| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-Finance PLOT NO 585 NETAJI VIHAR K CIRCLE APARTMENT 3RD FLOOR RASULGARH BHUBANESWAR 751010 | BHUBANESWAR | KHORDHA | ODISHA | 751010 | ₹7.6 L | L1 | Accepted-Finance Q |
| 2 | L2₹7.6 LSame as L1Accepted-Finance KHURDA KHORDHA ODISHA 751015 UDYAM OD 19 0011250 | KHORDHA | ODISHA | 751015 | ₹7.6 LSame as L1 | L2 | Accepted-Finance Q |
| 3 | L3₹7.6 LSame as L1Accepted-Finance | ₹7.6 LSame as L1 | L3 | Accepted-Finance Q |
Tender Value
Refer Docs
EMD Value
₹7,600
Closing Date
15 Apr 2026, 5:00 pmClosed
SE CUTTACK R AND B DIVISION II OMP SQUARE
SE CUTTACK R AND B DIVISION II OMP SQUARE
Supply, Installation, Testing and Commissioning of Fire fighting, Manual Fire alarm, Fire Extinguisher, Public Address System and Signage system at CHC Dampada(G plus1)Building, Cuttack.
2026_EICCL_127872_5
SE CTC (RnB)-II -22 of 2025-26
Open Tender
Civil Works - Buildings
Percentage
30 days
DAMPADA
AS PER DTCN
3 documents required · 3 mandatory
₹4,000
₹7,600
Yes
7 Jul 2026
6 Apr 2026
16 Apr 2026
6 Apr 2026
15 Apr 2026
6 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying, Installing, Testing and commissioning of electrical motor driven booster pump of Monoblock type capable to deliver 450 LPM at 35MWC. The pump shall be coupled to TEFC motor of suitable HP with speed of 2900RPM and complete set shall mounted on common base frame as per direction of engineer in charge.Make-
Kirloskar/Wilo/Ksb. | - | No | - | - |
| 2 | Control panel for fire pumps for auto action :Supply, installation, testing and commissioning of Floor/Wall mounted sectionalised, front operated top entry dust and vermin proof M.V.Panel Boards suitable for operation at 415V, 3 phase, 4 wire, 50Hz distribution system fabricated out of 2.0 mm thick CRCA sheet, insulated busbar
with heat shrienkable PVC sleeve, base frame, complete with all accessories including interconnections, earth bus | - | No | - | - |
| 3 | 1100 V GRADE POWER/CONTROL CABLES :SITC of FRLS, PVC outer sheateh, steel armoured, aluminium, 1100v grade power cables with glands etc. The minimum size of the cables shall as mentioned below as per direction of engineer in charge.Make-Polycab/Havels/KEI.:-3.5C x 16 mmsq | - | Rmt | - | - |
| 4 | 2 C x 1.5 mmsq | - | Rmt | - | - |
| 5 | G.I. earthing strip of size 25x3 mm shall be run for PUMPS to panel. | - | Rmt | - | - |
| 6 | Supplying, Installing, Testing and commissioning of waffer type C.I. Non-return valves as per with required flanges, nuts, bolts and gaskets etc. complete of size 100 mm nominal dia.as per direction of engineer in charge.Make-Zoloto/Leader/Audco | - | No | - | - |
| 7 | Supplying, Installing, Testing and commissioning of CI butterfly valves (PN 10) as per BS 5155 slim seal standard lever operated type with required flanges, nuts, bolts etc. complete of size 100 mm nominal dia.Make- Zoloto/Leader/Audco | - | Nos | - | - |
| 8 | Providing, installing and commissioning C.I. flanged "Y" type Strainer with SS mesh, suitable flanges, nuts, bolts, gaskets etc. complete..Make-Zoloto/Audco/Leader/Kartar.100 mm | - | No. | - | - |
| 9 | SITC of Gun metal chrome finished Ball valves with fittings of screwed end type.as per direction of engineer in charge of size 15 mm dia. | - | Nos | - | - |
| 10 | Supply and installaion of pressure switches of suitable range for pump sets.as per direction of engineer in chargeMake-Indfos/Grandfos. | - | Set | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
DTCN.pdf
Tender Documents • 1.47 MB
BOQ_587156.xls
BOQ • 0.56 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .