV, 250 KVA 3-Phase Distribution Transformer including Transportation from Divisional Store at Miran Sahib to erection site. (11/0.433kV, 250 KVA , 3-phase Distribution Transformer shall be provided by the Department)
Erection of 9 Mtr Long ST Pole (ST-410 SP33) including Transportation from Divisional Store at Miran Sahib to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. (9 Mtr Long ST Pole ST-410 SP33 shall be provided by the Department)
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 240 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 240 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
11kV Polymeric composite Disc Insulator 12kV with Fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Pole mounted LT Distribution Box for 250 KVA DTR with 2 No. Triple Pole MCCB of 300 Amp with adjustable overload release of (80-100%) for incomer & & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Description of Work / Item(s)
Amount
Creation of 11/0.433kV, 400KVA , 3-phase Distribution Substation
Installation, Testing & commissioning of 11/0.433 KV, 400 KVA 3-Phase Distribution Transformer including Transportation from Divisional Store at Miran Sahib to erection site. (11/0.433kV, 400 KVA , 3-phase Distribution Transformer shall be provided by the Department)
Erection of 9 Mtr Long ST Pole (ST-410 SP33) including Transportation from Divisional Store at Miran Sahib to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. (9 Mtr Long ST Pole ST-410 SP33 shall be provided by the Department)
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
11kV Polymeric composite Disc Insulator 12kV with fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of Pole mounted LT Distribution Box for 400 KVA DTR with 2 No. Triple Pole MCCB of 400 Amp with adjustable overload release of (80-100%) for incomer & & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Construction of Concrete-Cement (1:2:4) Platform (8x8x3) & 3feet below ground level ) for 400 KVA SubStation along with the mesh fencing (with two coats of metal oxide & Al. Paint) around the Periphery. (complete Job)
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Description of Work / Item(s)
Amount
Creation of 11/0.433kV, 630KVA , 3-phase Distribution Substation
Installation, Testing & commissioning of 11/0.433 KV, 630 KVA 3-Phase Distribution Transformer including Transportation from Divisional Store at Miran Sahib to erection site. (11/0.433kV, 630 KVA , 3-phase Distribution Transformer shall be provided by the Department)
Erection of 9 Mtr Long ST Pole (ST-410 SP33) including Transportation from Divisional Store at Miran Sahib to erection site, excavation of pit and back filling of soil & consolidating by ramming, watering etc. Including painting with two coats of Red Oxide and Al. Paint for smooth surface. (9 Mtr Long ST Pole ST-410 SP33 shall be provided by the Department)
Supply & Fixing of Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
Supply, Installation, Testing & Commissioning of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Supply, Installation, Testing & Commissioning of 11 kV Horn Gap Fuse Set 3 Phase 200A
Providing & Fixing of Single Phase PVC Cable 400 mm² ,1.1K V Grade, PVC Insulated Stranded Un-Armoured FRLS type alongwith Al. Thimbles for 400 mm² Cable termination with four colored PVC Tapings to distinguish the LT Phases and the Neutral. (2 Ckt)
11kV Polymeric composite Disc Insulator 12kV with Fitting, min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply, Transportation, Fabrication & Fixing of MS Channel Iron, Cross arms, Angle Iron Braces, Clamps etc duly fabricated, red oxide & aluminium paint coated including all necessary Nut & Bolts & Washers etc.
Providing of Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Providing & Fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Providing & Fixing of LT Distribution Box with 2No 630Amp Triple Pole MCCB for incomer with adjustable overload release of (80-100%) & switch fuse unit for Out Going 2No Ckts. including Busbar arrangements for Phases & Neutral of EC Grade Aluminium,PVC Insulated Sleeved Busbar of required load handling capacity with colour code for Phases and Neutral differentiation, including Aluminium thimbles of required sizes for proper termination etc.
Construction of Concrete-Cement (1:2:4) Platform (8x8x3) & 3feet below ground level ) for 630 KVA SubStation along with the mesh fencing (with two coats of metal oxide & Al. Paint) around the Periphery. (complete Job)
Providing & Fixing of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Providing & Fixing of Wedge Connectors / PG Clamps
Providing & Fixing of Danger Plates with Clamps
Providing & Fixing of Anti Climbing device with Clamps
Providing of Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
M/S NEW TRIKUTA TECHNOCRATES
NEW ALLIED TRADERS
M/S SWASTIC ELECTRICAL CONTRACTOR AND SUPPLIERS
M/S NEW TRIKUTA TECHNOCRATES
NEW ALLIED TRADERS
M/S SWASTIC ELECTRICAL CONTRACTOR AND SUPPLIERS
M/S NEW TRIKUTA TECHNOCRATES
NEW ALLIED TRADERS
M/S SWASTIC ELECTRICAL CONTRACTOR AND SUPPLIERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .