Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹10.5 LAccepted-Finance | L-1 | Accepted-Finance Accept | |
| 2 | Rejected-Technical | - | Rejected-Technical Technical BID not found in order |
Tender Value
₹10.3 L
EMD Value
₹20,523
Closing Date
24 May 2025, 3:00 pmClosed
Office of the CE (E) BSNL Bhopal
MIG- V-11-14, C Old Saket Nagar Bhopal 462024 MP
Servicing and repairing of air conditioning units (Split Window type) on call basis in BA Gwalior under BSNL Electrical Division Bhopal
2025_BSNL_228609_2
27/NIT /CEE/BSNL-BPL/2024-25
Open Tender
Electrical Works
Item Rate
730 days
BSNL Electrical Division Bhopal
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
The Account officer (A nd B) CGMT Bhopal (M.P.)
₹20,523
Yes
29 Jul 2025
17 May 2025
29 May 2025
17 May 2025
24 May 2025
17 May 2025
General Servicing of 1.5 /2.0 TR WAC/SAC units at site of different make I/c removing from existing position if reqd., dismantling of faulty parts, cleaning the air filter, cleaning the condenser and evaporator coil with help of caustic soda soap solution, lubrication of moving parts, complete checking, testing and minor faults rectification i/c replacement of knobs/ wiring kit (if required), setting of thermostat, preparing report including tightness of all electrical connections from SP MCB in DB to DP MCB/Plug & socket to TDR to AC unit etc as reqd.
Charging of Refrigerant gas R-22/R-410A/R-32 up to specified pressure(as per manufacturer's recommendation) in following capacity AC units and pressure testing by nitrogen, vaccumisation for 2 hours, purging with gas and testing commissioning of the AC unit etc. as reqd. Note : One job consists of charging of Gas in one compressor i.e.. One complete air conditioning circuit only.
a) 1.5 TR WAC/ Split AC
b) 2.0 TR WAC/ Split AC
Replacement of the following capacity rotary type compressor I/c dismantling of the existing fulty compressor from AC unit , to and fro transportation charges and I/T/C of compressor in existing WAC / Split AC etc complete as required. Note: The agency has to provide one year guarantee for every replaced compressor along with Test Certificate / Invoice of Purchase from authorized dealer, Faulty Compressor shall be the property of contractor.
Replacement of the following capacity reciprocating type compressor I/c dismantling of the existing faulty compressor from AC unit , to and fro transportation charges and I/T/C of compressor in existing WAC / Split AC etc complete as required. Note: The agency has to provide one year guarantee for every replaced compressor along with Test Certificate / Invoice of Purchase from authorized dealer, Faulty Compressor shall be the property of contractor.
Replacement of the following items/accessories in the existing AC Units in place of faulty/unserviceable parts i/c dismantling of the faulty, fixing the new item and testing, connection etc. complete as reqd.
a)Thermostat
b) Starting Capacitor ( 80-100/120 mfd)
c) Running Capacitor ( 36 / 40 / 60 mfd )
e) Fan Motor Capacitor (4/6 mfd)
f) Blower/Fan Blade
Replacement of condenser / Blower fan motor for 1.5 / 2 TR Window/Split A.C unit in lieu of damaged i/c connection etc as required.
Provision of Top up of R-22 gas in existing Window A.C /Split A.C units, i/c flushing, testing etc. as required.
Repairing of different makes and models of Power card (PCB) Indoor/Outdoor and Replacement of faulty parts i.e diodes,resistors,transistors etc. including dismantling and fixing the same connection, testing etc. complete as required.
P/F following size refrigerant copper piping i/c making joints with existing covering with polystyrene insulation i/c cutting, brazing, jointing, bends, sockets etc. as reqd.er, Faulty Compressor shall be the property of contractor.
Rewinding of existing Blower/Condenser fan motor for 1.5/2.0 TR W/SAC unit i/c replacement of bush i/c oiling ,greasing etc. as reqd.
Supplying and laying of one number PVC insulated & PVC sheathed Copper conductor unarmoured power cable of 1.1 KV grade of size of following size as mentioned below.
a) 3 x 2.5 Sqmm
Supplying and fixing 25 mm dia. 2 mm thick threaded PVC Pipe suitable for drain water on exisitng Tray / on wall with suitable clamps etc. compelte as required
P/F 12mm thick Exterior grade ISI mark both side laminated particle board for closeing of extra space of AC unit i/c fixing the same with screw ,complete etc. as reqd.
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
a) Single Pole
b) Double Pole
Supplying & Fixing of PCB card of suitable for invertor Split type AC unit of capacity 1.5 TR including testing, commissioning etc. complete as required.
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .