SE 6
33/11 KV S/S Puraniya Aliganj Lucknow
For routine testing of power transformer 33KV Panel 11 KV incoming and outgoing and replacement installation of 33 KV 11 KV outdoor CT PT Unit Repairing and other related work at substations against M and R head under the area of EUTD V Transgomti
2022_MVVNL_719089_1
14/EUDC(VI)/2022-23
Open Tender
Electrical Works
Item Rate
365 days
EUTD-V
As per NIT
2 documents required · 2 mandatory
₹3,540
EUDD MAHANAGAR
₹15,000
Yes
23 Aug 2022
3 Aug 2022
8 Aug 2022
3 Aug 2022
8 Aug 2022
3 Aug 2022
Amount
Testing of power T/F at 33/11 KV S/S’s under the area of EUTD-V including following tests:- a) Insulation test. b) Open circuit/Ratio test & sort circuit test. c) Magnetization current test. d) Magnetic Balance test. e) Other test including BDV & neutral and body resistance of T/F. The test should be carried out by bringing testing kit and all required instruments on site by the contractor, making all necessary connection for above tests and insuring healthiness of transformers. Complete testing shall be done.
Testing of 33 KV VCB by primary injection set. Testing of winding temperature indicator, oil temperature indicator, oil level indicator & buchholz relay, by operation of individual alarm/trip circuits of above. Testing of annunciation/indication circuits displaying on panel. The work includes cleaning, adjustment of relay contacts & springs by manual and protection trip command generated by relays through primary injection set and Overhauling, annual maintenance of 33 KV VCB with one year guarantee petty items & consumerable item will be provided by contractor and major item will be provided by department.
Testing for 11 KV incoming/outgoing panels including testing of CT ratio by primary injection set. Testing of relays, and its setting as per requirement. The work includes cleaning of relay contacts and adjustment of springs. Checking and operation of VCB/OCB by remote/local and manual/protection command generated through primary injection set with operation of relays and overhauling, annual maintenance of 11 KV VCB with one year guarantee petty items & consumerable item will be provided by contractor and major item will be provided by department.
Replacement/Installation of 33 KV outdoor CT/PT unit.
Replacement/Installation of 11 KV outdoor CT/PT unit.
Repairing of 11 KV & 33 KV pilfer roof metering cubical including replacement of CT/PT, testing
Neutral and body earth resistance measurement of 33/11 KV Transformer.
Earth resistance measurement.
P. K. POWER SOLUTIONS
PRITHVI ENTERPRISES
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .