Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.5 LAccepted-AOC H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹4.5 L Quoted ₹4.9 L | L1 | Accepted-AOC AOC |
| 2 | L1₹5.3 LRejected-Finance SHIVAJI NAGAR GALI NO 1 DHANGU ROAD MODEL TOWN PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹5.3 L | L1 | Rejected-Finance Being not L1 |
| 3 | L3₹5.5 LRejected-Finance | ₹5.5 L | L3 | Rejected-Finance Being not L1 |
| 4 | L4₹5.9 LRejected-Finance GOVT CONTRACTOR VILL NAYA SUJAN FEROZPUR KALAN TEH DIST PATHANKOT PIN 145023 | PATHANKOT | PATHANKOT | PUNJAB | 145023 | ₹5.9 L | L4 | Rejected-Finance Being not L1 |
Tender Value
Refer Docs
EMD Value
₹12,000
Closing Date
7 Dec 2021, 6:00 pmClosed
AGE(I) DALHOUSIE
AGE(I) DALHOUSIE
REPAIR AND MAINTENANCE OF US LT CABLES LT PANELS LT SWITCH GEAR PROTECTION SYSTEM OH LINES AND OTHER CONNECTED WORK AT GEMINI HWW AND TICCA AREA AT DALHOUSIE CANTT
2021_MES_486913_1
8825/2021-22/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE(I) DALHOUSIE
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
AGE(I) DALHOUSIE
₹12,000
Yes
AGE(I) DALHOUSIE
8 Feb 2022
8 Nov 2021
9 Dec 2021
8 Nov 2021
7 Dec 2021
23 Nov 2021
9 Nov 2021 - 18 Nov 2021
18 Nov 2021
Amount
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m for laying cables, stays etc and getting out in hard dense soil all as specified.
Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cms thick in soils complete all as specified
Material and labour for dry sand in trenches cushioning to under ground cable spreading, levelling hand punning complete all as specified and directed.Note- Punned down thickness will be measured for payment purpose.
M&L for bricks common burnt old size sub class `B' bricks laid dry for cable protection flat width wise complete all as specified and directed.
M&L and jointing testing and commisioning in replacement XLPE LT UG Cable insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 1100 Volt grade, laid in trenches / ducts / encased in GI pipe / fixed to pole/wall etc Make of LT UG Cable- Havells / KEI/ Polycab and including taking down old unserviceable cables complete all as specified and directed of following sizes :-
Cross sectional area 3.5 core 50 Sqmm
Cross sectional area 4 core 25 Sqmm
Cross sectional area 4 core 16 Sqmm
Supply & lay GI tubing light grade 40 mm dia bore in protection of cable at road crossing /hard standing/pole protection fixed with clamps as per site requirement etc all as specified and directed. Make :- Prakash surya/Jindal/Tata
M&L for preparation of surfaces, scraping of old paint of steel surface of poles and applying two coats of aluminium paint over a coat of red oxide primer of LT steel tubular pole 9 metre hight, Including fixing of reflection tape/reflection paint in altternate coloured of width 6" on poles 1.5 to 1.8 metre above the ground level including writing pole number with black letter under yellow circle complete all as specified and directed. Note :- The reflection tape/reflection colour shall be as directed by Engr-in-charge.
Unbinding from insulators ACSR conductor any size of LT over head line for repairs, restretching of ACSR conductor to achieve proper sag and rewinding to the insulators using aluminium/GI wire all as required at site or directed. Note:- Distance between two poles irrespective of no of lengths of conductor shall be considered as a single span.
Cutting/ trimming of tree branches clearing 5 metres horizontal and 5 metres vertical distance from both sides of conductor including removing branches from site, complete all as specified & directed.Note:- (i) Clearing branches from both sides of conductor in between two consequtive poles shall be considered as one span irrespective of distance between poles.(ii) Cost of T&P required for cutting and removing branches shall be deemed to be included in rate quoted by bidder.
Supply and stringing ACSR conductor in replacement of (Weasel/ Ferret) on on LT over head line securing on pole complete including necessary binding work, jumpering, PG clamp, maintaining proper sag as per IE rule etc and including taking down old unserviceable ACSR conductor complete all as specified & directed. Make:-Bharat conductor /ICC /Alind (Note :- (a) Rate is inclusive of jumper on cut point/2 pole structure shall be provided with PVC insulated sleeve.
M&L for line seperator 3 phase 4 wire to making suitable gap in between LT line conductor with nuts bolts,washer complete all fixing accessories. all as specified and as directed by Engr-in-charge
M & L for Shackle Type, Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers,insulator bolts, washers and nuts, for 75 mm height, 90 mm dia, 1100 volts grade all as specified and directed by Engr- in -Charge.
Outdoor type factory made bus bar chamber of size 0.75x0.45x0.40 metres depth made out of CRCA sheet 3.15mm thick with 4 No's aluminium bus bars of capacity 200 Amps,with colour code supported on insulators, internally prewired having locking arrangement, handle, provision of suitable hole at bottom for incoming and outgoing under ground cables, panel having angle iron frame made of 40 X 40 X 6 mm angle iron and 50 cms long legs made of 40 X 40 X 6 mm angle embedded upto 20 cms in PCC & 30 cms clear above ground complete including painting with two coats of powder coated paint over a coat of red oxide primer on exterior and interior faces, errection of Bus Bar chamber duly grouted in PCC M-15, type B0 using 12.5 mm graded crushed stone aggregate including earth work complete all as specified and directed.
M&L in replacement for Earthing complete with galvanised steel earth plate electrode 60 X 60 cm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and inclduing GI Strip 25X4 mm as earthing lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 5 of MES SSR Part I and testing on completion inclduing excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, and cover 6 mm thick in cement concrete (1:2:4) type B1, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed with earth resistance not more than 1.0 OHMS. Note- In case earth resistance more than 1.0 ohms, the contractor wiil re earthing at no extra cost.
Cutting of road / hardstanding upto a size not exceeding 20 cms in width and not exceeding 60 cms in depth for laying of LT UG cable protection pipe line making good the disturbed portion so as to match existing finishing or with PCC 1:2:4 type B1 complete all as specified and directed.
M & L in repair for cement concrete PCC 1:3:6 type D-2 using 40mm graded stone aggregate as in pole foundation/ coping in shape of round/square complete all as specified and directed.
Supply & fixing of Automatic Street Light Control Switch using Infrared Sensor based NATURE SWITCH for automatic switching of Street Lights. Nature Switch operation should be based on Natural Light Lux* level. Required Illuminance Level for Switching ON is ≤ 30 Lux and for Switching OFF ≥ 10 Lux. The Sensor should also have part night operation facility of min. 4 hrs. to max. 12 hrs.Three-Phase load of 8kW (Swadeep-02EC8kW3P) with 3 nos. Contactors, 3 nos. Incoming MCBs & 3 nos. Outgoing MCBs of 20-32 Amps each & Circuit wiring (Copper) of min.10 sq.mm The Sensor along with suitable Power Contactor(s) and Incoming-Outgoing MCBs should be enclosed in a pole/wall mountable Rust Proof, Electric Shock Proof, Termite proof and FR grade SMC Enclosure conforming to IP54. The circuit should also have provision for Manual Operation (i.e. Sensor By-Pass option). complete all as specified and directed. Make-HEALER ENTERPRISES, BHOPAL OR EQVT in CG/Philips.
KEWAL SONS
Mahashakti Enterprises
BALKRISHAN GUPTA AND SONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .