Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.3 LAccepted-AOC NO 99 IE DG INDUSTRIAL ESTATE DOLLYUNJ POST BOX NO 554 JUNGLIGHAT POST SRI VIJAYA PURAM 744 103 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744103 | L1 | Accepted-AOC Lowest | |
| 2 | L2₹28.3 L+₹49,170 (1.77%)Rejected-Finance 1 TROPICAL REFRIGERATION PHONIX BAY PORT BLAIR PORT BLAIR ANDAMAN NICOBAR 744101 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹28.5 L+₹66,910 (2.40%)Rejected-Finance | L3 | Rejected-Finance Not Lowest | |
| 4 | L4₹29.4 L+₹1.6 L (5.74%)Rejected-Finance 365 B 10 HENRY COMPLEX MATHIYAS NAGAR KP ROAD NAGERCOIL KANNIYAKUMARI DISTRICT 629001 | KANNIYAKUMARI | TAMIL NADU | 629001 | L4 | Rejected-Finance Not Lowest | |
| 5 | L5₹29.6 L+₹1.8 L (6.38%)Rejected-Finance 30 M A ROAD M A ROAD PHOENIX BAY SOUTH ANDAMAN ANDAMAN NICOBAR 744102 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744102 | L5 | Rejected-Finance Not Lowest |
Tender Value
₹29.3 L
EMD Value
₹58,600
Closing Date
23 Feb 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GARRISON ENGINEER HADDO
GARRISON ENGINEER HADDO Military Engineer Services Haddo Post Port Blair Andaman and Nicobar 744102
ADDITION AND ALTERATION TO LT PANEL AND CONNECTED CABLES AT CG AREA UNDER GE HADDO PORT BLAIR
2022_MES_505877_1
8604/GE/H/PB
Open Tender
Civil Works
Item Rate
180 days
GE Haddo Port Blair
Class D Category b (i)
9 documents required · 9 mandatory
₹500
GE Haddo
₹58,600
9 Mar 2022
4 Feb 2022
28 Feb 2022
4 Feb 2022
23 Feb 2022
18 Feb 2022
4 Feb 2022 - 14 Feb 2022
60 days
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 m in depth, for foundation etc., or for foundation, laying of cables/pipes lines etc not exc. 10 Sqm on plan and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm each as in soils complete all as specified and as directed.
Removing excavated material (soils) to a distance not exceeding 50 metres and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and as directed.
M&L for LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade, laid in trenches/floors/ducts or fixed on poles/walls with suitable clamps/saddles or drawn through pipes etc., including connecting up with suitable size of lugs, glands and jointing material complete of following cross sectional area:-
3½ Core 70 Sqmm
3½ Core 95 Sqmm
3½ Core 120 Sqmm
3½ Core 240 Sqmm
3½ Core 300 Sqmm
3½ Core 400 Sqmm
M&L for HDPE DWC (Double wall corrugated) pipe of size 77mm (Outer diameter) x 63mm (Inner diameter) along with connected accessories like couplers, bends, end caps etc., laid in trenches/floors/ducts or fixed on poles/walls for as in protection of LT/ HT cable complete all as specified and as directed.
M&L for HDPE DWC (Double wall corrugated) pipe of size 120mm (Outer diameter) x 103mm (Inner diameter) along with connected accessories like couplers, bends, end caps etc., laid in trenches/floors/ducts or fixed on poles/walls for as in protection of LT/ HT cable complete all as specified and as directed.
Supply and laying GI Pipe, 100mm dia, medium grade in road crossing/ obstructions complete all as specified and as directed. Note: Including cutting of exisitng road and making good with shalimar patch
M&L for plain cement concrete (1:2:4) type B1 (using 20mm graded stone aggregate) as copings,of poles including weathering, slightly rounded or chamfered angles and throating including necessary form work, exposed surfaces of concrete finished even and smooth without using extra cement complete all as specified and as directed.
M&L for earthing complete with GI earth plate electrode of size 600mmx600mmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of the earth plate not less than 1.5m below normal ground level connected to 32x6mm GI earth strip as earth lead connected by means of bolts, nuts, washers and check nuts made out of galvanised iron or steel all as shown on electrical plate No. 3 of SSR Part-I connected to common earth dolly including testing on completion complete all as specified and directed. NOTES: 1) The unit rate shall also include for earth work in any type of soil, PCC (1:3:6) type C1 chamber, pre-cast RCC (1:2:4) type B-1 using 20mm graded stone aggregate cover 50mm thick reinforced with TMT bars 8mm dia @ 100mm c/c both ways, funnel with watering pipe 20mm dia medium grade, GI protection pipe light grade 40mm dia and wire mesh complete in addition to item No. 1(a) to (e) of preamble (notes) under sub-heading earthing, specified on Sl. Page Nos. 422 & 423 of SSR Part-II. 2) Earthing lead and GI protection pipe beyond 7.5m will be measured and paid separately.
S&F Galvanised iron strip 32x6mm buried in ground or fixed to walls/poles with necessary clamps, bolts and nuts complete all as specified and as directed.
S&F Indoor type LT panel / LT pillar box of dimensions 2.4m x 1.3m x 0.5m size with following specifications. Fabrication Details : CPRI approved Main frame 3mm thick CRCA sheet, partition sheets / covers / doors of 3 mm thick CRCA sheet, gland plates 3mm thick MS sheet (undrilled), base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP-54 and locking arrangements including taking down old unserviceable LT panel complete all as specified and as directed. Bus bar details: Material shall be aluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 40x20mm aluminium flat, neutral 40x10mm aluminium flat and bus bar support of epoxy type. Painting Details : Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer and marking of details of capacity/ rating/ incoming/ outgoing/ danger notice board in capital English alphabets with red colour radium sticker of required size.
Accessories for Pillar Box: (i) 0-500V Digital voltmeter - 01 No (Flush type) (ii) 0-500A Digital Ammeter - 01 No (Flush type) (iii) Indication Lamps (LED) RYB - Set of 03 Nos. (iv) Incomer:- 400A, 4 pole, Changeover Switch Make:L&T, Cat No. CO44000OOOO -1 No. (v) Outgoing:- (i) 250A, 3 pole, MCCB, 36kA, Make: L&T, Cat No. CM98060OOO -2Nos. (ii) 125A-160A ,3 pole,MCCB, 30kA, Make: L&T, Cat No. CM90678OOLO -5No. (iii) 100A, 3 pole, MCCB, 10kA, Make: L&T, Cat No. CM98922OOOO -2Nos. (iv) 63A, 3 pole, MCCB, 30kA, Make: L&T, Cat No. CM97894OOJ2 -4Nos. NOTES: (i) The unit rate quoted is deemed to include the cost of MCCBs, Volt meter, Ammeter, Indication lamps and connected control wiring with 2.5Sqmm FRLS copper conductor necessary spreader links, lugs, glands and connecting of cables as per site conditions and complete all as specified and as directed. (ii) Drawings must be approved by Engineer-in-Charge before fabrication of LT Panel.
S&F Out door LT panel / LT pillar box of dimensions 1.6m x 1.4m x 0.9m size with following specifications. Fabrication Details : CPRI approved Main frame 3mm thick CRCA sheet, partition sheets / covers / doors of 3mm thick CRCA sheet, gland plates 3mm thick MS sheet (undrilled), base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP-65 and locking arrangements including taking down old unserviceable LT panel complete all as specified and as directed. Bus bar details: Material shall be aluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 50x12mm aluminium flat, neutral 50x12mm aluminium flat and bus bar support of epoxy type. Painting Details : Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer and marking of details of capacity/ rating/ incoming/ outgoing/ danger notice board in capital English alphabets with red colour radium sticker of required size.
Accessories for Pillar Box: (i) 0-500V Digital voltmeter - 01 No (Flush type) (ii) 0-500A Digital Ammeter - 01 No (Flush type) (iii) Indication Lamps (LED) RYB - Set of 03 Nos. MAKE: L&T / BINAY/ ELMEASURE (iv) Incomer:-400A, 4 pole, Changeover Switch Make:L&T, Cat No. CO44000OOOO -1 No. (v) Outgoing:- (i) 250A, 3 pole, MCCB Make: L&T, Cat No. CM98060OOO -3 Nos. (ii) 125A,3 pole,MCCB Make: L&T, Cat No. CM90678OOLO -3 No. (iii) Astro Timer Switch for Street Light/PTL/Bollard Light Control. Make: L&T, Cat No AUTS02AST00- 1 No NOTES: (i) The unit rate quoted is deemed to include the cost of MCCBs, Volt meter, Ammeter, Indication lamps and connected control wiring with 2.5Sqmm FRLS copper conductor necessary spreader links, lugs, glands and connecting of cables as per site conditions and complete all as specified and as directed. (ii) Drawings must be approved by Engineer-in-Charge before fabrication of LT Panel.
S&F Out door LT panel / LT pillar box of dimensions 1.6m x 1.4m x 0.9m size with following specifications. Fabrication Details : CPRI approved Main frame 3mm thick CRCA sheet, partition sheets / covers / doors of 3mm thick CRCA sheet, gland plates 3mm thick MS sheet (undrilled), base frame on ICMS channel with provision of incoming and outgoing cable entry at the bottom for outdoor installation, free standing floor mounted with degree of protection IP-65 and locking arrangements including taking down old unserviceable LT panel complete all as specified and as directed. Bus bar details: Material shall be aluminum bus bar, sleeving heat shrinkable type, with bus bar sizes for phase 50x12mm aluminium flat, neutral 50x12mm aluminium flat and bus bar support of epoxy type. Painting Details : Pillar box shall be powder coated and painted with two coats of synthetic enamel spray paint over a coat of redoxide primer and marking of details of capacity/ rating/ incoming/ outgoing/ danger notice board in capital English alphabets with red colour radium sticker of required size.
Accessories for Pillar Box: (i) 0-500V Digital voltmeter - 01 No (Flush type) (ii) 0-500A Digital Ammeter - 01 No (Flush type) (iii) Indication Lamps (LED) RYB - Set of 03 Nos. MAKE: L&T / BINAY/ ELMEASURE (iv) Incomer:- 400A, 4 pole, Changeover Switch Make:L&T, Cat No. CO44000OOOO -1 No. (v) Outgoing:- (i) 250A, 3 pole, MCCB Make: L&T, Cat No. CM98060OOO -2 Nos. (ii) 125A,3 pole,MCCB Make: L&T, Cat No. CM90678OOLO -4 No. (iii) Astro Timer Switch for Street Light/PTL/Bollard Light Control. Make: L&T, Cat No AUTS02AST00- 1 No NOTES: (i) The unit rate quoted is deemed to include the cost of MCCBs, Volt meter, Ammeter, Indication lamps and connected control wiring with 2.5Sqmm FRLS copper conductor necessary spreader links, lugs, glands and connecting of cables as per site conditions and complete all as specified and as directed. (ii) Drawings must be approved by Engineer-in-Charge before fabrication of LT Panel.
Tropical Refrigeration
SRI HARSHITA ELECTRICALS
M/s Power Engineering Co
ISLAND SALES ENTERPRISES
Sree Tirumala Enterprises
SKV Engineering
A. R. ELECTRICALS
EVEREST COOLING WORKS
Ravi Enterprises
OPS Associates
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .