| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.6 LAccepted-AOC H NO 01 MADINA BAGH MEHJOOR NAGAR NEAR HOTEL RAFADA SRINAGAR 190015 J K | BUDGAM | JAMMU AND KASHMIR | 190015 | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹25.6 L+₹3.0 L (13.4%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
Refer Docs
EMD Value
₹69,000
Closing Date
13 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col S S Babu
Headquarters 138 Works Engineers Pin-914138 C/o 56 APO
MAINT AND REPAIRS TO HT NETWORK INCL TRANSFORMERS AND CERTAIN RELATED MISC WORKS AT BASE CAMP AND MISC ELECT REPAIR / REPLACEMENT OF WORK OF UG CABLE, LT PANEL, JUNCTION BOX AND LT OH LINE AND ALLIED SERVICE AT FD HOSP AND OMP UNDER GE PARTAPUR
2021_MES_475480_1
138WE/L-64/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE PARTAPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE PARTAPUR
₹69,000
Yes
29 Oct 2021
15 Sept 2021
20 Oct 2021
15 Sept 2021
13 Oct 2021
29 Sept 2021
60 days
Amount
Re-stringing, restretching ACSR conductor of overhead HT/LT line on steel poles after removing binding from insulator and rebinding the conductor with insulator including providing new binding wire jumpering providing with sleeves of appropriate size, ACSR conductor with colour code sleeves after restraining and removing unavoidable sags in the lines, complete all as specified and directed by Engr-in-charge.
M&L for aluminium conductor steel reinforced (ACSR) in replacement as in over head conductor including provision of aluminium tapes for binding all as specified and directed by Engr-in-charge. Note : (i) Weight of ACSR conductors shall be determined by measuring the horizontal distance between center of two adjacent poles and compounding the wieght of conductors of size and length provided and 3% extra added for sag, jointing, jumpers etc. (ii) The weight of the aluminium tapes shall not be added in the weight of the conductors for payment purpose. (iii) Size of ACSR conductor will be decided by GE/Engr-in-charge as per electric load and site requirement.
Supply and fix in replacement Pin type insulator, porcelain, vitrous, white brown or green insulator incl one galvanized mild steel spindle, two galvanised iron washer and one galvanized iron nut of size 100mm height and 65 mm dia for 1100 volts complete all as specified and directed by the Engr-in-charge.
Supply and fix in replacement Pin type insulator, porcelain, vitrous, white brown or green insulator incl one galvanized mild steel spindle, two galvanised iron washer and one galvanized iron nut of size 150mm height and 150 mm dia for 1100 volts complete all as specified and directed by the Engr-in-charge.
Supply and fix in replacement shackle type porcelain, vitreous, brown or green insulator 1100 volts working pressure, 75 mm height and 90 mm dia with and including galvanised mild steel straps, washer, insulator bolts 12 mm dia, and nuts complete after removing unserviceable item all as specified and directed by Engr-in-charge.
M&L for loop type insulator, vitreous porcelain white, brown or green large size (65 x 90mm) clearance of hole 16 mm complete all as specified and directed by Engr-in-charge.
S&F in replacement cross arm bracing, supports clamps and back plated fabricated from structral steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engr-in-charge.
M&L for galvanised stay strand of size 7/4 mm complete all as specified and directed by Engr-in-charge.
S&F of gaurding wire, cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4 mm dia all as specified and directed.
Supply, laying, fixing, passing through pipe or laid in trenches and testing underground XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross section area 10x2 sqmm complete.
Ditto as per srl No 10, but 4x25 sqmm complete
Ditto as per srl No 10, but 3.5 x 35 sqmm cable
Ditto as per srl No 10, but 3.5 x 50 sqmm cable
Ditto as per srl No 10, but 3.5 x 70 sqmm cable
Ditto as per srl No 10, but 3.5 x 185 sqmm cable
Ditto as per srl No 10, but 3.5 x 500 sqmm cable
M&L for line separators of LT OH lines with nut, bolts & washers straight type fixed at a point as directed and suitable for 4 wire complete all as specified and directed by Engr-in-charge.
M&L for painting steel and iron surfaces, old/new surfaces of steel tublar poles/steel tublar swaged poles of any description, length n. exc 11 mtr above ground level incl angle iron/clamps bracket etc with one coat of silver aluminium paint two coat of synthetic enamel paint upto 1.5 mtr above coping in 30 cm wide strips in alternate black and white colour complete all as specified and directed by Engr-in-charge.
Supply and fixing aluminium bus bar chamber 200 AMP capacity 4 strips not less than 600mm long, outdoor type including one MCCB of 125 Amps 4 pole as incommer with locking arrangement, grouting in PCC 1:3:6 and connecting with UG XLPE cable with suitable copper thimbles complete.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5m in depth for laying cable, fixing of stay etc 10 Sqm on plan and n exc 1.5 in depth and getting out in hard/dence soil complete all as specified and directed by Engr-in-charge
Returning, filling in including spreading, levelling watering and well ramming in layers not exc. 25cm width complete all as specified and directed by Engr in Charge.
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5 above the starting point including spreading and leveling complete all as specified and directed by Engr-in-charge.
Sand cushioning for under ground cable 8 cm before laying the cable and 15cm after laying and streching the cable complete all as specified and directed by Engr-in-charge.
M&L Un-reinforced precast factory made concrete cable covers, class LV type-I with flat size 250x 150x 40 cm complete all as specified and directed by Engr-in-charge.
Supply and laying GI pipe light grade 40 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection.
Supply and laying GI pipe light grade 50 mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection.
S&F MCCB 4 Pole, 415V, 100 Amps with breaking capacity 25 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F MCCB 4 Pole, 415V, 125 Amps with breaking capacity 25 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F MCCB 4 Pole, 415V, 160 Amps with breaking capacity 36 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F MCCB 4 Pole, 415V, 250 Amps with breaking capacity 36 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F MCCB 4 Pole, 415V, 400 Amps with breaking capacity 36 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F Changeover of 200 Amps euro load with breaking capacity 36 KA, adjustable type complete all as specified and directed by Engr-in-charge.
S&F on load changeover switch of 630 Amps AC 230 Amps 415 V, with breaking capacity 80 KA, adjustable type complete all as specified and directed by Engr-in-charge.
Supply and laying in repairs synthetic insulating mat of size 2m x 1m and 12mm thick for 1100 volts made from synthetic insulating material, free from any insertions leading to detoriation of insulating properties. Note : The upper surface should have small aberration (Rough Surface) with out edges to avoid slippery effects. The mat should be fire retardant & self extinguishing complete all as specified and directed by Engr-in-charge.
Material and Labour for PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation, filling or mass concrete as in foundation stays etc complete all as specified and directed by Engr-in-charge.
Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green in-series assembly for tension with tension clamps for conductors, working pressure 11000 volts
M&L Stay assembly complete with accessories i.e. stay plae 230mm x 230mm x 6mm with 16mm dia rod, galvanized thimbles GI stay wire 7/4 SWG, loop type insulators, vitreous porecelain, white brown or green of large size with overall dimensions 90mm x 140mm, clearance of hole 25.5mm etc and all other accessories as shown in electrical plate No 1 on ser page No 495 of ES Schedule Part-I (specification) complete including taking out existing unserviceable stay complete all as specified and directed. Note : Excavation and earth work and concrete for stay pit shall be measured and paid for separately.
M&L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables HT (heavy duty) with aluminium conductor, 11000 volts, grade cross sectional area 95 Sqmm 3 Core all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x60mm thickness not less than 6mm thick buried directly in ground (earth plate not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 2.5 mtr below the normal ground level connected to galvanized iron earth strip of size 32x6mm thick by means of nuts bolts, nuts, check nuts and washers of GI steel all as shown in electric plate No 3 connected to earth test point all as specified and indicated complete and including charcoal dust, salt etc and GI protection pipe light grade 40mm bore and GI watering pipe 20mm bore medium grade with funnel and wire mesh, 40mm thick pre cast RCC M-15 (Nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover, PCC -15 (nominal mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed by Engr-in-charge.
M&L for earthing complete with galvanized steel earth plate electrode 600x600x60mm thickness not less than 6mm thick buried directly in ground (earth plate not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 2.5 mtr below the normal ground level connected to galvanized iron earth strip of size 32x6mm thick by means of nuts bolts, nuts, check nuts and washers of GI steel all as shown in electric plate No 3 connected to earth test point all as specified and indicated complete and including charcoal dust, salt etc and GI protection pipe light grade 40mm bore and GI watering pipe 20mm bore medium grade with funnel and wire mesh, 40mm thick pre cast RCC M-15 (Nominal mix) cover reinforced with SPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover, PCC -15 (nominal mix) pit, excavation and earth work in any type of soil and connected all as specified and as directed by Engr-in-charge.
Supply and laying reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm all as directed and specified.
Supply and laying/fixing in replacement, GI pipe medium grade 80mm bore (dia) including all type fittings fixed on walls/to poles with clamps/laid in trenches as cable protection all as specified and directed.
S&F cable jointing kit for 11KV (earthed) grade cable for indoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed by Engr-in-charge.
S&F cable jointing kit for 11KV (earthed) grade cable for outdoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specif
S&F cable jointing kit for 11KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed by Engr-in-charge.
S&F lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11000 volts complete all as specified and directed by Engr-in-charge.
S&F Gang operated Device (GOD) Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps suitable for 11000 volts complete all as specified and directed by Engr-in-charge.
S&F Expulsion fuse single pole suitable for 6600 volts, 50 Amps complete all as specified and directed by Engr-in-charge.
M&L for dehydration and decentrifuging of Transformer insulating oil after decanning it from drain plug and carrying out chemical process to remove moisture and refill the oil after achieving a dielectric strength of 40 KV for sphere to sphere gap of 2.5mm duly tested and approved by Engr-in-charge.
M&L for Transformer insulating oil as per IS 335 : 1993 with density 0.89 gm/cum Max. Flash point 140 cm Dielectric strength 40 KV (rms). The oil shall not contain anti oxidant additives. Water content 50 PPM Max.
M&L for Brass LT Studs including gas kit and seal for up to 200 KVA transformers duly approved by Engr-in-charge.
M&L for Brass HT Studs including gas kit and seal for up to 200 KVA transformers duly approved by Engr-in-charge.
M&L for Brass LT Studs including gas kit and seal for up to 400 KVA transformers duly approved by Engr-in-charge.
M&L for Brass HT Studs including gas kit and seal for up to 400 KVA transformers duly approved by Engr-in-charge.
M&L for Brass LT insulating bushes for upto 200 KVA transformers duly approved by Engr-in-charge.
M&L for Brass HT insulating bushes for upto 200 KVA transformers duly approved by Engr-in-charge.
M&L for Brass LT insulating bushes for upto 400 KVA transformers duly approved by Engr-in-charge.
M&L for Brass HT insulating bushes for upto 400 KVA transformers duly approved by Engr-in-charge.
Replacement of breather assembly complete with silica jel in transparent container with metallic top & bottom cup with pipe entry of 15/20 mm dia, including air oil bath tub, complete all as specified and directed.
Replacement of existing unserviceable silica jel with new crystal clear silica jel for the breather or transformer all as shown and directed.
Material and labour for painting of transformer capacity 200 KVA/400 KVA complete with synthetic enamel paint by spraying including filling cavaties with filler one coat after cleaning all dust/rust including writing the MES No and all as directed and Engr-in-charge.
M&L carrying out lab test for acidity of transformer oil for various transformers and submission of test reports on the proper format as specified and directed
Supply and Fixing First Aid Box wall mounted type duly empanelled as "First Aid Box" and front opening single higned door with locking arrangements as specified and directed.
Material and labour for arrest the leakage of transformer oil from the LT/HT side busings of Transformer capacity 200 KVA to 400 KVA including the followings :- (a) Taking down the top cover and refixing after repair duly pasted with gasket. (b) Taking out the trnsformer Oil from the transformer upto the level suitable to carry out the repair work. (c) Taking out the bushings and supply and replacement of the same duly coupled with suitable gasket nuts, bolts and washers. (d) Refilling of Transformer Oil after completion of repair work and ensure that the leak has been arrested. (e) Reassebling complete and testing and commissioning. (f) Supply and replacement of brass Spindle on LT/HT Side.
darshan kumar gandhi
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .