Supply, Installation and Commissioning of VRF Air Cooled System at Golf Building, MCL HQ
2023_MCL_294458_1
MCL/SAMB/TA/ENM/2023-24/02 dated 23.11.2023
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
Jagruti Vihar, MCL HQ, Burla
Please refer Tender documents.
3 documents required · 3 mandatory
₹19,400
2 Feb 2024
23 Nov 2023
13 Dec 2023
24 Nov 2023
11 Dec 2023
24 Nov 2023
24 Nov 2023 - 28 Nov 2023
Amount
Air Cooled VRV / VRF Outdoor Unit Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow/Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R 410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5 .
16 H.P Cool / Heat Pump Unit (For First Floor)
8 H.P Cool / Heat Pump Unit (For Ground Floor)
6 H.P Cool / Heat Pump Unit (For TFA First Floor) ----- Quoting 8 HP
INDOOR UNITS Supply, Instalaltion, testing and commissioning of Indoor units equipped with pre-filter, fan section with suitable static fan to distribute the air as per approved shop drawings, multispeed motor, coil section with DX coil, outer cabinet / cassette panel, drain pan, insulation, pipe connections etc. of various capacities as per specifications and drawings.
DUCTABLE UNIT
Supply, installation, testing and commissioning of following minimum capacity and external static pressure VRF/VRV ceiling mounted ductable type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX copper coil, For TFA Dx copper coil with hydrophilic coating, electronic expansion valve, corded remote control, outer cabinet, vibration isolators, drain pan, other necessary supports etc., suitable for operation on single phase AC supply 230 V ± 10%, 50 Hz complete as required. The unit shall have automatic force shut down provision in case of fire on receiveing signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C WB temperature & For TFA 45 degree C temperature temperature.
6.36 TR(High-Static)
636 CFM \ 3.98 Tr. (TFA)
Y-joints For Indoor Unit
Supply,installation,testing and commissioning of Imported Y/T refnet Joints with insulation to connect indoor units with main header as per drawing. It should be complete as per manufacturing standards & as per directions of Engineer-in-charge . (1 Set will comprise of 2 Y/T Refnet Joints each for sution & discharge side)
Main Intelligent Programmable Central Controller (Corded Type)
Supply, Installation, testing and commissioning of Main centralized controller / manager digital type of latest generation for VRV/VRF system for controlling all the indoor & outdoor units installed in building with adapters (for connecting additional indoor units, cost for the same is deemed to be included in this item) with On / Off, touch screen and Temparature Controls, fan speed, scheduling, air flow direction setting, operation history etc. The controller should be compatible with automation system (Bacnet/IP) with all accessories. It should be complete as per manufacturing standards & as per directions of Engineer-in-charge.
Hi Wall Type Inverter Split AC Units: Supply Installation Testing and Commissioning of Hi Wall Type 5 star Inverter Type Split AC units with cordless remote control, Inverter driven compressor factory pre-charged with R-410A Refrigerant, washable synthetic media pre-filter, refrigerant piping duly insulated with 13 mm thick nitrile rubber, PVC drain piping duly insulated with 6 mm thick nitrile rubber, outdoor units equipped with highly efficient compressors, Air cooled heat exchanger, low noise condenser fan, auto check function for connection error, MS structure/wall bracket for outdoor unit etc complete as per specifications of following capacities.
1.5 TR, 5 Star Rating
Insulated Refrigerant Piping for VRV / VRF System: Supply, installation, testing and commissioning of interconnecting high pressure copper refrigerant piping work including vaccumiazation and Nitrogen testing suitable for refrigerant R 410A duly insulated with FACTORY PREFORMED TUBULAR EPDM RUBBER FOAM SECTIONS with completely closed cell structure as per specifications - Density 40-60 kg /cum , Class A as per ASTM E 84 , Class V-0 as per UL 94 and Mu value > 7000 between indoor & outdoor units as per specifications. External refrigerant piping shall be laid on 16 G GI covered perforated cable trays. Piping inside occupied area & vertical shaft inside the AHU Room shall be supported using 16 G GI hangers. All exposed pipe shall have UV coating on insulation & cost to be included in the piping. Cable tray is quantified seperately.
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.9 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19.1 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.6 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
Total impact of GST plus Labour Cess [@ 1 % (BOCW Cess to be deducted from the RA bill as per the value of the work progress)] for the purpose of CTC
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .