| Sl No | Description | Qty | Unit | M/s SCHOLASTIC ENTERPRISES L2 | SHRI SAINATH ENGINEERS L3 | virendera singh L4 | GUPTA ENGINEERING WORKS L1 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm complete all as specifiand as directed. | 460 | RM | 1,050 ₹4,83,000 Lowest | 1,595 ₹7,33,700 | 1,100 ₹5,06,000 | 1,265 ₹5,81,900 |
| 2.00 | Supply, installation, Testing, Commissioning of Oil Cooled, Copper wound, Step down down "BIS marked as per Electrical transformers (Quality Control) order, 2014 issued by ministry of Heavy Industries and Public Enterprises & BEE star labelled as per DT notification issued by ministry of power” transformer of capacity 500 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433V 3phase 4 wire,50 C/S oil immerse, naturally cooled (ONAN) externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433V with tapping at +/-2.5 %to +/-5 % & +/- 7.5 % on HV side and to be changed by means of hand operated off load tap changing gear including first filling of new transformer oil as per IS:335 (mineral oil) of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland, Silica gel, breather, Oil level indicator gauge, drain out valve (oil tank), exhaust vent, air release valve, temp gauge, cast iron wheel etc. comply with EEL-3 IS 1180 (Part-1)-2014 with amendment no. 4 having total losses @ 50% load 1354W & total losses @ 100% load 3909W. Including following items/ Accessories.
Contd........
(i) Name, rating & diagram plate
(ii) Off circuit tap changing switch
(iii) Earthling terminals
(iv) Lifting lugs
(v Oil drain valve with plug
(vi) Oil filter valve with plug
(vii) Conservator with oil filling hole | 1 | EACH | 27,00,000 ₹27,00,000 | 23,75,000 ₹23,75,000 | 28,00,000 ₹28,00,000 | 17,95,000 ₹17,95,000 Lowest |
| 2.01Contd item No 2 (viii) Thermometer pocket (ix) Air release plug (x) Silicagel breather (xi) Removable inspection opening (xii) Explosion vent Note : (i) The drawings of transformer shall be got approved from GE. (ii) Manufacturer’s inhouse Lab must be NABL approved. (iii) All tests shall be carried out at factory before the dispatch of Transformer inspection of officer as detailed by Accepting Officer. (iv) Manufacturer must have ISO Certificates (ISO:9001, ISO:14001, ISO:45001). (v) In case of any fault or failure of the transformer during the warranty/defect liability period, the contractor shall be fully responsible to arrange and install a temporary replacement transformer of the same make and rating within 24 (twenty-four) hours at site to ensure uninterrupted power supply. (vi) The rent/hire charges of the temporary transformer, including transportation, installation, operation and removal, shall be borne entirely by the contractor until the original transformer is repaired, tested, and reinstalled in healthy working condition at site, to the satisfaction of the Engineer-in-Charge, at no extra cost to the department. | |||||||
| 3.00 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core all as specifiand as directed. | 180 | RM | 2,500 ₹4,50,000 | 1,785 ₹3,21,300 Lowest | 3,000 ₹5,40,000 | 1,936 ₹3,48,480 |
| 4.00 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm tthick buried directly in ground(earth pit not less than 2.25 mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to copper earth strip 20 x 3 mm thick by means of nuts, bolts, washers and check nuts of brass, 40 mm bore GI pipe light grade proection pipe up to test point, 20mm dia light grade GI pipe for watering, meshed funnel, alternate layer of charcoal and common salt complete all as per SSR with PCC pit 50mm thick, RCC cover 540 x 540 x 50 mm thick in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 75 mm c/c both way in lieu of CI cover, and protection including necessary excavation and earth work complete all as specified and directed. | 6 | Each Job | 30,000 ₹1,80,000 | 21,252 ₹1,27,512 Lowest | 32,000 ₹1,92,000 | 24,500 ₹1,47,000 |
| 5.00 | Supply, installing, erecting, commissioning and testing new factory made LT panel board, 415 Volts, 3 Phase & 4wire system, cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable alley protected with bakelite sheet between bus bar & cable alley with front side shutters with locking arrangement, including TPN Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating not less then 1.5 times the rated capacity of the incomer ACB/ MCCB and bus bar chamber covered both side using bakelite sheet partition and wire mesh to the back side of cable alley for the protection purpose . All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job. The TPN bus bar shall be mounted on F class insulators with intervals not more then 500 mm. All interconnections between the main bus bar as well as incoming/outgoing feeders shall be carried out with TPN Aluminium bus bar of rating not less then 1.5 times rated capacity of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 2.5 sqmm multi-stranded copper conductor and shall be properly bunched. The panel board shall have bottom channel of size 75 x 40 mm properly welded with 45 CM long 04 legs of angle iron 50x50x6 mm using 3 mm thick CRCA sheet corners to all legs and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of Aluminum lugs and suitable size of chrome plated brass double compression glands provided for incoming and out-going cables comprising the following :- Make of ACB/ MCCB/MCB/Change over switch: L&T /ABB/ LEGRAND/ SCHNIEDER/ SIEMENS | 1 | Each | 7,30,000 ₹7,30,000 | 8,38,652 ₹8,38,652 | 7,35,000 ₹7,35,000 | 6,49,000 ₹6,49,000 Lowest |
| 5.01Contd item No 4. INCOMING ACB (a) All interconnections between the main bus bar as well as incoming/outgoing feeders shall be carried out with Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating 1000 Amps rated capacity of individual outgoing feeders. (b) ACB 4 Pole, 415 V,50 KA with microprocessor release (Manual Drawout type) of capacity 800 Amps- 01 Nos OUTGOING ACB (c) ACB 4 Pole, 415 V,50 KA with microprocessor release (Manual Drawout type) of capacity 630 Amps-02 Nos Metering: d) AC digital voltmeter 0-500 volts Size 4"X4" with 3 Ph selector switch-01 Nos e) 0-500 digital Amp meter with suitable Size 4"X4" with 3 Ph selector switch- 01 No.. f) LED Indicating lamps RYB set of three -01 Sets Note: (a) Cable entry should be incoming/ out going from separate cable gallery. (b) All incoming/outgoing ACB shall be provided with suitable size of copper connection plates. (c) All incoming/outgoing ACB shall be provided with suitable spreader links. (d) Provision of gland hole, brass glands and heat shrinkable end joints of all incoming and out going cables all as directed. (e) All incoming/outgoing ACBs should be marking label/end plate/end clams/ suitable size of terminal block stud/screw less type etc. (f) Main bus bar/ link bus bar should be full covered including back side. | |||||||
| 6.00 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm tthick buried directly in ground(earth pit not less than 2.25 mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to copper earth strip 20 x 3 mm thick by means of nuts, bolts, washers and check nuts of brass, 40 mm bore GI pipe light grade proection pipe up to test point, 20mm dia light grade GI pipe for watering, meshed funnel, alternate layer of charcoal and common salt complete all as per SSR with PCC pit 50mm thick, RCC cover 540 x 540 x 50 mm thick in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 75 mm c/c both way in lieu of CI cover, and protection including necessary excavation and earth work complete all as specified and directed. | 2 | Each Job | 30,000 ₹60,000 | 22,325 ₹44,650 Lowest | 31,000 ₹62,000 | 24,500 ₹49,000 |
| 7.00 | Excavation in trenches in soft/loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay and pipe line,and getting out complete all as specified and directed | 250 | Cum | 100 ₹25,000 Lowest | 145 ₹36,250 | 110 ₹27,500 | 130 ₹32,500 |
| 8.00 | Returning & filling including spreading, leveling watering and well ramming in layers n. exc 25 cm thick in any type of soil complete all as specified. | 220 | Cum | 70 ₹15,400 | 110 ₹24,200 | 80 ₹17,600 | 50 ₹11,000 Lowest |
Tender Value
₹44.3 L
EMD Value
₹88,520
Closing Date
1 Apr 2026, 6:00 pmClosed
CWE (AF) AGRA
HQ CWE (AF) Agra
PROVN OF POWER SUPPLY FOR INSTALLATION OF FAST CHARGER FOR ELECT BUSES UNDER GE (AF) ADM AREA AT AF STN AGRA
2026_MES_755920_1
80025-49/E8
Open Tender
Civil Works
Item Rate
180 days
GE (AF) ADM AREA AGRA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE (AF) ADM AREA AGRA
₹88,520
Yes
12 May 2026
11 Mar 2026
8 Apr 2026
11 Mar 2026
1 Apr 2026
25 Mar 2026
11 Mar 2026 - 18 Mar 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm complete all as specifiand as directed. | 460 | RM | - | - |
| 2 | Supply, installation, Testing, Commissioning of Oil Cooled, Copper wound, Step down down "BIS marked as per Electrical transformers (Quality Control) order, 2014 issued by ministry of Heavy Industries and Public Enterprises & BEE star labelled as per DT notification issued by ministry of power” transformer of capacity 500 KVA plinth mounted outdoor type with latest feature complete with standard fitted HT 11 KV 3 phase, LT 433V 3phase 4 wire,50 C/S oil immerse, naturally cooled (ONAN) externally cooling tube delta connection on primary HT 11 KV side and star connection on secondary LT 433V with tapping at +/-2.5 %to +/-5 % & +/- 7.5 % on HV side and to be changed by means of hand operated off load tap changing gear including first filling of new transformer oil as per IS:335 (mineral oil) of dilectric strength not less than 55 KV with all fitting and accessories such as LT box with cable gland, HT box with cable gland, Silica gel, breather, Oil level indicator gauge, drain out valve (oil tank), exhaust vent, air release valve, temp gauge, cast iron wheel etc. comply with EEL-3 IS 1180 (Part-1)-2014 with amendment no. 4 having total losses @ 50% load 1354W & total losses @ 100% load 3909W. Including following items/ Accessories.
Contd........
(i) Name, rating & diagram plate
(ii) Off circuit tap changing switch
(iii) Earthling terminals
(iv) Lifting lugs
(v Oil drain valve with plug
(vi) Oil filter valve with plug
(vii) Conservator with oil filling hole | 1 | EACH | - | - |
| 2.01 | Contd item No 2
(viii) Thermometer pocket
(ix) Air release plug
(x) Silicagel breather
(xi) Removable inspection opening
(xii) Explosion vent
Note :
(i) The drawings of transformer shall be got approved from GE.
(ii) Manufacturer’s inhouse Lab must be NABL approved.
(iii) All tests shall be carried out at factory before the dispatch of Transformer inspection of officer as detailed by Accepting Officer.
(iv) Manufacturer must have ISO Certificates (ISO:9001, ISO:14001, ISO:45001).
(v) In case of any fault or failure of the transformer during the warranty/defect liability period, the contractor shall be fully responsible to arrange and install a temporary replacement transformer of the same make and rating within 24 (twenty-four) hours at site to ensure uninterrupted power supply.
(vi) The rent/hire charges of the temporary transformer, including transportation, installation, operation and removal, shall be borne entirely by the contractor until the original transformer is repaired, tested, and reinstalled in healthy working condition at site, to the satisfaction of the Engineer-in-Charge, at no extra cost to the department. | - | - | - | - |
| 3 | Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core all as specifiand as directed. | 180 | RM | - | - |
| 4 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm tthick buried directly in ground(earth pit not less than 2.25 mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to copper earth strip 20 x 3 mm thick by means of nuts, bolts, washers and check nuts of brass, 40 mm bore GI pipe light grade proection pipe up to test point, 20mm dia light grade GI pipe for watering, meshed funnel, alternate layer of charcoal and common salt complete all as per SSR with PCC pit 50mm thick, RCC cover 540 x 540 x 50 mm thick in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 75 mm c/c both way in lieu of CI cover, and protection including necessary excavation and earth work complete all as specified and directed. | 6 | Each Job | - | - |
| 5 | Supply, installing, erecting, commissioning and testing new factory made LT panel board, 415 Volts, 3 Phase & 4wire system, cubical out door type of suitable size for housing of all equipments & proper heat dissipation, CPRI approved weather/dust proof, made out of 3.15 mm thick CRCA sheet powder coated with front and back side openable with suitable cable alley protected with bakelite sheet between bus bar & cable alley with front side shutters with locking arrangement, including TPN Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating not less then 1.5 times the rated capacity of the incomer ACB/ MCCB and bus bar chamber covered both side using bakelite sheet partition and wire mesh to the back side of cable alley for the protection purpose . All type Test Certificates and Design varification with switch gears ( ACB & MCCB) as per confirming to IS/ IEC: 61439/2011 Part-1 and part -2 with short circuit test at 65 KA, should be submitted by the contractor before executing the job. The TPN bus bar shall be mounted on F class insulators with intervals not more then 500 mm. All interconnections between the main bus bar as well as incoming/outgoing feeders shall be carried out with TPN Aluminium bus bar of rating not less then 1.5 times rated capacity of individual outgoing feeders. All control wiring shall be with FRLS PVC insulated 2.5 sqmm multi-stranded copper conductor and shall be properly bunched. The panel board shall have bottom channel of size 75 x 40 mm properly welded with 45 CM long 04 legs of angle iron 50x50x6 mm using 3 mm thick CRCA sheet corners to all legs and complete mounted or fixed on PCC foundation above 0.45 mtr on floor and cable connection with suitable size of Aluminum lugs and suitable size of chrome plated brass double compression glands provided for incoming and out-going cables comprising the following :- Make of ACB/ MCCB/MCB/Change over switch: L&T /ABB/ LEGRAND/ SCHNIEDER/ SIEMENS | 1 | Each | - | - |
| 5.01 | Contd item No 4. INCOMING ACB
(a) All interconnections between the main bus bar as well as incoming/outgoing feeders shall be carried out with Aluminium bus bar insulated with colour coaded heat shrinkable sleeve of rating 1000 Amps rated capacity of individual outgoing feeders.
(b) ACB 4 Pole, 415 V,50 KA with microprocessor release (Manual Drawout type) of capacity 800 Amps- 01 Nos
OUTGOING ACB
(c) ACB 4 Pole, 415 V,50 KA with microprocessor release (Manual Drawout type) of capacity 630 Amps-02 Nos
Metering:
d) AC digital voltmeter 0-500 volts Size 4"X4" with 3 Ph selector switch-01 Nos
e) 0-500 digital Amp meter with suitable Size 4"X4" with 3 Ph selector switch- 01 No..
f) LED Indicating lamps RYB set of three -01 Sets
Note: (a) Cable entry should be incoming/ out going from separate cable gallery.
(b) All incoming/outgoing ACB shall be provided with suitable size of copper connection plates.
(c) All incoming/outgoing ACB shall be provided with suitable spreader links.
(d) Provision of gland hole, brass glands and heat shrinkable end joints of all incoming and out going cables all as directed.
(e) All incoming/outgoing ACBs should be marking label/end plate/end clams/ suitable size of terminal block stud/screw less type etc.
(f) Main bus bar/ link bus bar should be full covered including back side. | - | - | - | - |
| 6 | M&L for earthing complete with copper earth plate electrode 600x600x3.15 mm tthick buried directly in ground(earth pit not less than 2.25 mtr deep below the normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to copper earth strip 20 x 3 mm thick by means of nuts, bolts, washers and check nuts of brass, 40 mm bore GI pipe light grade proection pipe up to test point, 20mm dia light grade GI pipe for watering, meshed funnel, alternate layer of charcoal and common salt complete all as per SSR with PCC pit 50mm thick, RCC cover 540 x 540 x 50 mm thick in 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8mm dia TMT bar @ 75 mm c/c both way in lieu of CI cover, and protection including necessary excavation and earth work complete all as specified and directed. | 2 | Each Job | - | - |
| 7 | Excavation in trenches in soft/loose soil n.exc 1.5m wide and n. exc 1.5m depth for laying of cable, errection of poles, stay and pipe line,and getting out complete all as specified and directed | 250 | Cum | - | - |
| 8 | Returning & filling including spreading, leveling watering and well ramming in layers n. exc 25 cm thick in any type of soil complete all as specified. | 220 | Cum | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
BOQ_846715.xls
BOQ • 0.29 MB
Tenderdocuments.pdf
Tender Documents • 1.79 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .