Construction of 10(ten) nos. of 132 KV AIS line bays for second source connectivity of GSS Ramnagar, Sherghati and Piro on Turnkey Basis
128993
15/PR/BSPTCL/2026
Open Tender
ELECTRICAL
Patna
• Name and designation of the officer of the Bidder to whom all reference shall be made for expeditious technical co-ordinationn.
• Place of manufacture: (Item wise)
• Services or facilities available
• Availability of spare parts
ELECTRICAL
ITEM RATE
L1
1
26 documents required · 26 mandatory
₹11,800
Processing Fee: 5900
₹40.1 L
13 Apr 2026
13 Apr 2026
30 Apr 2026
13 Apr 2026
28 Apr 2026
13 Apr 2026
INDEX FOR G.T.P TO BE FILLED IN BY TENDERERS
4.2 PLCC Equipments
4.3 FIRE Protection System
4.4 Air Conditioning System
4.5 LT Switchgear
4.6 400KV, 220 KV, 132 KV AND 33 KV Isolators
4.8 630 KVA, L.T Transformers.
400 KV,220 KV, 132 KV AND 33 KV Voltage Transformers
4.11 Battery and Battery Chargers
4.12 Control Cables
4.13 Hardware Fittings, Clamps and Connectors
4.14 400KV, 220 KV And 132 KV SF6 Circuit Breakers
4.15 400 KV, 220 KV, 132 KV and 33 KV Lightning Arresters
4.16 400 KV, 220 KV, 132 KV and 33 KV Current Transformer
4.17 Disc Insulators.
4.18 Hardware Fittings for Moose, Panther and Earth wire
4.19 Post Insulators
4.21 Control and Relay Panels.
4.22 AC & DC Distribution Boards.
4.23.1 500 MVA, 400/200/33 KV Power Transformers
4.23.2 160 MVA, 220/132/33 KV Power Transformers
4.24 125 MVAR REACTOR
4.25.1 Station HMI
4.25.2 Redundant Station HMI
4.25.3 Bay Level units along with bay mimic.
4.25.4 Bay Level limit for Auxiliary System.
4.25.5 Disturbance Recorder work station.
4.25.6 Colour Leser printer
4.25.7 Dot matrix printer.
4.25.8 Interface equipment for gateway to RCC and RSCC
4.25.9 Communication infrastructre between bay level units, station HMI, Printers, gateways, redundant LAN.
4.25.10 Remote work Station.
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 400 KV GIS PANEL
Name of the Tenderer
As per Tenderer
Sl. No. DESCRIPTION Transformer Bay Line bay Bus Coupler
2 Name of manufacturer (OEM)
3 Country of Origin
4 Delivery from (location)
5 Type & Designation
6 Type tested at Name of Laboratory Address of laboratory
7 Installation (indoor or outdoor)
8 Standards applicable
9 No. of Phases
10 Single or Three Phase design
11 Configuration
i Number of Feeder bays
ii Number of transformer bays
iii Number of Bus coupler bay
iv GIS to transformer connection
v GIS to Feeder connection
vi Number of VT
vii Number of SA
Future extension possibility
12 Service conditions
i Ambiant Air Temp. in Deg. C
ii Max Temp. in Deg. C
iii Min Temp. in Deg. C
iv Daily Average Temp. in Deg. C
v Solar Radiation W/sq mtr
vi Altitude above MSL, in mtr
vii Pollution class
viii Creepage distance, in mm/kV
ix Relative humidity
xi Vibration level
xii Noise level
xiii Induced Electromagnetic Disturbance, in kV
xiv Seismic conditions
i Code of pressure vessel
ii Type of manufacturing
iii Design temperature in Deg.C
v Material grade & applicable standard
vi Outside diameter in mm
vii Minimum Wall Thickness, in mm
viii Painting Shade & Thickness
ix Degree of Protection
x Inductance in H/mt
xi Capacitance in pF/mt
xii Resistance in Ohm/mt
xiii Expansion Bellow
b Min allowable adjustable displacement Longitudinal Transverse
xiv Sealing system
xv Estimated life in years
b Dielectric strength
14 Support Structure
ii Minimum thickness of galvanizing
iii Foundation channels /Anchor bolts
i Grounding Material
ii Grounding of complete GIS
iii Grounding of individual compartment
iv Grounding at flange joints
16 System Parameters
i Highest System voltage in kV
ii Rated voltage of System in kV
iii Rated voltage of Equipment in kV
iv Rated Insulation level Phase to Earth and between Phases
a One Min Power Frequency withstand voltage kVrms
b Switching impulse withstand voltage, kVp
- Phase to Earth
- Between Phases
c Lightning Impulse withstand voltage, kVp
iv Rated Frequency
v Rated current in Amp
vi Rated current at 50 °C (equipment) in Amp
vii Rated current at 50 °C (bus bar) in Amp
viii Rated short circuit withstand current kArms
a Duration in sec
ix Enclosure withstand time for an internal fault in sec.
x Estimated total energy loss at
100 % of rated capacity
75 % of rated capacity
50 % of rated capacity
25 % of rated capacity
xi Measures taken to minimize Over Voltage
xii Phase labeling
xiii Auxiliary supply (AC Voltage, Frequency; DC voltage)
- Illumination & heater
17 Delivery conditions
i Bays fully assembled at works
ii Dimensions of longest section for transportation
iii Weight of heaviest package
iv Pressure of SF6 gas during transportation
v SF6 gas monitoring system provided during transportation
i Configuration (Single / Double)
ii Nos of Phases
vi Current density adopted
vii Current density as per type test report
viii Short time current withstand rating in kA
x Resistance per phase
xi Surge impedance
xii SF6 immersed insulator
b Dielectric strength
xiv Maximum Partial Discharges measured at HSV
i Applicable standard
ii Quantity of SF6 Gas of complete GIS at filling pressure, in kg
iii Quantity of SF6 Gas of largest compartment GIS at filling pressure, in kg
iv Nos of Gas compartments
v Quantity of SF6 Gas of individual compartment GIS at filling pressure, in kg
vi Maximum permissible dew point, in Deg.C
vii Composition of Gas
a SF6 > 99.90 % by weight
b Air < 500 ppm by weight (0 25 vol -%)
c CF4 < 500 ppm by weight (0.1 vol -%)
d H2O < 15 ppm by weight (0.012 Vol-%)
e Mineral oil < 10 ppm by weight
f Acidity, in terms of HF < 0.3 ppm by weight
g Hydrolysable fluorides In terms of HF < 1 ppm by weight
vii Design pressure
a Circuit breaker
b Other compartments
ix Rated filling pressure
a Circuit breaker
b Other compartments
x Type tested pressure.
a Circuit breaker
b Other compartments
xi Routine test pressure
a Circuit breaker
b Other compartments
xii Operating pressure of PRD
a Circuit breaker
b Other compartments
xiii Alarm Pressure
a Circuit breaker
b Other compartments
c CB lock out Pressure
d Over pressure signaling
xiv Maximum SF6 Gas leakage rate, in % per year
xv Density Monitor to be provided for each Individual gas compartment.
20 Circuit Breaker
i Applicable standard
iii Designation
iv Operating Mechanism type
v Nos. of phases
vi Rated current in Amp
vii Mechanical Endurance class
viii Electrical Endurance class
ix Restrike probability class
x Rated SC breaking current
xi Rated SC breaking current - single phase test
xii Rated Line charging breaking current
xiii Rated Cable charging breaking current
xiv Capacitor bank switching capability,
xv Inductive current
xvi Reactive current
xvii Out of phase making & breaking current
xviii Rated short line fault current
xix TRV characteristic
xx First Pole to Clear factor
xxi Nos. of interrupters per phase
xxii Type of arc control device provided, if any
xxiii Type of arcing contacts
xxiv Material of main contact
xxv Material of Arcing contacts
xxvi Filter material
xxvii Timings of operations
a - Opening at nominal control voltage
- Opening at minimum control voltage
b Closing time at nominal control voltage
xxviii Maximum pole discrepancy time Tripping Closing
xxix Rated operating duty cycle
xxx Tripping Coils
- Rated Voltage
- Rated Current
xxxi Closing Coil
- Rated Voltage
- Rated Current
xxxii Spring Charging Motor
- Rated Voltage
- Rated Current
xxxiii Spring charging time at rated Aux supply
xxxiv Spring charging time at min Aux supply
xxxv Maintenance required after nos. of operation at
ii Rated current
iii 25% of rated SC current
iv 50% rated SC current
v Rated SC current
e Provision of anti pumping
f No of operations after switching off of motor Aux. supply
xxxvi Provision of Manual trip
xxxvii Electrical interlocking
xxxviii Padlocking
xxxix Type of Operation counter provided
21 DISCONNECTORS
i Applicable standards
iii Rated current in Amp for
- Bus disconnector
- Line disconnector
- Transformer disconnector
- PT disconnector
iv Maximum Current that can be safely interrupted by the Isolator (Amp).
v Rate Short time withstand Current in kA, for 3 sec
vi Rated peak short time Current, kAp
vii Rated bus charging current, in Amp
viii Type of contacts
ix Material of contacts
x Current Density at minimum cross section (A/mm2)
xi Rated lightning impulse withstand voltage across the open gap, kVp
xii Rated Power Freq withstand voltage across the open gap, kVrms
xiii Mechanical Endurance class
xiv Type of Operating Mechanism
xv Operating Motor details
- Rated Voltage
- Rated Current
xvi Operating Time
- Closing - Opening
xvii Mechanical indication on drive shaft
22 Maintenance Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated lightning impulse withstand voltage across the open gap, kVp
vi Rated Power Freq withstand voltage across the open gap, kVrms
vii Type of Operating Mechanism
viii Operating Motor details
- Rated Voltage
- Rated Current
ix Operating Time
- Closing - Opening
x Mechanical indication on drive shaft
23 Fast Acting Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated induced current switching capability Rated capacitive current switching capability
vi Rated lightning impulse withstand voltage across the open gap, kVp
vii Rated Power Freq withstand voltage across the open gap, kVrms
viii Electrical Endurance class
ix Type of Operating Mechanism
x Operating Motor details
- Rated Voltage
- Rated Current
xi Operating Time
- Closing - Opening
xii Mechanical indication on drive shaft
24 Current transformers
iii Position of Current Transformer
iv Reference Standard
v Rated Continuous thermal current
vi Rated Short Time current
a Feeder Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
b Transformer Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
iv Protection Core -3
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
c Bus Coupler Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Accuracy Class
iii Protection Core -2
- Accuracy Class
25 Voltage Transformer
Position of Voltage Transformer
Reference Standard
Rated Over Voltage Factor - Continuous
Short Time Over Voltage Factor
Partial Discharge Level
Thermal Rating of Primary Winding
26 Line & Bus VT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
27 Enclosed Surge Arrester
ii Name of Manufacturer
iii Arrester Class & Type (with mfr type designation)
iv Applicable Standard
v Rated system voltage (kV)
vi Rated Arrester Voltage (kV)
vii Max continuous operating voltage (MCOV) – (kV)
viii i)Nominal Discharge Current (KA) with 8/20 Micro-second wave
ii)Max resistive component of cont current at MCOV-mA crest
iii)Max capacitive component of cont current at MCOV -mA crest
ix Long Duration Discharge Class
x Min. Energy Discharge Capability (KJ/KV rating)
xi Max. switching current impulse residual voltage (KVP) 1000 Amps 250 Amps
xii Pressure Relief Class KA (rms)
xiii High Current short duration impulse withstand level with 4/10 micro-second wave (KA) peak
xiv Over –voltage withstand capability – KV
e) Reference Voltage (KV)
f) Reference Current (KA)
xv Surge counter
xvi Leakage monitor
28 Local Control Cubical
i Name of Manufacturer (OEM of GIS)
ii Location in GIS
iv Sheet Thickness
v Degree of Protection
vi Padlocking arrangement
vii Major components of LCC
- Bay control mimic diagram
- Control Switches
- Indicating lamps
- Position indicators
- Annunciation scheme
- Auxiliary relays
- Contact multiplication relays
- System parameters display
- Heater with thermostat
- Interface terminal blocks for relaying & protection
29 GIS to Line connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
30 GIS to Transformer connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
i Maximum down time for replacement or removal of any part
ii Maximum down time for degassing and re- filling the biggest compartment
iii Time between two refilling of SF6 gas.
iv Recommended period for overhauling
v Operation and Maintenance manual attached
vi Nearest local service centre
vii Minimum time of availability of local service
viii Availability of spares at local service centre
ix List of recommended spares attached?
x List of recommended special tools, etc attached?
xi List of commission spares attached?
xii List of maintenance spares attached?
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 220 KV GIS PANEL
Name of the Tenderer
As per Tenderer
Sl. No. DESCRIPTION Transformer Bay Line bay Bus Coupler
Name of manufacturer (OEM)
Country of Origin
Delivery from (location)
Type & Designation
Type tested at Name of Laboratory Address of laboratory
Installation (indoor or outdoor)
Standards applicable
Single or Three Phase design
i Number of Feeder bays
ii Number of transformer bays
iii Number of Bus coupler bay
iv GIS to transformer connection
v GIS to Feeder connection
vi Number of VT
vii Number of SA
Future extension possibility
Service conditions
i Ambiant Air Temp. in Deg. C
ii Max Temp. in Deg. C
iii Min Temp. in Deg. C
iv Daily Average Temp. in Deg. C
v Solar Radiation W/sq mtr
vi Altitude above MSL, in mtr
vii Pollution class
viii Creepage distance, in mm/kV
ix Relative humidity
xi Vibration level
xii Noise level
xiii Induced Electromagnetic Disturbance, in kV
xiv Seismic conditions
i Code of pressure vessel
ii Type of manufacturing
iii Design temperature in Deg.C
v Material grade & applicable standard
vi Outside diameter in mm
vii Minimum Wall Thickness, in mm
viii Painting Shade & Thickness
ix Degree of Protection
x Inductance in H/mt
xi Capacitance in pF/mt
xii Resistance in Ohm/mt
xiii Expansion Bellow
b Min allowable adjustable displacement Longitudinal Transverse
xiv Sealing system
xv Estimated life in years
b Dielectric strength
Support Structure
ii Minimum thickness of galvanizing
iii Foundation channels /Anchor bolts
i Grounding Material
ii Grounding of complete GIS
iii Grounding of individual compartment
iv Grounding at flange joints
System Parameters
i Highest System voltage in kV
ii Rated voltage of System in kV
iii Rated voltage of Equipment in kV
iv Rated Insulation level Phase to Earth and between Phases
a One Min Power Frequency withstand voltage kVrms
b Switching impulse withstand voltage, kVp
- Phase to Earth
- Between Phases
c Lightning Impulse withstand voltage, kVp
iv Rated Frequency
v Rated current in Amp
vi Rated current at 50 °C (equipment) in Amp
vii Rated current at 50 °C (bus bar) in Amp
viii Rated short circuit withstand current kArms
a Duration in sec
ix Enclosure withstand time for an internal fault in sec.
x Estimated total energy loss at
100 % of rated capacity
75 % of rated capacity
50 % of rated capacity
25 % of rated capacity
xi Measures taken to minimize Over Voltage
xii Phase labeling
xiii Auxiliary supply (AC Voltage, Frequency; DC voltage)
- Illumination & heater
Delivery conditions
i Bays fully assembled at works
ii Dimensions of longest section for transportation
iii Weight of heaviest package
iv Pressure of SF6 gas during transportation
v SF6 gas monitoring system provided during transportation
i Configuration (Single / Double)
ii Nos of Phases
vi Current density adopted
vii Current density as per type test report
viii Short time current withstand rating in kA
x Resistance per phase
xi Surge impedance
xii SF6 immersed insulator
b Dielectric strength
xiv Maximum Partial Discharges measured at HSV
i Applicable standard
ii Quantity of SF6 Gas of complete GIS at filling pressure, in kg
iii Quantity of SF6 Gas of largest compartment GIS at filling pressure, in kg
iv Nos of Gas compartments
v Quantity of SF6 Gas of individual compartment GIS at filling pressure, in kg
vi Maximum permissible dew point, in Deg.C
vii Composition of Gas
a SF6 > 99.90 % by weight
b Air < 500 ppm by weight (0 25 vol -%)
c CF4 < 500 ppm by weight (0.1 vol -%)
d H2O < 15 ppm by weight (0.012 Vol-%)
e Mineral oil < 10 ppm by weight
f Acidity, in terms of HF < 0.3 ppm by weight
g Hydrolysable fluorides In terms of HF < 1 ppm by weight
vii Design pressure
a Circuit breaker
b Other compartments
ix Rated filling pressure
a Circuit breaker
b Other compartments
x Type tested pressure.
a Circuit breaker
b Other compartments
xi Routine test pressure
a Circuit breaker
b Other compartments
xii Operating pressure of PRD
a Circuit breaker
b Other compartments
xiii Alarm Pressure
a Circuit breaker
b Other compartments
c CB lock out Pressure
d Over pressure signaling
xiv Maximum SF6 Gas leakage rate, in % per year
xv Density Monitor to be provided for each Individual gas compartment.
Circuit Breaker
i Applicable standard
iii Designation
iv Operating Mechanism type
v Nos. of phases
vi Rated current in Amp
vii Mechanical Endurance class
viii Electrical Endurance class
ix Restrike probability class
x Rated SC breaking current
xi Rated SC breaking current - single phase test
xii Rated Line charging breaking current
xiii Rated Cable charging breaking current
xiv Capacitor bank switching capability,
xv Inductive current
xvi Reactive current
xvii Out of phase making & breaking current
xviii Rated short line fault current
xix TRV characteristic
xx First Pole to Clear factor
xxi Nos. of interrupters per phase
xxii Type of arc control device provided, if any
xxiii Type of arcing contacts
xxiv Material of main contact
xxv Material of Arcing contacts
xxvi Filter material
xxvii Timings of operations
a - Opening at nominal control voltage
- Opening at minimum control voltage
b Closing time at nominal control voltage
xxviii Maximum pole discrepancy time Tripping Closing
xxix Rated operating duty cycle
xxx Tripping Coils
- Rated Voltage
- Rated Current
xxxi Closing Coil
- Rated Voltage
- Rated Current
xxxii Spring Charging Motor
- Rated Voltage
- Rated Current
xxxiii Spring charging time at rated Aux supply
xxxiv Spring charging time at min Aux supply
xxxv Maintenance required after nos. of operation at
ii Rated current
iii 25% of rated SC current
iv 50% rated SC current
v Rated SC current
e Provision of anti pumping
f No of operations after switching off of motor Aux. supply
xxxvi Provision of Manual trip
xxxvii Electrical interlocking
xxxviii Padlocking
xxxix Type of Operation counter provided
i Applicable standards
iii Rated current in Amp for
- Bus disconnector
- Line disconnector
- Transformer disconnector
- PT disconnector
iv Maximum Current that can be safely interrupted by the Isolator (Amp).
v Rate Short time withstand Current in kA, for 3 sec
vi Rated peak short time Current, kAp
vii Rated bus charging current, in Amp
viii Type of contacts
ix Material of contacts
x Current Density at minimum cross section (A/mm2)
xi Rated lightning impulse withstand voltage across the open gap, kVp
xii Rated Power Freq withstand voltage across the open gap, kVrms
xiii Mechanical Endurance class
xiv Type of Operating Mechanism
xv Operating Motor details
- Rated Voltage
- Rated Current
xvi Operating Time
- Closing - Opening
xvii Mechanical indication on drive shaft
Maintenance Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated lightning impulse withstand voltage across the open gap, kVp
vi Rated Power Freq withstand voltage across the open gap, kVrms
vii Type of Operating Mechanism
viii Operating Motor details
- Rated Voltage
- Rated Current
ix Operating Time
- Closing - Opening
x Mechanical indication on drive shaft
Fast Acting Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated induced current switching capability Rated capacitive current switching capability
vi Rated lightning impulse withstand voltage across the open gap, kVp
vii Rated Power Freq withstand voltage across the open gap, kVrms
viii Electrical Endurance class
ix Type of Operating Mechanism
x Operating Motor details
- Rated Voltage
- Rated Current
xi Operating Time
- Closing - Opening
xii Mechanical indication on drive shaft
Current transformers
iii Position of Current Transformer
iv Reference Standard
v Rated Continuous thermal current
vi Rated Short Time current
a Feeder Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
b Transformer Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
iv Protection Core -3
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
c Bus Coupler Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Accuracy Class
iii Protection Core -2
- Accuracy Class
Voltage Transformer
Position of Voltage Transformer
Reference Standard
Rated Over Voltage Factor - Continuous
Short Time Over Voltage Factor
Partial Discharge Level
Thermal Rating of Primary Winding
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
Enclosed Surge Arrester
ii Name of Manufacturer
iii Arrester Class & Type (with mfr type designation)
iv Applicable Standard
v Rated system voltage (kV)
vi Rated Arrester Voltage (kV)
vii Max continuous operating voltage (MCOV) – (kV)
viii i)Nominal Discharge Current (KA) with 8/20 Micro-second wave
ii)Max resistive component of cont current at MCOV-mA crest
iii)Max capacitive component of cont current at MCOV -mA crest
ix Long Duration Discharge Class
x Min. Energy Discharge Capability (KJ/KV rating)
xi Max. switching current impulse residual voltage (KVP) 1000 Amps 250 Amps
xii Pressure Relief Class KA (rms)
xiii High Current short duration impulse withstand level with 4/10 micro-second wave (KA) peak
xiv Over –voltage withstand capability – KV
e) Reference Voltage (KV)
f) Reference Current (KA)
xv Surge counter
xvi Leakage monitor
Local Control Cubical
i Name of Manufacturer (OEM of GIS)
ii Location in GIS
iv Sheet Thickness
v Degree of Protection
vi Padlocking arrangement
vii Major components of LCC
- Bay control mimic diagram
- Control Switches
- Indicating lamps
- Position indicators
- Annunciation scheme
- Auxiliary relays
- Contact multiplication relays
- System parameters display
- Heater with thermostat
- Interface terminal blocks for relaying & protection
GIS to Line connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
GIS to Transformer connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
i Maximum down time for replacement or removal of any part
ii Maximum down time for degassing and re- filling the biggest compartment
iii Time between two refilling of SF6 gas.
iv Recommended period for overhauling
v Operation and Maintenance manual attached
vi Nearest local service centre
vii Minimum time of availability of local service
viii Availability of spares at local service centre
ix List of recommended spares attached?
x List of recommended special tools, etc attached?
xi List of commission spares attached?
xii List of maintenance spares attached?
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 132 KV GIS PANEL
Name of the Tenderer
As per Tenderer
Sl. No. DESCRIPTION Transformer Bay Line bay Bus Coupler
Name of manufacturer (OEM)
Country of Origin
Delivery from (location)
Type & Designation
Type tested at Name of Laboratory Address of laboratory
Installation (indoor or outdoor)
Standards applicable
Single or Three Phase design
i Number of Feeder bays
ii Number of transformer bays
iii Number of Bus coupler bay
iv GIS to transformer connection
v GIS to Feeder connection
vi Number of VT
vii Number of SA
Future extension possibility
Service conditions
i Ambiant Air Temp. in Deg. C
ii Max Temp. in Deg. C
iii Min Temp. in Deg. C
iv Daily Average Temp. in Deg. C
v Solar Radiation W/sq mtr
vi Altitude above MSL, in mtr
vii Pollution class
viii Creepage distance, in mm/kV
ix Relative humidity
xi Vibration level
xii Noise level
xiii Induced Electromagnetic Disturbance, in kV
xiv Seismic conditions
i Code of pressure vessel
ii Type of manufacturing
iii Design temperature in Deg.C
v Material grade & applicable standard
vi Outside diameter in mm
vii Minimum Wall Thickness, in mm
viii Painting Shade & Thickness
ix Degree of Protection
x Inductance in H/mt
xi Capacitance in pF/mt
xii Resistance in Ohm/mt
xiii Expansion Bellow
b Min allowable adjustable displacement Longitudinal Transverse
xiv Sealing system
xv Estimated life in years
b Dielectric strength
Support Structure
ii Minimum thickness of galvanizing
iii Foundation channels /Anchor bolts
i Grounding Material
ii Grounding of complete GIS
iii Grounding of individual compartment
iv Grounding at flange joints
System Parameters
i Highest System voltage in kV
ii Rated voltage of System in kV
iii Rated voltage of Equipment in kV
iv Rated Insulation level Phase to Earth and between Phases
a One Min Power Frequency withstand voltage kVrms
b Switching impulse withstand voltage, kVp
- Phase to Earth
- Between Phases
c Lightning Impulse withstand voltage, kVp
iv Rated Frequency
v Rated current in Amp
vi Rated current at 50 °C (equipment) in Amp
vii Rated current at 50 °C (bus bar) in Amp
viii Rated short circuit withstand current kArms
a Duration in sec
ix Enclosure withstand time for an internal fault in sec.
x Estimated total energy loss at
100 % of rated capacity
75 % of rated capacity
50 % of rated capacity
25 % of rated capacity
xi Measures taken to minimize Over Voltage
xii Phase labeling
xiii Auxiliary supply (AC Voltage, Frequency; DC voltage)
- Illumination & heater
Delivery conditions
i Bays fully assembled at works
ii Dimensions of longest section for transportation
iii Weight of heaviest package
iv Pressure of SF6 gas during transportation
v SF6 gas monitoring system provided during transportation
i Configuration (Single / Double)
ii Nos of Phases
vi Current density adopted
vii Current density as per type test report
viii Short time current withstand rating in kA
x Resistance per phase
xi Surge impedance
xii SF6 immersed insulator
b Dielectric strength
xiv Maximum Partial Discharges measured at HSV
i Applicable standard
ii Quantity of SF6 Gas of complete GIS at filling pressure, in kg
iii Quantity of SF6 Gas of largest compartment GIS at filling pressure, in kg
iv Nos of Gas compartments
v Quantity of SF6 Gas of individual compartment GIS at filling pressure, in kg
vi Maximum permissible dew point, in Deg.C
vii Composition of Gas
a SF6 > 99.90 % by weight
b Air < 500 ppm by weight (0 25 vol -%)
c CF4 < 500 ppm by weight (0.1 vol -%)
d H2O < 15 ppm by weight (0.012 Vol-%)
e Mineral oil < 10 ppm by weight
f Acidity, in terms of HF < 0.3 ppm by weight
g Hydrolysable fluorides In terms of HF < 1 ppm by weight
vii Design pressure
a Circuit breaker
b Other compartments
ix Rated filling pressure
a Circuit breaker
b Other compartments
x Type tested pressure.
a Circuit breaker
b Other compartments
xi Routine test pressure
a Circuit breaker
b Other compartments
xii Operating pressure of PRD
a Circuit breaker
b Other compartments
xiii Alarm Pressure
a Circuit breaker
b Other compartments
c CB lock out Pressure
d Over pressure signaling
xiv Maximum SF6 Gas leakage rate, in % per year
xv Density Monitor to be provided for each Individual gas compartment.
Circuit Breaker
i Applicable standard
iii Designation
iv Operating Mechanism type
v Nos. of phases
vi Rated current in Amp
vii Mechanical Endurance class
viii Electrical Endurance class
ix Restrike probability class
x Rated SC breaking current
xi Rated SC breaking current - single phase test
xii Rated Line charging breaking current
xiii Rated Cable charging breaking current
xiv Capacitor bank switching capability,
xv Inductive current
xvi Reactive current
xvii Out of phase making & breaking current
xviii Rated short line fault current
xix TRV characteristic
xx First Pole to Clear factor
xxi Nos. of interrupters per phase
xxii Type of arc control device provided, if any
xxiii Type of arcing contacts
xxiv Material of main contact
xxv Material of Arcing contacts
xxvi Filter material
xxvii Timings of operations
a - Opening at nominal control voltage
- Opening at minimum control voltage
b Closing time at nominal control voltage
xxviii Maximum pole discrepancy time Tripping Closing
xxix Rated operating duty cycle
xxx Tripping Coils
- Rated Voltage
- Rated Current
xxxi Closing Coil
- Rated Voltage
- Rated Current
xxxii Spring Charging Motor
- Rated Voltage
- Rated Current
xxxiii Spring charging time at rated Aux supply
xxxiv Spring charging time at min Aux supply
xxxv Maintenance required after nos. of operation at
ii Rated current
iii 25% of rated SC current
iv 50% rated SC current
v Rated SC current
e Provision of anti pumping
f No of operations after switching off of motor Aux. supply
xxxvi Provision of Manual trip
xxxvii Electrical interlocking
xxxviii Padlocking
xxxix Type of Operation counter provided
i Applicable standards
iii Rated current in Amp for
- Bus disconnector
- Line disconnector
- Transformer disconnector
- PT disconnector
iv Maximum Current that can be safely interrupted by the Isolator (Amp).
v Rate Short time withstand Current in kA, for 3 sec
vi Rated peak short time Current, kAp
vii Rated bus charging current, in Amp
viii Type of contacts
ix Material of contacts
x Current Density at minimum cross section (A/mm2)
xi Rated lightning impulse withstand voltage across the open gap, kVp
xii Rated Power Freq withstand voltage across the open gap, kVrms
xiii Mechanical Endurance class
xiv Type of Operating Mechanism
xv Operating Motor details
- Rated Voltage
- Rated Current
xvi Operating Time
- Closing - Opening
xvii Mechanical indication on drive shaft
Maintenance Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated lightning impulse withstand voltage across the open gap, kVp
vi Rated Power Freq withstand voltage across the open gap, kVrms
vii Type of Operating Mechanism
viii Operating Motor details
- Rated Voltage
- Rated Current
ix Operating Time
- Closing - Opening
x Mechanical indication on drive shaft
Fast Acting Grounding Switch
i Applicable standards
iii Rate Short time withstand Current in kA, for 3 sec
iv Rated peak short time Current, kAp
v Rated induced current switching capability Rated capacitive current switching capability
vi Rated lightning impulse withstand voltage across the open gap, kVp
vii Rated Power Freq withstand voltage across the open gap, kVrms
viii Electrical Endurance class
ix Type of Operating Mechanism
x Operating Motor details
- Rated Voltage
- Rated Current
xi Operating Time
- Closing - Opening
xii Mechanical indication on drive shaft
Current transformers
iii Position of Current Transformer
iv Reference Standard
v Rated Continuous thermal current
vi Rated Short Time current
a Feeder Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
b Transformer Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
iv Protection Core -3
- Accuracy Class
- Minimum Knee Point Voltage at highest ratio
- Maximum Excitation Current at Vk
- Maximum Resistance at highest ratio
c Bus Coupler Bay CT
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Accuracy Class
iii Protection Core -2
- Accuracy Class
Voltage Transformer
Position of Voltage Transformer
Reference Standard
Rated Over Voltage Factor - Continuous
Short Time Over Voltage Factor
Partial Discharge Level
Thermal Rating of Primary Winding
i Metering Core
- Output Burden
- Accuracy Class
ii Protection Core -1
- Output Burden
- Accuracy Class
iii Protection Core -2
- Output Burden
- Accuracy Class
Enclosed Surge Arrester
ii Name of Manufacturer
iii Arrester Class & Type (with mfr type designation)
iv Applicable Standard
v Rated system voltage (kV)
vi Rated Arrester Voltage (kV)
vii Max continuous operating voltage (MCOV) – (kV)
viii i)Nominal Discharge Current (KA) with 8/20 Micro-second wave
ii)Max resistive component of cont current at MCOV-mA crest
iii)Max capacitive component of cont current at MCOV -mA crest
ix Long Duration Discharge Class
x Min. Energy Discharge Capability (KJ/KV rating)
xi Max. switching current impulse residual voltage (KVP) 1000 Amps 250 Amps
xii Pressure Relief Class KA (rms)
xiii High Current short duration impulse withstand level with 4/10 micro-second wave (KA) peak
xiv Over –voltage withstand capability – KV
e) Reference Voltage (KV)
f) Reference Current (KA)
xv Surge counter
xvi Leakage monitor
Local Control Cubical
i Name of Manufacturer (OEM of GIS)
ii Location in GIS
iv Sheet Thickness
v Degree of Protection
vi Padlocking arrangement
vii Major components of LCC
- Bay control mimic diagram
- Control Switches
- Indicating lamps
- Position indicators
- Annunciation scheme
- Auxiliary relays
- Contact multiplication relays
- System parameters display
- Heater with thermostat
- Interface terminal blocks for relaying & protection
GIS to Line connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
GIS to Transformer connection
i Nos of XLPE cable can be terminated
ii Type of cable termination required
i Maximum down time for replacement or removal of any part
ii Maximum down time for degassing and re- filling the biggest compartment
iii Time between two refilling of SF6 gas.
iv Recommended period for overhauling
v Operation and Maintenance manual attached
vi Nearest local service centre
vii Minimum time of availability of local service
viii Availability of spares at local service centre
ix List of recommended spares attached?
x List of recommended special tools, etc attached?
xi List of commission spares attached?
xii List of maintenance spares attached?
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 33 KV INDOOR GIS PANEL
Name of the Tenderer
Sl. No. DESCRIPTION UNITS As per Tenderer
Transformer Bay Line bay Bus Sectionalizer PT Module LT Transformer Module
1 SITE CONDITIONS
1.01 Altitude meters
1.02 Maximum Ambient Temperature °C
1.03 Minimum Ambient Temperature °C
1.04 Design Ambient Temperature °C
1.05 Relative Humidity %
2.01 Voltage kV
2.03 Frequency Hz
2.04 Short Time Rating for 3 Sec kA
2.05 Voltage Class kV
2.06 Insulation level (PF rms /Impulse peak) kVrms / kVpeak
2.07 Internal arc test
a Rated current and duration kA, sec
b Classification
3 ENCLOSURE TYPE
3.01 Rear Doors -
3.02 Indoor / Outdoor -
3.03 Arc Resistant -
3.04 Tamperproof Category
3.05 Dust resistant (gasketed) -
4 PANEL CONSTRUCTION
4.01 Gas pressure – busbar compartment Bar / MPa
a Normal gas pressure Bar / MPa
b Permitted range of Gas pressure for safe operation Bar / MPa
c Alarm level Bar / MPa
d Gas pressure for operation of PRD Bar / MPa
e Withstand gas pressure of enclosure Bar / MPa
f Number of aux.contacts /stages provided for the gas density meter
4.02 Gas pressure – breaker compartment Bar / MPa
a Normal gas pressure Bar / MPa
b Permitted range of Gas pressure for safe operation Bar / MPa
c Alarm level Bar / MPa
d Gas pressure for operation of PRD Bar / MPa
e Withstand gas pressure of enclosure Bar / MPa
Number of aux. Contacts /stages provided for the gas density meter Nos.
4.03 Material and thickness of gas enclosure
4.04 Total no. of Gas compartments per panel No.
4.05 Number of Gas Density meters provided per panel No.
4.06 Rating of Isolator (A) Amp.
4.07 Rating of earthing switch (A) Amp.
4.07 Guaranteed Gas leakage Rate
4.08 Rodent damage protection
4.09 Ground and test device
4.1 Equipment Labeling
4.11 Lift truck
4.12 Testing facility
5 BUS INFORMATION
5.02 Bus Joint Plating
5.03 Rated Continuous Current A rms
5.04 Short time Withstand Current A rms
6 BUS SUPPORTS AND INSULATION
6.01 Manufacturer's Standard & Type
7 POWER CABLE ACCOMMODATION
7.01 Power Cable entry
7.02 Terminal lug type
7.03 Qty of power cables per phase per compartment
7.04 Make of termination
8 CIRCUIT BREAKER INFORMATION
8.01 Manufacturer / Model No.
8.02 Type (SF6/Vacuum)
8.03 Rated Short-Circuit Current kA
8.04 Short circuit-Current Withstand Time sec
8.05 Rated Maximum Voltage kV rms
8.06 Rated Voltage Range Factor,K
8.07 Power Frequency Withstand Voltage kV rms
8.08 Lightning Impulse Withstand Voltage kV crest
8.09 Rated Continuous Current A rms
8.1 Rated Transient Recovery Voltage Time to Peak (T2) microsec
8.11 Switching duty/capability
a Power Transformers (oil filled) Capacity
b Cables Length
c Over head lines Length
8.12 Rated Interrupting Time ms
8.13 Time for Opening Operation cycles
8.14 Time for Closing Operation cycles
8.15 Closing and latching capability (peak) kA
8.16 Control Power Voltage Range, Trip Coil V dc
8.17 Control Power Voltage Range, Closing Coil V dc
8.18 Auxiliary Contacts Total qty
8.19 Min. Auxiliary Contacts for Customer use qty
8.2 Auxiliary Contact voltage rating V dc
8.21 Auxiliary Contact current rating Amps
8.22 Stored Energy System Minimum Voltage V dc
8.23 Stored Energy Spring Charging Motor Current Amps
8.24 Stored Energy Spring Charging Motor Inrush Amps
8.25 Stored Energy Time to Fully Recharge Spring: seconds
8.26 Rated Operating duty cycle
8.27 Rated out of phase switching capability to IEC 56
8.28 Operating Power Consumption
a Trip Coil Watt
b Closing Coil Watt
c Operating Motor Watt
8.29 Number of trip coils Nos.
8.3 Quantity of Gas in CB
b Volume at Normal Pressure CuM
8.31 Interrupting Gas Pressure Maximum / Normal / Minimum Bar
Number of Close / Open
8.32 Operation No.
possible without re-charging
Number of operations
8.33 possible before interrupter maintenance required
a At rated S.C. current Nos.
b At full load current Nos.
c At no load Nos.
Method used to relieve
8.34 internal overpressure due to short circuit (Bursting disc /relief valve / none. Etc.)
8.35 Operating pressure of pressure relief device
9 PROTECTIVE RELAYS
9.01 Manufacturer
9.02 Model no. of each relay
9.03 Relay functions
9.04 Relay Communication
10 INDICATING METERS
c Auxilairy suppy
10.02 Voltmeter
c Auxilairy supply
11 CONTROL WIRING
11.02 Control wire Size minimum:
11.03 Voltage Rating: Vac
11.04 FRLS type
12 CURRENT TRANSFORMERS
(Details to be furnished for each type of CT)
12.01 Manufacturer/Model Number:
12.02 Accuracy Class
12.05 Knee point voltage
12.07 Excitation current
13 VOLTAGE TRANSFORMERS
13.01 Manufacturer
13.02 Model Number
13.04 Primary Fuse
13.05 Secondary Fuse/min-breaker:
13.07 Disconnecting switch for VT
14 PANEL ACCESSORIES
14.01 Indications
14.02 Control switches
14.03 L/R switch
14.04 CT & PT Terminal blocks
14.05 Terminal blocks
15.01 Bus Losses Watts
15.02 Heat loss at rated breaker current –1250A W/bkr
15.03 Heat loss of space heater per vertical section W/vrtl
16 INSTALLATION INFORMATION
16.01 Mass of heaviest piece to be shipped as a unit kg
16.02 Largest section to be shipped a unit -Length: mm
16.03 Largest section to be shipped a unit -Width: mm
16.04 Largest section to be shipped a unit -Height: mm
16.05 Total Mass of assembly to be shipped kg
16.06 Total assembly (breaker line- up only) -Length mm
16.07 Total assembly (breaker line-up only) -Width mm
16.08 Total assembly (breaker line-up only) -Height mm
16.09 Transition section (breaker line-up only) -Mass kg
16.1 Transition section (breaker mm
line-up only) -Length
16.11 Transition section (breaker line-up only) -Width mm
16.12 Transition section (breaker line-up only) -Height mm
16.13 Total Number of shipping sections per line up: qty
17 PANEL DIMENSIONS
17.01 Incomer (Width x Depth x Height) mm
17.02 Bus-coupler (Width x Depth x Height) mm
17.03 Outgoing (Width x Depth x Height) mm
17.04 Overall length of Complete board mm
18 CONTROL AND AUXILIARY SUPPLY
18.01 Control power supply (Volts)
18.02 Control power current rating (A)
18.03 control power supply short circuit level
18.04 AC power supply (Volts)
18.05 AC power supply current rating (A)
18.06 AC power supply short circuit rating (kA)
19 PAINTING / FINISHING
19.01 Manufacturer's Standard
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.1 4.1 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR DG SET
Name of the tendering company
Sl.No Description As per Tenderer
1.1 Name & Address of Manufacturer
1.3 Manufacturer’s Name, type and Address for
a) Diesel Engine alongwith accessories
e) Battery Charger
f) D.G. Set control Panel for site condition
2.3 No of strokes
2.4 Type of Governor
2.5 Guaranteed fuel consumption
a) At full load
2,6 Lubricating oil consumption
2,7 Mechanical efficiency
2.8 Thermal efficiency
2,9 Total weight
2.1 Rated KW capacity
2.2 Rated Terminal Voltage
2.3 Rated Power Factor
2.4 Rated Speed
2.5 Rated Frequency
2.6 No of phases
2.7 Efficiencies and power factor at 110%, 100% ,75%,50% and 25% of full load
2.8 Permissible Temperature rise
a) Armature winding
b) Field winding
2.9 Overload capacity
2.1 Applicable standards
4.2 SCHEDULE OF THE GUARANTEED TECHNICAL PARTICULARS FOR PLCC EQUIPMENT
Name of the tendering company
Sl. No. Description As per Tenderer
A COUPLING DEVICE (Phase to Phase Type)
1 Name of Manufacturer and Country
2 Type, Model and Catalogue Number
3 Nominal primary side impedance
4 Nominal secondary side impedance
5 Composite loss with in pass-band
6 Return loss with in pass-band
7 Available Bandwidth (with 4400/6600/8800 pF CVTS)
8 Nominal Peak Envelope Power (with Distortion and Inter modulation Products 80 dB down)
9 Maximum number of PLC terminals that can be connected in parallel:
a) 20 W (PEP) PlC terminals
b) 40 W (PEP)PLC terminals
c) 100 W(PEP) PLC terminals
10 Power Frequency Impedance between primary terminal and Earth Terminals of Coupling Device
11 Maximum temperature rise over ambient 50°C due to rated current in main contacts, measured after breaking test
12 No of H.F. terminals provided for carrier equipment connection
HIGH FREQUENCY CABLE
1 Name of Manufacturer and country
2 Type, Model and Catalogue no.
3 Applicable standards
4 Maximum attenuation per km of cable for carrier Frequency range 40 to 500 kHz
5 Maximum loop resistance/ km of cable
POWER LINE CARRIER TERMINAL FOR SPEECH AND DATA TRANSMISSION OR NETWORK PROTECTION
1 Name of Manufacturer and country
2 Type, Model and Catalogue no.
3 Type of Modulation
4 Mode of transmission
5 Carrier Frequency Range
6 Nominal carrier frequency band in either direction of transmission
7 Return loss within the nominal carrier frequency band
8 Effectively transmitted V.F. band
b) For telephone signaling
9 Return Loss within the effectively transmitted voice frequency band
10 Maximum H.F Amplifier output with single /Multiple tone keying (Peak Envelope Power )
11 Nominal carrier frequency power (peak envelop power) at output terminals
VF TRANSMISSION TERMINAL FOR NETWORK PROTECTION SIGNALS (PROTECTION COUPLER)
1 Name of Manufacturer and country
2 Type, Model and catalogue number
3 Whether equipment works on frequency shift principle of coded signal principle
4 Whether Equipment is suitable for independently protecting two circuits
5 Frequencies used in the equipment for transmission of signal for un-coded signal transmission
a) Guard frequency
b) Working frequency (Trip system-I)
c) Working frequency (Trip system-II)
d) Working frequency (Trip system (I&II)
6 Criteria used for command transmission
7 Transmission time corresponding to telegraph speed for transmission on PLCC channel of coded signal
8 Mode of transmission of guard signal
9 Whether equipment is suitable for Direct circuit breaker tripping.
10 Whether loop test is possible
11 Whether the equipment is suitable for transmitting and receiving more than two independent commands (please furnish details)
12 Whether receiver design provides protection against false tripping from random noise
1 Name of Manufacturer and country
3 System Voltage Rating
4 Continuous current rating at 50°C ambient
5 Continuous current rating at 65°C
6 Maximum Symmetrical short circuit current rating for 1 sec. duration
7 Asymmetric peak value of first half wave of rated short time current
8 Rated Inductance
9 Blocking Range
10 Minimum Guaranteed Resistive component in blocking frequency range
11 Details of protection of capacitors and coils against voltage surges. Indicate type of protective device.
12 Rated voltage of the arrestor (protective device )
ELECTRONIC PRIVATE AUTOMATIC EXCHANGE (EPAX)
1 Name of manufacturer
2 Type and model
3 Capacity of exchange (Subscribers & trunk lines)
4 Whether compatible to both i.e PLCC & DOT lines for communication
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.3 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR FIRE PROTECTION SYSTEM
Name of the tendering company
Sl.No Description As per Tenderer
1 Name and Address of the fire protection system supplier
2 Number of Fire Protection System executed by the supplier and duration of successful operation as on date of bid opening for each type fire protection system
a) Automatic HVW / MVW spray type fire protection system
b) Automatic Hydrant type fire protection system
3 Confirm that fire protection system supplier have designed, erected, tested & commissioned fire protection system of each type as in 2(a), (b) & (c) above as per the recommendations of TAC of India or any other international reputed authority like (FOC, London or NFPA, USA et) and are in successful operation for at least two years.
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.4 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR AIR CONDITION SYSTEM
Name of the tendering company
Sl.No Description As per Tenderer
1 Name and Address of Air Conditioning system supplier
2 Number of A/C system executed by the supplier and duration of successful operation as on date of bid opening .
3 Split type air conditioning Unit
a) Make & Model
b) Nominal Capacity (TR/Kcal/Hr.)
c) Nominal Air quantity (cu.m/hr -CFM)
d) Number of units offered
e) Guaranteed power consumption for each unit
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.5 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR LT SWITCH GEAR
Name of the tendering company
Sl.No Description As per Tenderer
1 Name & Address of Manufacturer
2 Confirm whether Manufacturer’s have supplied 50 Nos drawout Air circuit breaker Panels out of which 5 Nos. are with CT and relaying scheme.
3 Confirm whether Manufacturer’s have supplied 50 Nos MCC panels similar to the offered panels.
4 Confirm whether 100 nos.(at least) circuit breakers of the make and type being offered are already been operating satisfactorily.
5 Rated short circuit current
5.1 Number of phases Symmetrical short circuit withstand current at rated voltage of switchgear cubicle
5.2 Peak short circuit withstand current
6 Degree of protection
6.1 Breaker/MCC/AC & DC
6.2 Distribution Cubicles
6.3 Busbar chamber
7 Standard height, width & depth of typical panel
7.1 Circuit Breaker Panel
7.3 AC/DC Distribution Board
8 Width of cable alley
9 Confirm whether equipment offered are from manufacturer and they are type tested as per IS/ International standard and are in successful operation for two years.
4.6 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR ISOLATORS & ISOLATORS WITHOUT EARTHING SWITCHES
Name of the tendering company
Sl.no. Description As per TENDERER As per TENDERER As per TENDERER As per TENDERER
400 KV 220 KV 132 KV 33 KV
Normal / Tendam Normal / Tendam Normal / Tendam Normal / Tendam
1) Name and manufacturer and country
2) Type Designation
3) Covering Standard
4) Class(Outdoor/Indoor)
5) Rated Voltage(KV)
6) Frequency (Hz)
7) Rated Current of Isolator(Amps) under site conditions
9) Maximum capacity for interrupting magnetising current of transformer or charging current of line when equipped with arching contacts (Amps)
10) (a) Maximum capacity for interrupting magnetising current of transformers or charging current of line when not equipped with arcing contacts(Amps)
b) No.of Operations possible without deterioration contacts
11) Rated Short time current (KA rms)
12) Rated peak Short circuit current(KA peak)
13) Rated current which can be made by earthing Switches(Amps)
14) Type of mounting
15) Phase Centres (mm)
16) Minimum Phase to Phase clearance (mm)
17) Minimum Phase to Ground clearance (mm)
18) No.of Pedestal Insulators per Phase
19) No.of breaks/Phase
20) Type of Interlock between isolating Switch & circuit breaker
21) Creepage Distance (mm) for heavily polluted atmosphere
22) Main Contacts(fixed & moving)
c) Whether contacts Silver Plated
d) Thickness of Silver coating(mm)
e) Contact area(sq.mm)
f) Contact Pressure(kg/cm²)
g) Current carrying capacity (Amps)
23) Arching Contacts
c) Whether contacts silver plated
d) Thickness of silver coating(MM)
e) Current carrying capacity (Amps)
24) Type of bearings
25) Location of Bearings
26) Type of lubricant for bearings
27) Size of Weight of Switch base per pole(mm)
28) Weight of one complete pole(Kg.)
29) Operating mechanism
A) Manual Operation Whether separate operating mechanism for operating of main blades and earthing blades.
a) Height of operatring handle above foundation(mm)
b) Force required for 3 Phase operation (Kg.)
c) Length of operation handle (m)
d) Torque on operating rod to operate three pole gang- operated earthing switch(Kgm)
e) Weight of Operating mechanism (Kg.)
B) Electrical Operation
a) Motor(AC/DC)
b) Rated Voltage of Motor (Volts)
c) Power Required
i) for Closing operation (Watts)
ii) for opening operation(Watts)
30) Running time of motor
i) for Closing operation (Sec.)
ii) for opening operation(Sec.)
31) Auxiliary Switches
I) Number of normally open and normaly cleared
ii) Rated Voltage
iii) Rated Current
iv) Test Voltage
32) Insulation Levels. Isolators and Isolator-cum-earthing switches
I) 1.2/50 microsecond dry impulse withstand voltage (Positive & negative polarity (KV peak)
a) Across the Isolating distance
b) To earth and between Poles
ii) One minute dry power frequency withstand voltage(Kv rms)
a) Across the Isolating distance
b) To earth and between Poles
iii) One minute wet power frequency withstand voltage(KV rms)
33) Minimum visible corona discharge voltage (KV rms)
34) Insulation Strength of auxiliary gear (KV rms)
35) Maximum temperature rise of main contact at rated current corresponding to an ambient temperature of air in Shade(°C)
36) Maximum temperature rise of main contact at rated short time current (°C)
37) Rated mechanical terminal load (excluding wind loads(Kg.)
38) Galvanisation
I) Governing Standard
ii) Method of Galvanisation
iii) Weight of Zinc coating Gm/cm²
39) Loading details for design of foundation
I) for isolator
ii) for isolator-cum-earthing Switch
40) Weight of 3 Phase Isolator complete with operating mechanism including support frame works. Etc. (Kg.)
41) Weight of 3 Phase Isolator-cum-earthing switch without operating mechanism(Kg.)
42) Weight of the heaviest package(Kgs.)
43) Space requirements I.e. (length, width & height)
b) Isolator-cum-earthing switch
4.7 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 50 MVA 132/33 KV POWER TRANSFORMERS
Name of the tendering company
SL.NO DESCRIPTION As per Tenderer
1 Name of the manufacturer and place of manufacture
3 Voltage ratio (kV)
4 Winding connection
6 Number of phases
7 Frequency (Hz)
8 Type of cooling
9 Rating available at different cooling (%)
10 Impedance Data
a Positive sequence impedance between,HV-LV at 75 deg. C with 100% rating at
i) Principal tap
ii) Maximum tap
iii) Minimum tap
b) Zero sequence impedance at principal tap
11 Guaranteed losses
a) Maximum no load loss on principal tap at rated voltage and frequency (KW)
b) Maximum load loss at rated current at principal tap at 75ºC (KW)
c) Maximum cooler loss (K/W)
12 Cooling Equipment Details
a) Number of radiator bank and its rating as % of transformer cooling
b) Type of mounting
13 Thermal Data
a) Temperature rise in top oil over an ambient of 50 deg. C. (deg.C)
b) Temperature rise in winding by resistance measurement method over an ambient of 50 deg. C. (deg. C)
c) Thermal time constant (Hours)
14 Withstand time for three phase short circuit at terminals (secs.)
15 Over excitation withstand time (secs.)
a) High Voltage
i) Manufacturer
iii) Total creepage distance (mm)
iv) Protected creepage distance (mm)
vi) Rated current (Amps)
i) Manufacturer
iii) Total creepage distance (mm)
iv) Protected creepage distance (mm)
vi) Rated current (Amps)
17 Proposed method of transformer transportation
18 Tap changing Equipment rating
a) Voltage class & current
b) Number of steps
d) Step voltage
f) Rated voltage of drive motor (volts)
g) No. of revolutions to complete one step
h) Time to complete one step on manual/auto operation (secs.)
i) Power required (kW)
19 Insulation Level
i) Lightning impulse withstand voltage (kVp
ii) Switching Surge withstand voltage (kVp)
iii) Power Frequency withstand voltage (kV rms)
i) Lightning impulse withstand voltage (kVp
ii) Power Frequency withstand voltage (kV rms)
i) Lightning impulse withstand voltage (kVp
ii) Switching Surge withstand voltage (kVp)
iii) Power Frequency withstand voltage (kV rms)
i) Lightning impulse withstand voltage (kVp
ii) Power Frequency withstand voltage (kV rms)
e) Neutral Bushings
i) Lightning impulse withstand voltage (kVp
ii) Power Frequency withstand voltage (kV rms)
20 Approximate dimensions
a) Tank (lxbxh) (mm)
b) Overall dimensions with coolers (lxbxh)
c) Shipping dimensions (lxbxh)
d) Height for un-tanking (mm)
e) Dimensions of largest (mm) package (lxbxh)
21 Weights of Transformer Components
b) Winding (Kg)
c) Insulation (Kg)
d) Tank and fittings (Kg)
f) Untanking weight (heaviest piece) (Kg)
g) Total weight (kg)
h) Weight of heaviest package (Kg)
i) Total shipping weight (Kg )
j) Parts detached for transport (furnish list)
22 Permissible overload (% of rating and time )
a) Minimum clearance between phases and phase to earth
ii) In air (mm)
b) Minimum clearance of HV winding to tank in oil (mm)
c) Minimum clearance of HV winding of earth in oil (mm)
d) Clearance between Core and Coil (mm)
e) Clearance between coils (mm)
f) Clearance between neutral to ground in air (mm)
a) Total Volume (Liter)
b) Volume between highest and lowest levels
25 Capacitance Values
a) HV to earth (pF)
b) LV to earth (pF)
26 (a) Type of oil preservation
b) Material of air cell
c) Continuous temp. withstand capability of the air cell
27 (a) No. of pressure relief device provided
b) Operating pressure of pressure relief device
a) Quality of Oil
i) Moisture Content (ppm)
ii) Max. tan-delta value (at 90 deg. C.)
iii) Resistivity (ohm-cm)
iv) Breakdown Strength (kV)
v) Interfacial tension at 20°C (min.)
b) Standards applicable
a) Type of construction (core/shell)
b) Net core area (mm2)
c) Core material and grade used
d) Type of joint between core and yoke
e) Thickness of stamping (mm)
f) Percentage silicon content (%)
g) Maximum flux density in core at rated frequency and at
i) 90% voltage (wb/sq.m)
ii) 100% voltage (wb/sq.m)
iii) 110% voltage (wb/sq.m)
a) Type of winding
b) Current density at rated load
i) HV (A/sq.mm)
ii) LV (A/sq. mm)
c) Conductor area
i) HV (A/sq.mm)
ii) LV (A/sq. mm)
d) Maximum current density under short circuit
i) HV (A/sq. mm)
ii) LV (A/sq. mm)
e) Magnetizing inrush current (Amps)
f) No load current (Amps) at rated frequency and at
i) 90% voltage (wb/sq.m)
ii) 100% voltage (wb/sq.m)
iii) 110% voltage (wb/sq.m)
g) Magnetising current at rated frequency and at rated voltage
h) Leakage reactance
i) High Voltage (Ohms)
ii) Low Voltage (Ohms)
i) Leakage resistance
i) High Voltage (Ohms)
ii) Low Voltage (Ohms)
a) Tank cover –Conventional /Bell Type
c) Approximate thickness of
ii) Bottom (mm)
iii) Cover (mm)
32 Vaccum withstand capability of
a) Main tank (torr)
b) Radiators and accessories (torr)
33 Pressure withstanding capability of
a) Main tank (torr)
b) Radiators and accessories (torr)
b) Temperature withstand capability (°C)
35 Minimum draw bar pull required to move the transformer on level track (kg)
36 Size of filter hose(mm)
37 Temperature Indicators
i) Manufacturer
i) Manufacturer
i) Manufacturer
iv) Auxiliary supply used
DATA SHEETS – BUSHING
CURRENT TRANSFORMER
1 Bushing Current Transformer on Auto Transformer
i) Type or voltage class
iii) Accuracy class
iv) Burden (VA)
v) Accuracy limit factor
vi) Knee point voltage (Volts) (minimum)
vii) Maximum resistance of secondary winding
viii) Maximum exciting (mA) current
i) Type or voltage class
iii) Accuracy class
iv) Burden (VA)
v) Accuracy limit factor
vi) Knee point voltage (Volts) (minimum)
vii Maximum resistance of secondary winding (Ohms)
viii) Maximum exciting (mA) current
c) Neutral side
i) Type or voltage class
iii) Accuracy class
iv) Burden (VA)
v) Accuracy limit factor
vi) Knee point voltage (Volts) (minimum)
vii) Maximum resistance of secondary winding
viii) Maximum exciting (mA) current
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.8 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR LT TRANSFORMER
Name of the tendering company
Sl.No Description As per Tenderer
1 Name & Address of Manufacturer
2 Voltage Ratio
4 Standards applicable
5 Rated frequency
6 Number of phases
8 Type of cooling
9 Tap changing equipment
ii) No. of steps & tap range
10 Positive sequence impedance at 75 C with 100% rating at
a) Principal tap
11 Temperature rise over an ambient of 50 deg.C
a) Top oil deg.C
b) Windings (by resistance measurement method ) deg.C
12 Guaranteed losses
a) Maximum no load loss on principal tap at rated voltage and frequency.(kW)
b) Maximum load loss at rated current at principal tap at 75 deg C(kW)
13 Withstand time for three phase short circuit at terminals (secs.)
14 Insulation level
a) Full wave lightning impulse withstanding
i) HV Winding (kVp)
ii) LV Winding (kVp)
15 Confirm whether similar equipment are type tested and are in successful operation for atleast two years.
16 Confirm whether similar equipment is tested for dynamic short circuit withstand capability ( furnish details)
4.9 SCHEDULED OF GUARANTEED TECHNICAL PARTICULARS OF 33 KV VCB
Name of the tendering company
Sl. No. Description As per Tenderer
1 Name of the Manufacturer
2 Manufacture’s type and designation
3 Governing standards
4 Rated voltage (kV)
5 Maximum continuous service rated voltage
6 Frequency (Mz)
7 Class (Outdoor)
8 Normal current rating (amps)
(i) Under standard condition
(ii) Under site condition
(iii) Derating factor, if any, for sites conditions
9 Short time current rating (KA)
i) For 1 second
(ii) For 3 second
10 Maximum temperature rise over ambient 50 C due to rated current in main contacts , measured after breaking test.
11 Rated short circuit breaking current
a) Rated short circuit current (AC component) KA (rms) at KV
b) Percentage DC component
c) Asymmetrical breaking current (including DC component) at KV
12 Making capacity (KA peak) part
13 Total break time (milli seconds)
(a) For interruption of 10% of the rated capacity
(b) For interruption of 30% of the rated capacity
(c) For interruption of 60% of rated capacity
(d) For interruption of the full rated capacity.
16 Minimum reclosing time at rated interrupting capacity from the instant of the trip coil energisation ( milli seconds )
17 Minimum Dead time
(a) 3 phase reclosing (milli second)
(b) 1 phase reclosing (do)
(c) Limit of adjustment of dead time for 1 phase reclosing
(d) Limit of adjustment of dead time for 1 phase reclosing.
18 Date on restriking voltage for 100, 50% or 30% rated capacity.
a) Amplitude factor
b) Phase Factor
c) Natural Frequency
d) Rate of Rise of Restriking Voltage (V) micro sec.
19 Maximum interrupting capacity under phase opposition condition (MVA) – indicate value as per test report.
20 Maximum line charging current breaking capacity without over voltage exceeding 2.5 time the rated phase to neutral voltage (amps – indicate value as per test report)
21 Maximum line charging current breaking capacity and corresponding over voltage recorded in test
(a) On supply side }
(b) On line side }
22 Maximum cable charging current breaking capacity and corresponding over voltage recorded in test
(a) On supply side }
(b) On line side }
23 Maximum shunt capacitor / Reactor Bank switching capacity (Single bank MVA)
24 Maximum breaking capacity on kilometric faults (MVA)
25 Maximum over voltage on switching transformer on no load and the charging current
26 Dry 1 minute power frequency test withstand voltage for complete circuit breaker.
(a) Between line terminal & ground parts (KV rms)
(b) Between terminal with breaker contacts open KV (peak
27 Wet 1 minute power frequency test withstand voltage for complete circuit breaker
28 1.2 / 50 microsecond wave impulse withstand test voltage for complete circuit breaker –
(a) Between the terminal & ground (KV peak)
(b) Between terminal with circuit breaker contacts open (kv peak)
SUPPORTING INSULATORS
29 Make and type
31 Transport dimension
32 Insulation class
33 Visible corona discharge voltage
34 Dry – 1 minute power frequency flashover voltage
35 Wet – 1 minute power frequency flashover voltage
36 1.2/5 microsecond impulse flashover voltage
37 Creepage distance to ground (mm) for heavily polluted atmosphere
38 Minimum clearance in air –
a) Between phase (mm)
b) Live parts and earth (mm)
c) Live parts to ground level (mm)
CONSTRUCTIONAL FEATURES
39 No. of poles per circuit breaker
40 No. of breaks per phase
41 Total length of breaks per hase (mm)
42 Type of main contacts
43 Materials of main contacts
44 Whether main contacts silver plated (Yes/no)
45 Thickness of silver coating on – main contacts (mm)
46 Contact pressure on main contacts (Kg/m2)
47 Type of arcing contacts
48 Contact pressure on arcing contacts (kg/m2)
49 Type of auxiliary switches
50 Material of switch contacts
51 Whether contacts silver plated (Yes/No)
52 No. of auxiliary switch contacts operating with all three poles or single pole of breaker
a) Which are closed when breaker is closed.
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts.
53 No. of auxiliary switch contacts operating with individual pole of a breaker
a) Which are closed when breaker is closed.
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts.
54 No. of spare auxiliary switch contacts operating with all three poles or single pole of breaker
a) Which are closed when breaker is closed.
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts.
55 No. of spare auxiliary switch contacts operative with individual pole of breaker
a) Which are closed when breaker is closed.
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts.
56 No. of operating possible without maintenance
(a) At full rated interrupting capacity
(b) At 50% of rated interrupting capacity
(c) At 100% of rated current
(d) At 50% of rated current.
57 Mounting flange details
58 Type of operating mechanism
59 Tripping and closing circuit voltage (V)
60 Power required for tripping coil
61 Power required for closing coil
62 Details of various selector switches
63 Details of push button switches
64 Details of various selector switches
65 Details of push button switches
66 Contigencies for which alarm provided
67 Desin data for supporting structure.
68 Weight of supporting structure (Steel) per breaker
69 Time required by motor to charge the closing spring
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR VOLTAGE TRANSFORMER
Name of the tendering company
Sl. No. Description As per Tenderer As per Tenderer As per Tenderer As per Tenderer
400KV 220 KV 132 KV 33 KV
2) Rated primary Voltage(KV)
3) Number of Secondary windings
4) Rated Secondary Voltage(KV)
5) Rated Burden(VA)
6) Accuracy Class
7) Maximum ratio error with rated burden and 5% normal primary voltage
8) Maximum phase angle error with rated burden and 5% normal primary volatage.
9) Variation in ratio and Phase angle error for variation in
a) Voltage by 1%
b) Frequency by 1 Hz
10) Temperature rise at 1.1 times rated voltage with rated burden
11) Rated Voltage factor and time.
12) 1.2/50 micro second impulse wave withstand test voltage (KV peak)
13) One minute power frequency withstand test (dry) Voltage KV rms.
14) One minute power frequency withstand test (wet) Voltage KV rms.
15) One Minute Power Frequency withstand voltage on secondary (KV rms)
16) Minimum creepage distance (mm)
a) Moderately polluted atmosphere
b) Heavily Polluted atmosphere
17) Whether corona shield provided or not ?
18) Weight of oil (Kg.)
19) Total Weight(Kg.)
20) Overall dimensions
21) Mounting Details
4.11 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR BATTERY & BATTERY CHARGERS
The tender shall furnish the technical particulars give for the battery set
Name of the tendering company
Sl.No. Description As per Tenderer As per Tenderer
A. BATTERY 220V 48V
2) Number of Battery Sets furnished
3) (i) Type of Battery
ii) manufacturer's catalogue No.
4) Amper hour rating of the battery at 10 hours rate
5) Voltage rating
6) Ten (10) hours discharge rate to 1.85 volts per cell :
7) One (1) hour discharge rate top 1.85 volts per cell
8) One(1) minute discharge rate to 1.85 volts per cell
9) Short Circuit Current for dead short across the Battery terminals when
a) Floated at 2.23 Volts per cell
b) Quick charged at 2.3 Volts per cell
10) (a) Is the battery furnished to sufficient capacity to meet the duty indicated
11) Battery conforms to ISS/BSS
12) Battery layout arrangement, drawing enclosed
a) Number of Cells per Battery
b) Type of the Cell
c) Cell designation as per ISS
d) Material & Thickness of the Container
e) Overall dimensions for each Cell.
f) Weight of complete cell with acid
g) Weight of acid required per cell
h) Normal cell voltage
14) Inter Cell connectors
a) Intercell connector furnished
b) Type of Intercell, Connected bolted or not ?
c) Material of Inter cell connector
a) Number of positive plates per cell.
b) No. of negative plates per cell
c) Type of positive plate
d) Type of Negative Plate
17) Battery Electrolytes
a) Amount of Electrolyte for first filling………..
b) First filling with 10% extra furnished
c) Electrolyte conforms to :-
d) Sp gravity of electrolyte at 27oC
e) Sp gravity of electrolyte at the end of discharge at hors rate :-
f) Sp gravity at the end of full charge:-
a) Number of racks per Battery
b) Number of cell per rack
c) Type of Rack(Row/Tiers)
d) Material of racks
d) Rack provided with
I) Numbering tags for cell
ii) Wood clamps for cables
19) Inter-row, Inter-tier connector and take off to be furnished
20) Recommended rate for Charging the Battery in 10(ten) Hours
21) Recommended Float Charge Rate
22) Cell Voltage charging At 0.5/1.0 and 1.5 times normal rate enclosed.
23) AH Efficiency (%)
24) WH Efficiency (%)
25) Maximum charging current per cell
26) Nominal Charging Current
27) Type pf supporting Insulator
28) Assured life span of Battery
29) Accessories furnished with battery set
B. BATTERY CHARGER
1) Manufacture's type, designation
2) Number of Charger furnished
a) Voltage (Volts)
b) Current (Amps)
c) No. of phases
d) Frequency, Cycles / Sec
e) Power factor
4) Rated D.C. Output for
a) Boost Charger (KW)
b) Float Charger (KW)
5) Rated D.C. output voltage for
a) Boost Charger (Volts)
b) Float Charger (Volts)
6) Rated D.C. output current for
a) Boost Charger (Amps)
b) Float Charger (Amps)
7) Rated D.C. voltage control for
a) Boost Charger (Volts)
b) Float Charger (Volts)
8) D.C. output voltage regulation from no load to full load volts
9) Maximum ripple content (%)
10) Method of control
a) Float Charger
b) Boost Charger
c) Load Limiting feature provided in the both Charger
11) Transformer
13) A.C.Switch fuse Unit
b) Continuos Rating
c) Interruption Rating
14) A.C.Contactor
b) Continuous Rating
c) Interrupting rating
16) D.C.Contactor(marked)
b) One(1) minute rating
c) One(1) hour rating
17) Blocking Diode
b) One Minute Rating
18) D.C.Ammeter/Voltmeter
19) a) Scales of meter (Voltmeter)
a) Float Charger
b) Boost Charger
20) Battery Charger panel
b) Thickness of steel metal
c) Overall dimenmsions (WXLXH)
d) Approximate Weight
20) Equipment conforms to………….
21) Any other particular which may need tobe mentioned, please mention
4.12 SCHEDULE FOR GUARANTEED TECHNICAL PARTICULARS FOR CONTROL CABLES
Name of the tendering company
Sl.No. Description As per Tenderer
3 Standard Applicable
a) Voltage Grade
b) Suitable for Service Voltage and System of Earthing.
4 Maximum Conductor temperature
5 Conductor(Copper)
b) Form of Conductor
c) Number of Cores
d) Number of diameter (Stranded/Solid) of wire per core.
a) Material Insulation
c) Average Dielectric Strength
d) Dielectric Constant
7 Suitability with regard to temperature moisture ozone, acid and alkaline surroundings
8 Thickness of sheath over conductor, if any………..mm.
9 Material of sheath over cable
10 Thickness of sheath over cable………mm.
11 Electrical Performance
a) Conductor resistance at 20°C per KM
b) Maximum conductor temperature
c) Under full load
d) Under transient condition
e) Maximum operation Voltage……..Volts
f) Insulation resistance of 1 Km of cable at 20°C Mega Ohms
g) Power afactor or loss angle.
h) Tan delta of dielectric materials
I) Dielectric loss per km at rated voltage.
j) Power frequency with stand voltage KV rms.
k) Current loading data for the cable for specified operating temperature.
12) Type of Cable : Single core or stranded
a) In air in cable trays
b) In cable channels
c) In cleode ducts
d) In cable conduits and Pipes
13) Derating factors for
a) Ambient temperature
b) Grouping of 3 or 4 cables in air.in trays, channels for different spacing between cable and in closed ducts in touching position.
14) Allowable short circuit current for one Sec.
15) D.C.Withstand voltage
16) A.C. 50 Cycles/ second impedance.
17) A.C. 50 Cycles/ second impedance.
MECHANICAL DATA
18) Weight of Cable
a) Wt. Of conductor per Km.
b) Wt. Of PVC compound per Km.
c) Complete wt. Per Km.
d) Wt. Of Armour
19) Overall diameter
20) Maximum length per drum
21) Drum dimensions
22) Gross weight of cable drum
23) Maximum Pulling tension
24) Minimum bending radius
25) I.S.I. Certification No.
4.13 GUARANTEED TECHNICAL PARTICULARS FOR PG CLAMPS/BUS SUPPORT CONNECTOR/T-CONNECTOR, PALM CONNECTOR SUSPENSION FITTING AND TENSION FITTING (TO BE FILLED BY TENDERER)
Name of the tendering company
Sl.No. Description As per Tenderer As per Tenderer As per Tenderer
For Moose conductor For Zebra conductor For Panther conductor
1 Maker's Name and Country :
4 Slipping Strength :
5 Breaking Strength :
6 Electrical conductivity
a) Resulting heating cycle test carried out
b) Value of Electrical resistance.
7 Corona formation voltage & Radio Interference level.
8 Standard specification to which conforms :
9 Make of Bolts & Nuts :
10 Packing Details :
11 Drawings indicating all dimensions and material used to be submitted
12 Details of type test report submitted for each type of clamps and connector. :
13 Weight of each complete set with bolts & nuts PG Clamp/T Connector/Bus support/Any other type :
a) Non ferrous parts
b) Ferrous parts
14 Number and weight of only bolts & nuts used in each set.
15 Minimum Thickness ocurring at any part of the clamps connector.
Furnish separate schedule for each type
4.14 SCHEDULE OF THE GUARANTEED TECHNICAL PARTICULARS FOR SF6 CIRCUIT BREAKERS
Name of the tendering company
Sl. No. Description As per Tenderer 400 KV As per Tenderer 220 KV As per Tenderer 132 KV
1 Name of the manufacturer
2 Manufacturer’s type and designation
3 Governing Standard
4 Rated voltage (kV)
5 Maximum continuous rated service voltage
6 Frequency (Hz)
8 Normal Current rating (amps)
a) Under standard conditions
b) Under site conditions
c) Derating factor, if any, for site conditions
9 Short time current rating (kA)
10 a) For 1 second
b) For 3 seconds
11 Maximum temperature rise over ambient 50°C due to rated current in main contacts, measured after breaking test
12 Rated short circuit breaking current
a) Rated short circuit current (A.C. component)-kA (Rms)- at kV
b) Percentage D.C. component
c) Assymeterical breaking current (including D.C. component) - at kV
13 Making capacity ( kA peak)
14 Total break time (milli second)
a) For interruption of 10% of the rated capacity
b) For interruption of 30% of the rated capacity
c) For interruption of 60% of the rated capacity
d) For interruption of the full rated capacity
15 Arcing time (milli seconds)
16 Making time (milli seconds)
17 Minimum reclosing time at rated interrupting capacity from the instant of trip coil energisation (milli seconds)
18 Minimum dead time
a) 3 phase reclosing (milli seconds)
b) 1 phase reclosing ( - do - )
c) Limit of adustment of dead time for 3 phase reclosing
d) Limit of adjustment of dead time for 1 phase reclosing
19 Data on restriking voltage for 100%, 50%, 30% rated capacity
a) Amplitude factor
b) Phase factor
c) Natural frequency
d) RRV Micro second
20 Maximum interrupting capacity under phase opposition condition ( MVA - indicate value as per test report)
21 Maximum line charging current breaking capacity and corresponding over voltage recorded (Amps - indicate value as per test report)
a) on line side
b) on supply side
22 Maximum line charging current breaking capacity without over-voltage exeeding 2.5 times the rated phase to neutral voltage (Amps - indicate value as per test report)
23 Maximum cable charging current breaking capacity and corresponding over-voltage recorded in test
a) On supply side
b) On line side
24 Maximum shunt capacitor/Reactor bank switching capacity ( Single bank MVA)
25 Maximum breaking capacity on Kilometric faults (MVA)
26 Maximum over-voltage on switching transformer on no load and the charging current
27 Dry 1 minute power frequency test withstand voltage, for complete Circuit Breaker
a) Between line and grounded parts ( kV rms)
b) Between terminals with breaker contact open ( kV rms)
28 Wet 1 minute power frequency test withstand voltage for complete Circuit Breaker
a) Between line terminals and grounded parts ( kV rms)
b) Between terminals with breaker contact open
29 1.2/50 microseconds wave impulse withstand voltage for complete Circuit Breaker
a) Between terminals with circuit breaker contacts open( kV peak)
b) Between the terminals and the ground ( kV peak)
SUPPORT INSULATORS
30 Make and type
32 Transport Dimension
33 Insulation class
34 Visible Corona discharge voltage
35 Dry 1 minute power frequency flashover voltage
36 Wet 1 minute power frequency flashover voltage
37 1.2/50 microsecond impulse flashover voltage
38 Creepage distance to ground for heavily polluted atmosphere
39 Minimum clearance in air
a) Between phases
b) Live parts and earth
c) Live parts to ground (mm)
CONSTRUCTIONAL FEATURES
40 No. of poles per Circuit Breaker
41 No. of breaks per pole
42 Total length of break per phase (mm)
43 Type of main contacts
44 Material of main contacts
45 Whether main contacts are silver plated ( Yes/No)
46 Thickness of silver coatings on main contacts
47 Contact pressure on main contacts (kg/sq. meter)
48 Type of arcing contacts
49 Contact pressure on arcing contacts (kg/sq. meter)
50 Type of auxiliary switches
51 Material of switch contacts
52 Whether contacts are silver plated (Yes/No)
53 No. of auxiliary switch contacts operating with all three poles or single pole of a breaker
a) Which are closed when breaker is closed
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts
54 No. of auxiliary switch contacts operating with individual pole of a breaker
a) Which are closed when breaker is closed
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts
55 No. of spare auxiliary switch contacts operating with all 3 poles or single pole of breaker
a) Which are closed when breaker is closed
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts
56 No. of spare auxiliary switch contacts operating with individual pole of a breaker
a) Which are closed when breaker is closed
b) Which are open when breaker is closed
c) Those adjustable with respect to the position of main contacts
57 No. of operation possible without maintenance
a) at full rated interrupting capacity
b) at 50% of rated interrupting capacity
c) at 100% of rated current
d) at 50% of rated current
58 Mounting flange details
59 Type of Operating mechanism
60 Tripping and Closing Circuit Voltage
61 Power required for trip coil
62 Power required for Closing coil
63 Details of various selector switches
64 Details of push button switches
65 Contingencies for which alarm provided
66 Weight data for supporting structure
67 Weight of supporting steel structure per breaker
68 Time required for motor to charge the closing spring (minute)
CONTROL CABINETS :
69 Details of running hour meters
70 Details of start counter
71 Details of various selector switches
72 Dimension of the control cabinets
73 Weight of control cabinet
WEIGHT & SPACE REQUIREMENT
74 Weight of 3 phase breaker complete with operating mechanism insulating supports frame work, etc.
75 Impact loading for foundation design to include dead load plus impact value on opening at max.
interrupting ratings in terms of equivalent static load.
76 Weight of the heaviest package
77 Circuit Breaker
78 Air Compressor of SF6
79 Duration of service of the breaker after first filling of SF-6 without any replenishment
80 Type of flow of SF-6 (Axial/Radial)
81 Type of nozzles (single/double)
82 Material of Nozzles
83 Dead or live tank
84 Normal operating pressure (kg/sq.cm)
85 Normal gas density (gm/cc)
86 Minimum gas density ( gm/cc)
87 Requirement of gas per breaker(kg)
88 Lockout pressure ( Kg/sq.cm)
89 Details of gas fillers
90 Life of gas fillers
91 Guaranteed maxm. leakage per hour under climatic conditions specified in the tender during operation.
92 Working on single or dual pressure
4.15 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 220 KV ,132kV AND 33kV CLASS GAPLESS LIGHTING ARRESTOR
Name of the tendering company
Sl.No. Description As per Tenderer As per Tenderer As per Tenderer As per Tenderer
400 KV 220 KV 132KV 33KV
5 No.of units per arrester
7 Nominal System Voltage
9 Highest System Voltage
10 Maxm. Continuous Operating Voltage(MCOV)
11 Nominal Discharge current(8x20)
12 Maximum residual voltage(8x20) (Lightning Impulse)
13 Switching current Impulse residual Voltage (45x90)
I) at 1000 AMP Maximum Minimum
ii) at 1000 AMP Maximum Minimum
14 High current Impulse withstand
15 Steep Front Current Impulse Max. Residual Voltage (10 KA of 10 MS)
16 Lightning Impulse residual Voltage (KVP)(8x20)
17 Long duration Discharge Class-III
18 Energy discharge Capability (KJ/KV)
19 Pressure Relief Class
20 Max. Radio Interference Voltage at COV(MV)
21 Reference Voltage at AMB, TEMP
22 Reference Current at AMB, TEMP
23 Resistive/Capacitive Components of Continuous Current at Ambient temperature.
24 Power Freq. O/v Capability (RMS) for
25 Capability of wiothstand over voltage immediately after discharge Energy Equivalent to maxm. capability of the Arrester
26 Arrester Housing Insulation withstand valuses
I) Lightning Impulse
ii) Switching Impulse
iii) Power Frequency Dry/Wet.
27 Creepage Distance (mm)
28 Cantilever Strength
29 Voltage/Time Curve
30 Other dimensional details
31 Diameter of Zinc Oxide blocks(in mm)
32 Height of discs (in mm)
33 Energy dissipation capability of the disc in assembled condition inside LA
34 Calculation showing KJ/per KV rating of the disc.
35 Details of thermal circuit employed for dissipation of heat.
36 Copy of latest type test Report furnished or not
37 Height of complete unit from base to lineside(mm)
38 In case ring type blocks are used indicate dimension of O.D & I.D.
Furnish separate schedule for each type
4.16 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR CURRENT TRANSFORMER
Name of the tendering company
Sl. No. Description As per Tenderer As per Tenderer As per Tenderer As per Tenderer
400 KV 220 KV 132 KV 33 KV
1 Manufacturer's name & type designation
3 Rated Voltage
4 Rated Primary Current
5 Rated Secondary current
6 No. of Cores Rated Output(VA) Rated Output(VA) Class of Accuracy Accuracy Limit factor
7 Secondary Voltage Exciting Current in mA
8 Short time thermal rating of Primary(Amps)
b) Three Second
9 Rated dynamic current of Primary (Peak value)
10 Rated continuous thermal current
11 Temperature rise at rated continuous thermal current over ambient temperature of 50°C.
b) Oil at the top
c) Exposed current carrying parts.
12 One minute power frequency dry withstand test voltage(KV rms)
13 Magnetisation curve of CT core
14 Characteristics:-
a) Ratio and phase angle curves
b) Magnetisation curves
c) Ratio correction factor curves
d) Limits of composite error at rated primary saturation current (for protective CT core)
15 Variation in ratio and phase angle error due to variation
a) Voltage by 1%
b) Frequency by 1 %
16 Current density in primary windings
17 Weight of coil
18 Total weight
19 Mounting details
20 Overall dimensions
21 Overall creepage distance in mm
Furnish separate schedule for each type
4.17 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF DISC INSULATORS
Name of the tendering company
Sl.No. Description As per Tenderer As per Tenderer As per Tenderer
1) Disc insulators 70KN 90KN 120 KN
I) Maker's name & Address
ii) Type of Insulator
iii) Size & Designation of Ball & Socket
iv) Disc Diameter(mm)
v) Unit Spacing(in mm)
vi) Creepage distance (in mm)
ix) Electro-Mechanical Strength(in Kg.)
x) Minimum failing load(in kg.)
xi) Impulse withstand test voltage
xii) Impulse withstand test voltage (1.2x50 Micro-second-Ve wave, KV(Peak)
xiii) Power frequency dry withstand test voltage, KV rms
xiv) Power frequency wet withstand test voltage, KV rms
xv) Power Frequency dry flashover voltage, KV rms
xvi) Power frequency wet flashover voltage,KV rms
xvii) Impulse flash over voltage 1.2x50 micro Sec. + Ve wave , KV (Peak)
xviii) Impulse flash over voltage 1.2x50 micro Sec. - Ve wave , KV (Peak)
xix) Power frequency puncture voltage, KV rms
xx) Net weight of single Insulator unit(in kg.)
xxi) I.S.S. to which insulator will conform
xxii) Type of locking Device and its dimension
xxiii) Reference of drawings enclosed
xxiv) Reference of Type test and other Test Reports enclosed.
xxv) Whether inter changeability guaranteed
xxvi) Details of Galvanisation of ferrous parts
xxvii) Other details, if any
4.18 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR HARDWARE FITTINGS(MOOSE, PANTHER AND E/W)
Name of the tendering company
Sl.No. Description As per Tenderer As per Tenderer As per Tenderer
A) Accessories/Fittings for ACSR Panther/ Moose Conductor. For Moose For Zebra For Panther
1 M.S.COMP.JOINT
I) Manufacturer's name/Address
a) Outer sleeve
b) Inner Sleeve
iv) Outside dimension of sleeve:
a) Before Compression-
b) After Compression
v) Length of Sleeve before compression
After compression:
vi) Weight of Sleeve:
vii) Slipping strength expressed as percent age of U.T.S. of ACSR Conductor
viii) Breaking strength expressed as percentage of UTS of ACSR Conductor
ix) Conductivity expressed as % of conductivity of ACSR Conductor
x) Resistance expressed as percentage of measured resistance of equivalent length of conductor
xi) Reference drawing
xii) I.S.S.to which conforms
xiii) Galvanisation
xiv) Packing details
xv) Any other particulars if any
2 REPAIR SLEEVE:
I) Manufacturer's name/Address
iv) Outside dia of sleeve :
a) Before compression
b) After compression
v) Length of Sleeve;
a) Before compression
b) After compression
vi) Weight of sleeve
vii) Breaking strength expressed as percentage of UTS of ACSR Conductor
viii) Conductivity expressed as % of conductivity of ACSR Conductor
ix) Resistance expressed as percentage of measured resistance of equivalent length of conductor
x) I.S.S.to which conforms
xi) Reference drawing
xii) Packing details
xiii) Any other particulars if any
3 HARDWARE FITTINGS
a) Disc Insulators for which suspension/Tension fittings should match
I) Type of insulator
ii) Size & designation of ball & Socket
iii) Porcelain disc dia
iv) Unit spacing
v) Electro-mechanical Strength
vi) Standard to which disc will conform
b) INSULATOR STRING ARRANGEMENTS
I) No.of disc per string
ii) Length of string assembly(in mm)
iii) Electro-mechanical strenght(in Kg)
iv) Creepage distance (mm)
v) Reference drgs.
vi) Weight of String assembly
I) Manufacturer & Name & Address
iii) Manufacturing Process
v) Breaking strength (minimum)
vi) Slipping strength
vii) Angle of inclination of jumper terminal
viii) ISS to which conforms
d) HARDWARE (Material)
I) Socket Clevis
ii) Ball Clevis
iii) Anchor Shackles
vi) Socket Link
vii) Yoke Plate
f) Nuts & Bolts
g) Reference drawing
I) Any other particulars if any
4 PERFORMED ARMOUR RODS
I) Maker's name & Address
iii) Total weight of a set of armour rods(Kg)
iv) No. of wire per Set
v) Diameter of wire
vi) Length of wire
vii) Percentage tolerance on length of dia of wire
viii) Overall dia of conductor after use of the armour rods(mm)
ix) Centre making provided (Y/N)
x) Pitch of Helix
xi) Direction of lay
xii) Corona & RI performance values
xiii) Efficiency of damping
xiv) Packing details
xv) End condition
xvi) Any other particulars if any
xvii) Reference drawing
5 VIBRATION DAMPERS
I) Maker's name/Address
iii) Total wt. Of each damper(Kg.)
iv) Diameter of balancing weight(mm)
v) Length of balancing weights (mm)
vi) Weight of each balancing weight(Kg)
vii) Tolerance in Balance weight %
viii) Material, quantity length and size of messenger cable
ix) Slipping strength of messenger cable(Kg)
x) Diagram showing power dissipated by the damper for various vibration frequency & amplitude
xi) Damping effeciency of damper
xii) Natural frequency of the damper
xiii) The number of dampers required per span for various span length and their spacing
xiv) Position of fixing damper on the conductor from the clamp mouth
a) At tension Points :
I) First damper(mm)
ii) Second damper(mm)
iii) Third damper(mm)
b) At suspension Points (after fixing armour rod)
I) First damper(mm)
ii) Second damper(mm)
iii) Third damper(mm)
xv) Corona & RI performance value
xvi) Packing details
xvii) Reference Drg.
B) ACCESSORIES/FITTINGS FOR 7/9 SWG EARTHWIRE
1) COMPRESSION JOINTS:
I) Manufacturer's name & Address
ii) Reference Drawing
vi) Minimum failing load
vii) Galvanisation
a) Ferrous part
b) Quality of Zinc used
c) No.of dips which the materials can withstand
viii) Standard to which conforms
ix) Packing details
x) Any other particulars
2) VIBRATION DAMPER
I) Manufacturer's name & Address
ii) Reference Drawings
iv) Total wt. Of each damper
v) Dia of balancing wt. (mm)
vi) Length of balance wt.(mm)
vii) Weight of each balance wt.
viii) Tolerance in balance wt.
ix) Material quality, length size of messenger cable
x) Slipping strength of messenger cable(Kg)
xi) Diagram showing power dissipated by the damperfor various vibration frequency and amploitude
xii) Damping effeciency by damper
xiii) No.of damper required for span for various span length and their spacing
xiv) Position of fixing damper on the wire from the damp clamp mouth
xvi) Any other particulars
3 SUSPENSION & TENSION CLAMPS WITH FLEXIBLE COPPER BOND:
I) Manufacturer's Name/Address
ii) Reference Drawing
vi) Slip Strength
vii) Minimum failing load
viii) Galvanisation:
a) Ferrous part
b) Spring Washer
c) Quality of Zinc
d) No.of dip which the clamp can withstand
ix) Standard to which conforming
x) composition of material
xi) Packing details
xii) Any other Particulars
4 REPAIR SLEEVE:
I) Manufacturer's name & Address
iv) Outside dia of sleeves
a) Before Compression
b) Aftere compression
v) Length of Sleeve
a) Before Compression
b) Aftere compression
vi)c Weight of Sleeve
vii) Conductivity
viii) Breaking strength
x) ISS to which conforms
xi) Reference Drawing
xii) Packing Details
xiii) Any other particulars
4.19 SCHEDULE OFGUARANTEED TECHNICAL PARTICULARS OF POST INSULATORS
Name of the tendering company
Sl. No. Description As per Tenderer
1) Maker's name & Address
2) Type of insulator
a) Height in mm
b) Maximum diameter in mm
c) Minimum diameter in mm
4) Creepage distance in mm(not less than)
5) Cantilever in Kg.
6) Tensile strength
7) Torsional Strength in Kg.
8) Visible discharge test voltage (Power frequency )KV rms
9) 1 min. P.F.witstand Test Voltage in KV (rms)
10) Impulse Voltage withstand test in KV (Peak) positive & negative
11) Power frequency Flashover Voltage in KV(rms)
12) Impulse flashover voltage in KV (Peak) positive & negative
13) Net weight per unit
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF EARTH WIRE
Name of the tendering company
Sl. No. STRANDED EARTHWIRE As per Tenderer(7/9 SWG) As per Tenderer(7/10SWG)
ii) ISS to which Earth wire will conform :
iii) Maker's name :
iv) Overall diameter of Earthwire(mm) :
v) Total weight (Kg/mm²) :
vi) Cross section area(mm²)
vii) Minimum ultimate tensile strength (kg/mm²) :
viii) Minimum breaking Load(Kg)
ix) Co-efficient of linear expansion per °C(calculated) :
x) Calculated modules of Elasticity (kg/cm²) :
xi) D.C.resistance at 20°C (Ohm/Km)
xii) Length of Lay of stranded earth wire(mm) :
xiii) Stranded length in which earth wire will be supplied :
B) INDIVIDUAL STRANDS/WIRE:
I) Number of wire :
ii) Diameter of each wire(mm) :
iii) Tolerance on diameter(mm) :
iv) Standard sectional area(mm²) :
v) Minimum elongation in 100mm length (mm)
vi) Normal length without any joint or weld(Mtr.)
vii) Ultimate tensile strength (Kg/mm²)
viii) Minimum breaking load (Kg)
4.21 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF CONTROL AND RELAY PANELS ( FOR PANEL WITH NUMERICAL TYPE OF RELAYS)
Name of the tendering company
220 KV Line / transformer 132 KV Line / transformer 33 KV Line / transformer
SL.NO DESCRIPTION As per Tenderer As per Tenderer As per Tenderer
I INSTRUMENTS & METERS Ammeter, Voltmeter, Wattmeter, KVAR meter and KWH meter Ammeter, Voltmeter, Wattmeter, KVAR meter and KWH meter Ammeter, Voltmeter, Wattmeter, KVAR meter and KWH meter
a) Maker's name
b) Type of instrument
c) Size of cases
d) Whether magnetically shielded or not
e) Type of case
f) Limits of error in effective range
g) Maxm. Scale length
h) Whether tropicalised
i) Type of selector switch
j) Short time overload capacity
a) Current coil(VA)
b) Potential coil(VA)
l) Power consumption
a) Current coil(watts)
b) Potential coil(watts)
m) Temp. at which instruments are calibrated
n) Grade of accuracy
o) Descriptive leaflet submitted
II RECORDERS Voltmeter Wattmeter Frequencymeter
a) Maker’s name
b) Type of recorder
c) Size and shape
d) Type of case
f) Visible range and length of recording
g) Flush or semi-flush
h) Overload capacity
i) Ink or Inkjet type
a) Current coil
b) Potential coil
l) Type of chart driving mechanism
b) Syn motor driven
m) No of hours for which spring reserve is provided
n) Description literature
III SWITCHES (Indicate separately for breaker / isolator / other control and selection switches)
a) Maker’s name
b) Type of switch
c) Size and sharp
e) Descriptive literature
IV) PROTECTIVE RELAYS
A NON-DIRECTIONAL OVER CURRENT RELAYS
iii) whether draw out type or not
iv) Current coil rating
vi) VA burden during normal & operating condition
vii) Time for operation on maximum time dial setting at:
i) 5 times tap setting current
ii) 10 times tap setting current
viii) Type of characteristics
ix) Trip contact rating(amps)
x) Whether seal in contacts provided or not( yes/no)
B NON DIRECTIONAL EARTH FAULT RELAY
iii) whether draw out type or not
iv) Current coil rating
vi) VA burden during normal & operating condition
vii) Time for operation on maximum time dial setting at:
i) 5 times tap setting current
ii) 10 times tap setting current
viii) Type of characteristics
ix) Trip contact rating(amps)
x) Whether seal in contacts provided or not( yes/no)
C DIRECTIONAL OVER CURRENT & E/F RELAY
i) Maker’s name
iii) Whether numerical in principle
iv) Sampling rate for current & voltage inputs
v) current coil rating
vi) potential coil rating
viii) VA burden
a) current coil
b) voltage coil
ix) Whether draw out type or not
x) Short time thermal over load rating of current coil
xii) Dynamic over load of current coil
xii) Aux. Voltage rating
xiii) Aux. Power consumption(max)
xiv) No. of binary inputs
xv) No. of binary out put relay
xvi) No. of LED indication
xvii) Type of serial comm. Interface
xviii) Type of mounting
xix) Degree of protection
xx) Reference standard
xxi) Characteristics provided
a) definite time
xxii) Tolerance in pickup
xxiii) Tolerance in delay time
xxiv) Reset ratio
xxv) Characteristics angle
b) for earth fault
xxvi) Voltage polarising threshold
a) for O/C unit
b) for earth fault
xxvii) Software model & version provided for communication unit PC
xxviii) Remote communication facility whether provided
xxix) Trip contact rating amps
xxx) Whether seal in contacts provided or not(yes/no)
a) Name and country of manufacturer
b) Manufaturer's type and designation
c) Overall dimension in mm (max.)
d) Flush type of not?
f) Weight in kgs
g) Min. and Max. voltage of operation
h) Reference Standard
i Type of hardware
j) Alarm sequence
k) Switching unit
M) Switch Board
a) Maker's name
b) Manufacturer's type designatin
ii) Complete Board
d) Details and description of minic provided
e) In how many sections each switchboard shall be despatched
f) Overall dimensions of each section
g) Weight of each section
h) Dimension of the largest package
i) Weight of the largest package
Each section of all switchboards shall have independent supporting and uniting arrangement
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.22 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF AC & DC BOARDS
Name of the tendering company
Sl.No Description As per Tenderer
3 Current Ratings
4 Temperature rise above 50°C ambient
5 Minimum clearance of busbars and Connections
a) Between Phase/(+) Ve to ( - ) Ve
b) Phase/(+)Ve or (-) Ve to Earth
6 Bus Support Insulator
c) Voltage class
7 All bus works braced for K.A.rms/KA for D.C
8 1 minutre H.V. withstand test KV rms/KV for DC
9 Bus Bar conforms to
B. MOULDED CASE CIRCUIT BREAKERS
2 Voltage Pole & Frequency
3 Current Rating
a) Rated continuous Current Amps
b) Derated current due to site conditions & 50° ambient Amps
c) Short time current rating for 1 sec.
4 Breaking Capacity
a) MVA Symmetrical at
b) KA (RMS) Symmetrical
c) KA(rms) symmetrical
5 Making Current
6 Total Interrupting time
7 Total closing time
8 One minute Power frequency withstand Voltage.
9 Breaker main contacts
a) Type & Material
b) Silver Plating Provided
10 Type and Operating mechanism
11 No.of Auxilliary Contacts
a) Short circuit & overload releases furnished
b) Range of release
13 Mechanical safety interlock furnished ?
14 Weight of each breaker
15 Standard to which breaker conforms
C MAGNETIC CONTACTORS AC DC
2) Catalogue No.
b) Derating factor, if any for higher ambient 50°C
d) Utilisation category
5) Contactor conforms to
6) Operating coil
a) Rated Voltage
b) Pick-up Voltage
c) Drop out Voltage
7) Power comsumption of operating Coil during closing/after closing
8) Auxiliary contact furnished
a) Number of NO Contacts
b) Number of NC Contacts
c) Contact ratings 240 VAC/250 VDC
I) Make & continuous- Amps
ii) Break Inductive- Amps
9) Starter capable of withstanding let through currents of back up fuses.
10) Thermal Overload
a) Temperature compensated type
b) II and reset type
c) Thermal overload fuse furnshed
11) D.C.Starters furnished complete with relays, capacitors, Resistors and Meter with shunt etc. as per drawings and schedule
12) Contractor conforms to
D. ISOLATING SWITCH FUSE
Isolating Switch
2) Catalogue No.
4) Voltage, Phase & Frequency
5) Current Rating
6) Derated current rating if any for higher ambient 50°C.
7) Incomer Switch fuse Unit of A.C system provided with removable neutral link.
8) Switch conforms to
2) Catalogue No.
5) Repturing capacity
6) Current rating Amps.
7) Cut off current K.A
8) Cut-off characteristics curves furnished
9) Control fuse
c) Repturing capacity KA rms/KADC
10 Fuse conforms to
E,. AUXILIARY RELAY/CONTACTOR, METER ETC.
Auxiliary Relay/Contactor AC DC
1) Furnished as shown in the schedule of materials ?
3) Catalogue no.
5) Coil voltage with variation METERS
2) Catalogue no.
4) Meter conforms to PUSH BUTTONS
2) Catalogue No.
3) Control function for
a) Non Reversing starter
b) Reversing Starter
4) No.of contacts per button
5) Contact rating
1) Voltage of lamps & series resistor
2) Wattage of lamps
3) Wattage of series resistor
F CURRENT TRANSFORMERS
3) Current ratio as per drawing
4) Rated output……….VA
5) Accuracy class
6) C.T.conforms to
6 DISTRIBUTION BOARDS
2) Fixed type control unit
a) Dust & Vermin proof
b) Thickness of sheet metal used.
4) Vertical wireways furnished for each section
5) Main & vertical buses furnished
6) Space heaters
a) Thermostate controlled space heater furnished for each Board
a) Furnished for each Board
b) Materials & size
a) Wirings size & Insulation
b) Voltage class
9) Cable lugs, glands & terminals furnished for power cables as given in the schedule of materials.
10) Control Cableterminals
b) 10% spare furnished for module
11) Board completely assembled wired and tested at the factory
12) Finish of Distribution Board
13) Boards conforms to
14) Name & Distribution Board, weight, overall dimension.
4.23 GUARENTEED TEHNICAL PARTICULAR FOR 500 MVA, 400/200/33 KV POWER TRANSFORMERS
Sl. No Description As Per BSPTCL's Specification To be quoted by bidder
4.23 GUARENTEED TEHNICAL PARTICULAR FOR 160 MVA, 220/132/33 KV POWER TRANSFORMERS
Sl. No Description As Per BSPTCL's Specification To be quoted by bidder
1 Name of the Manufacturer
2 Installation [indoor/outdoor]
3 Reference standards
4 Continuous Ratings
a Type of cooling
i With ONAN cooling
ii With ONAF cooling
iii With OFAF cooling
c Rated voltage
ii IV [KV-rms.]
iii LV [KV-rms.]
d Highest system voltage
ii IV [KV-rms.]
iii LV [KV-rms.]
e Rated frequency with ±% variation
f Number of phases
g Current at rated full load and on principal tap
6 Connection symbol and vector group.
7 Temperature rise
a Temperature rise of oil above reference peak ambient temperature i.e.50 °C [by thermometer] [°C]
i At full ONAN rating [°C]
ii At full ONAF rating [°C]
iii At full OFAF rating [°C]
b Temperature rise of winding above reference peak ambient temperature [by resistance method][°C]
i At full ONAN rating [°C]
ii At full ONAF rating [°C]
iii At full OFAF rating [°C]
c. . Temperature gradients between windings & oil
d. Limit of Hot spot temperature for which the Transformer is designed [°C]
e Period of operation of transformer at full load without calculated winding hot spot temperature exceeding l50°C and with
ii 100% Coolers
8 Type of ON load tap changing switch
9 Tapping on windings for
i Constant flux/variable flux/combined regulation.
ii Tapping provided at
iii Number of steps
iv Range of tapping for variation [+ percent to- percent]
10 i No load loss at rated voltage and frequency at principal tap [KW]
ii No load loss at the voltage corresponding to highest tap [KW]
11 Load loss at rated output, rated frequency, ONAN ONAF OFAF corrected for 75 °C winding temperature at:-[Copper loss + cooler loss]
i Principal tap [In KW]
ii Highest tap [In KW]
iii Lowest tap [In KW]
12 Auxiliary losses at rated output, normal ratio, rated voltage, rated frequency and ambient temperature [KW]
13 Total losses at normal ratio inclusive of auxiliary equipment losses [KW]
14 Positive sequence impedance on rated MVA HV to IV HV to LV IV to LV base at rated current and frequency at 75° Centigrade winding temperature at
i Principal tap [%]
ii Highest tap [%]
iii Lowest tap [%]
15 Zero sequence impedance at reference temperature of 75°C at principal tap [%]
16 % reactance at rated MVA base at rated current and rated frequency at
i Principal tap [%]
ii Highest tap [%]
iii Lowest tap [%]
17 % resistance at rated MVA base at rated current and rated frequency at
i Principal tap [%]
ii Highest tap [%]
iii Lowest tap [%]
18 % Impedance at rated MVA base at rated current and rated frequency at
i Principal tap [%]
ii Highest tap [%]
iii Lowest tap [%]
19 a. Polarisation index i.e. ratio of Megger values at 600 secs to 60 secs, (H.V. to E,I.V. to E, L.V. to E, H.V. to I.V., H.V. to L.V.& I.V.to L.V.
b. Regulation at full load and 75°C winding temperature expressed as a percentage of normal voltage
i At unity power factor [%]
ii At 0.8 power factor [lagging][%]
20 Efficiency at 75°C winding temperature asderived from guaranteed loss figures at
a At full load [%]
b At ¾ load [%]
c At ½ load [%]
21 i Maximum efficiency [%]
ii Load at which maximum efficiency occurs[% of full load]
22 Time in minutes for which the transformer can be run at full load without exceeding the maximum permissible temperature at reference ambient temperature when supply to:-
i Fans is cut off
ii Fans & pumps is cut off
23 Short time thermal rating of
i Tertiary winding in kA and duration in seconds
ii IV winding in KA and duration in seconds
iii HV winding in KA and duration in seconds
24 Permissible over loading:-
25 Terminal arrangement
a High voltage [HV]
b Intermediate voltage [IV]
c Low voltage (LV)
26 ` Insulating and cooling medium
27 [A] Test voltage HV IV LV
i. Lightning impulse withstand test voltage [KVP]
ii Power frequency withstand test voltage [dry and wet] [for 1 minute] [KV-rms.]
iii Switching impulse test voltage [KVP]
[B] Design value of surges transferred on tertiary terminals:
I For 1300[900] KVP, 1.2/50 micro second surge striking HV terminal and with
a Both the tertiary terminals open[KVP]
b One terminal earthed [KVP]
ii For 900[550] KVP, 1.2/50 micro second surge striking IV terminal and with
a Both the tertiary terminals open [KVP]
b One terminal earthed [KVP]
28 Partial discharge level as per relevant IEC/ISS
29 Noise level when energized at normal voltage, frequency without load and with all cooling fans, oil pumps in running condition.
30 External short circuit withstand capacity [MVA] and duration [seconds]
31 Over-fluxing withstand capability of the Transformer
32 DETAILS OF CORE
a Type of core construction
b Type of corner joints of the core
c Maximum flux density at
i Rated voltage [220/132/33 KV] & rated frequency 50 Hz][in Tesla]
ii Highest system voltage [245/145/36 KV] and lowest system frequency [48.5Hz.][inTesla]
d No load current, no load loss and no load power factor at normal ratio and frequency [Amp/KW/p.f.]
i 10 percent of rated voltage
ii 25percent of rated voltage
iii 50 percent of rated voltage
iv 85 percent of rated voltage
v 100 percent of rated voltage
vi 105percent of rated voltage
vii 110 percent of rated voltage
viii 112.5 percent of rated voltage
ix 115 percent of rated voltage
x 120 percent of rated voltage
xi 121 percent of rated voltage
xii 125 percent of rated voltage
e Core laminations:-
i Material of core lamination [HIB/Laser grade]
ii Grade of core laminations
iii Thickness of core lamination [mm]
iv Specific loss [watt/Kg.] at rated voltage and rated frequency
v Specific loss [watt/Kg.] at highest system voltage and lowest system frequency
vi Whether specific core loss graph [flux density vs. watt/Kg.submitted
vii VA/Kg at rated voltage and rated frequency
viii VA/Kg. at highest system voltage and lowest system frequency
ix Whether VA/Kg. Vs. flux density graph submitted.
x Insulation of core laminations
f CORE ASSEMBLY:-
i Core diameter [mm]
ii Core window height [mm]
iii Core leg centre [mm]
iv Gross core cross-sectional area [m²]
v Whether details of core widths, stacks and calculation furnished as per enclosed annexure
vi Distance between centres [mm]
vii Total height of core [mm]
viii Core bolt size [mm]
ix Core bolt Insulation [mm]
In case of bolt less core design
1) Details of core belting.
2) Material, grade & type.
5) Fixing method.
x Details of top end frame.
xi Details of Bottom end frame.
xii Details of clamp plate [Material, thickness, Insulation]
xiii Details of clamp plate [material, thickness, Insulation]
xiv Total core weight [kg]
xv Core loss basing on core loss graph at operating flux density [rated voltage and rated frequency] [kw]
xvi Core stacking factor
xvii Net core area Sq. m.
xviii Margin towards corner joints, cross fluxing etc [kw]
xix Total core loss at rated voltage and rated frequency [xv+xviii] [kw]
xx Dielectric loss at rated voltage and rated frequency [KW]
xxi No load loss at rated voltage and rated frequency [xix+xx] [KW]
g Describe location/method of core grounding
h Details of oil ducts in core
i Peak value of magnetisingInrush current (% of HV rated current).
33 DETAILS OF WINDINGS.
a Type of winding
b Material of the winding conductor.
c Maximum current density of windings Conductor Current [at rated current] and conductor area area [cm²] density [A/cm²]
d Whether HV/IV windings are interleaved.
e Whether windings are pre-shrunk?
f Whether adjustable coil clamps are provided for H.V., I.V. and L.V. windings?
g Whether steel rings are used for the windings? If so, whether these are split?
h Whether electrostatic shields are provided to obtain uniform voltage distribution in the windings?
i Winding Insulation
i. H.V. & Regulating ungraded
j Insulating material used for
i H.V. & Regulating winding.
iii L.V Winding
iv For core bolts washers and end plates.
v Tapping connection.
k Insulating material used between
i H.V. and I.V. winding
ii I.V. and Regulating winding.
iii Regulating winding and H.V.winding.
iv Core and L.V winding.
v L.V.Winding and core.
vi I.V.Winding and core
vii Regulating winding and core
viii H.V.winding and core
ix H.V. to H.V.winding [between phases]
l Type of axial coil supports.
iii Regulating winding
m Type of radial coil supports
iii Regulating winding
n Maximum allowable torque on coil clamping bolts (HV IV Regulating LV )
o Bare conductor size (mm).
p Insulated conductor size (mm).
q No. of conductors in parallel (Nos.).
r No. of turns/phase
s No. of discs/phase
t No. of turns/disc
u Gap between discs. (mm).
v Inside diameter (mm).
w Outside diameter (mm).
x Axial height after shrinkage (mm).
y D.C.RESISTANCE
i L.V winding at 75 ° C (Ohms).
ii H.V. winding at 75 ° C (Ohms).(series winding) m
iii IV winding and Regulating winding at normal tap at 75° C (Ohms).(common+reg. winding)
iv IV winding and Regulating winding at highest tap at 75° C (Ohms).
v IV winding and regulating winding at lowest tap. (Ohms).
vi Total I²R losses at 75 ° C. for normal tap. (KW)
Vii Total I²R losses at 75 ° C. for highest tap. (KW)
viii Total I²R losses at 75 ° C for lowest tap.(KW).
ix Stray losses including eddy current losses in winding at 75°C (KW).
a Normal tap position
b Highest tap position
c Lowest tap position.
d Any special measures taken to reduce eddy current losses and stray losses, mention in details.
x Load losses at 75°C [I²R + stray].
a Normal tap position [KW].
b Highest tap position [KW].
c Lowest tap position [KW].
z Details of special arrangement provided to improve surge voltage distribution in the windings
aa. Tandelta(Power factor) of Winding(Max.)
bb Max. tan delta (power factor) of windings at 20 C
34 BUSHINGS. HV IV LV Neutral
a Make and type
i Rated voltage class [KV-rms.]
ii Rated current [Amps.]
b. Lightning Impulse withstand test voltage [1.2/50 micro second][KVP]
c Switching surge withstand test voltage [KVP]
35 Minimum clearance [mm]
(i) Tertiary to Core
(ii) Tertiary to top yoke
(iii) Tertiary to bottom yoke
(iv) Tertiary to IV (radially)
(v) IV to HV (radially)
(vi) HV to Regulating(radially)
(vii) IV to top yoke
(viii) IV to bottom yoke
(ix) HV to top yoke
(x) HV to bottom yoke
(xi) Regulating to Top yoke
(xii) Regulating to bottom yoke
(xiii) Outer winding to Outer winding
(xiv) Outer winding to Tank
(a) Length wise
(b) Breadth wise
36 Weight [Tolerance + 5%]
[Approximate value is not allowed]
b Core with clamping [Kg.]
c H.V. [series] winding insulated conductor [Kg.]
d I.V. [common] winding insulated conductor [Kg.]
e Regulating winding insulated conductor [Kg.]
f L.V.winding insulated conductor [Kg.]
g Coils with insulation [Kg.]
h Core and winding [Kg]
i Oil required for first filling [Liter/Kg.]
j Tank and fittings with accessories [Kg.]
k Untanking weight [Kg.]
l l Total weight with oil and fittings [kg.]
37 DETAILS OF TANK
a Material for Transformer tank
c Thickness of sheet
[No approximate value to be mentioned]
iv Radiators [mm]
d Inside dimensions of main tank
[No approximation in dimensions to be used]
ii Breadth [mm]
iii Height [mm]
e Outside dimensions of main tank
[No approximation in dimensions to be used]
ii Breadth [mm]
iii Height [mm]
f. Thickness of spray galvanisation of tank bottom.
g. Vacuum recommended for hot oil circulation [torr]
h. Vacuum to be maintained during oil filling in Transformer tank [torr]
i. Vacuum to which the tank can be subjected without distortion [torr]
j. No. of bi-directional wheels provided
k. Track gauge required for the wheels
i Transverse axis
ii Longitudinal axis
l. Type and make of pressure relief device and minimum pressure at which it operates [Kpa]
a Total volume [Liters]
b Volume between the highest and lowest visible oil levels [Litres]
c Power required by heaters [if provided][KW]
d Conservator sheet thickness
a Governing standard
b Density in gms/cu-cm
c Kinematics viscosity in CST
d Inter facial tension at 27°C in N/m
e Flash point in °C
f Pour point in °C
g Acidity [neutralization value] in mg of KOH/gm
h Corrosive sulfur in %
i Electric strength [breakdown voltage]
i As received [KV-rms.]
ii After treatment [KV-rms.]
j Dielectric dissipation factor [tan delta] at 90°C
k Saponification value in mg of KOH/gm
l Water content in ppm
m Specific resistance
i At 90°C [ohm-cm]
ii At 27 °C [ohm-cm]
n N- dm analysis CA%
o Oxidation stability
i Neutralization value after oxidation
ii Total sludge after oxidation
p Characteristic of oil after ageing test as per
i Specific resistance at
iii Sludge content
iv Neutralization number
v. % of Napthanic Content
vi. % of Paraffinic Content
vii. Details of oil preserving equipment offered
a Overall dimensions lxbxh [mm]
b Total weight with oil [Kg.]
c Total weight without oil [Kg.]
d Thickness of radiator tube [mm]
e Types of mounting
f Vacuum withstand capability
g Total radiating surface in sq.m
h Type and make of material used for the radiators
i Total number of radiators/Banks for Transformer and dimensions of tubes.
j Thickness of hot dip galvanization of radiators.
41 COOLING EQUIPMENT
a Make and type
b No. of connected units
c No. of stand -by units
d Rated power input
e Capacity [cu-m/min. or] [liters/min]
f Rated voltage [volts]
g Locked rotor current [Amps.]
h Efficiency of motor at full load [%]
i Temperature rise of motor at full load [°C]
j BHP of driven equipment
k Temperature range over which control is adjustable [°C]
l Whether the fans and pumps are suitable for continuous operation at 85 % of their rated voltage.
m Estimated time constant in v
i Natural cooling
ii Forced air cooling
iii Forced oil cooling
42 GAS AND OIL OPERATED RELAY
d Whether supervisory alarm and trip contacts provided and their sizes and Nos.
43 [I] TEMPERATURE INDICATORS
a Make and type
b Permissible setting ranges for alarm and trip
c Number of contacts
d Current rating of each contact
e Whether supervisory alarm contacts provided?
h Ratio and type of CT used for winding Temperature indicators.
[II] OPTIC FIBER TEMPERATURE SYSTEM
b Whether the offered Optic Fiber Temperature System fulfills the stipulations for the same as per this Specification
c Whether the end-user’s certificate for offered Optic Fiber Temperature System, from Indian Utilities furnished
d Whether, the Bidder has got past experience of supply of Transformers with Optic Fiber Temperature System [YES/NO]
e If ‘YES’, please state the No. of such Transformers, supplied along with the name(s) of Organisation(s), to whom supplied with Make of the Optic Fiber Temperature System, supplied and performance of the same.
44 APPROXIMATE OVERALL DIMENSIONS OF TRANSFORMER INCLUDING COOLING SYSTEM, TAP CHANGING GEAR ETC.
45 a Minimum clearance height for lifting core and winding from tank [mm]
b Minimum clearance height for lifting tank cover [mm]
46 SHIPPING DETAILS
a Approximate weight of heaviest package [Kg.]
b Approximate dimensions of largest Package [Kg.]
47 Transformers will be transported with oil/gas.
48 Size of rail recommended for the track.
49 Details of current transformers including CT for separate mounting in neutral connection to earth
b Type and voltage class
f Accuracy class
g Minimum knee point voltage [volts]
h Maximum magnetization current at minimum knee point voltage [mA]
i Maximum secondary winding resistance at 75°C[ohms]
50 LIFTING JACKS:-
a Governing standard
b No. of jacks in one set
c Type and make
d Capacity [tonnes]
g Height in closed position [mm]
h Mean diameter of thread [mm]
51 MARSHALLING KIOSK
a Make and type
b Details of apparatus proposed to be housed in the kiosk
52 Details of anti-earthquake device provided, if any
53 Separate conservator and Buchholz relay provided
54 TAP CHANGING EQUIPMENT
[These details refer to the basic rating of O.L. T.C. as guaranteed by OLTC manufacturers]
c Power flow [Uni.-directional/bi -directional/restricted bi-directional]
d Rated voltage to earth [KV]
e Rated current [Amps.]
f Step voltage [volts]
g Number of steps
h Control - manual/local-electrical/remoteelectrical
i Voltage control [Automatic/Non -automatic]
j Line drop compensation provided/not provided
k Parallel operation
l protective devices
m Auxiliary supply details
n Time for complete tap change [one step][Sec.]
o Diverter selector switch transient time [cycles]
p Value of maximum short circuit current [Amps]
q Maximum impulse withstand test voltage with 1.2/50 micro seconds full wave between switch assembly and ground [KVP]
r Maximum power frequency test voltage between switch assembly and earth [KV-rms]
s Maximum impulse withstand test voltage with 1.2/50 micro-seconds across the tapping range [KVP]
t Approximate overall dimensions of tap changer [WxBxD] in mm.
u Approximate overall weight [Kg.]
v Approximate mass of oil [Kg.]
w Particulars of the OLTC control panel for installation in control room
55 DRIVINGMECHANISM BOX
a Make and type
b Details of apparatus proposed to be housed in the box
56 Types of terminal connectors and drawing No
57 Details of painting, galvanization conforms to this Specification [Yes/No]
58 Type of oil level indicator and whether Supervisory alarm contact for low oil level provided [Yes/No]
59 Type and size of thermostat to be used
60 No. of breathers provided [Nos.]
61 Type of dehydrating agent used for breathers
62 Valve sizes and numbers
a Drain valves- mm-Nos.
b Filter valves- mm-Nos.
c Sampling valves- mm-Nos.
d Radiator valves- mm-Nos.
e Other valves- mm-Nos.
63 a) Type and make of PRV.
b No. of each type of devices per transformer
c Min. pressure at which device operates.
64 Please enclose the list of accessories and fittings, being provided on transformer. Please confirm, these are as stipulated in the tender.
65 Whether the transformer, covered is fully type tested and if so, whether copies of type test certificates, enclosed with the tender.
66 Whether tenderer can supply transformer, wound on vertical coil winding machine. Preference shall be given to the tenderer who will ensure supply of transformer wound on vertical winding machines.
67 In case Sl.No.66 is not confirmed, what are the additional pre-cautions which shall be taken by the tenderer to justify that the coil, wound on horizontal machine shall be equivalent in all respects to that which are wound on vertical winding machine.
68 What are the arrangements, available for jointing the winding. Preference shall be given to the tenderer using high-frequency brazing machines. In case other jointing techniques are used, adequacy of the same is to be recorded. Please note that bolted joints in the winding are not acceptable. This should be confirmed here.
69 Please confirm that you will guarantee maximum Impedance variation between phases within the limit of 2% only.
70 a) Please confirm that the transformer shall be dried by vapour-phase drying method. Please specify level of dryness.
b) In case, other methods of drying are used, the level of dryness, so achieved should be identical to that by VPD. Adequacy
71 Please confirm whether the In-House facilities for all routine tests as per this Tender Specification are available with the tenderer and the tenderer shall agree to conduct these tests on the transformer in the event of order.
72 Whether the Tenderer has got In-House core-cutting facility for cutting core materials for the transformer ratings as offered. (YES/NO)
73 If ‘YES’, following informations/confirmations are required: -
a Name of the manufacturer of HIB Grade core material and if so, whether copies of type test certificates, enclosed with the tender. 66. Whether tenderer can supply transformer, wound on vertical coil winding machine. Preference shall be given to the tenderer who will ensure supply of transformer wound on vertical winding machines. 67. In case Sl.No.66 is not confirmed, what are the additional pre-cautions which shall be taken by the tenderer to justify that the coil, wound on horizontal machine shall be equivalent in all respects to that which are wound on vertical winding machine. 68. What are the arrangements, available for jointing the winding. Preference shall be given to the tenderer using high-frequency brazing machines. In case other jointing techniques are used, adequacy of the same is to be recorded. Please note that bolted joints in the winding are not acceptable. This should be confirmed here. 69. Please confirm that you will guarantee maximum Impedance variation between phases within the limit of 2% only. from whom core materials will be directly imported or through their accredited marketing organization of repute. If to be imported through the accredited Marketing Organisation, Please state the name of such Marketing Organisation and please enclose the relevant documents with the Tender Offer regarding accreditation of the said Marketing Organisation by the manufacturer of the HIB core material.
b Grade, Trade Name and Thickness of the core material, to be imported
c Whether agreed for witnessing of core materials by BSPTCL’s representative(s)
d. Whether, the Bidder has past experience towards direct import of core materials. If ‘YES’, the copies of recent past Import documents to be furnished with the Tender Offer (Please state, whether the said import documents are enclosed with the Tender Offer)
e. Whether, the Bidder has got In-House CNC Machine facility for cutting of core materials
f. Whether the Bidder is agreed to follow the procedures, as stipulated at Cl.No.5.4.8 (o), (p) &(q) of this Technical Specification, as applicable for those, who have got In-House core-cutting facility
74 If the Bidder has no In-House core-cutting facility, the following informations/confirmations are required: -
a. Name of the core manufacturer of core materials from whom core materials will be directly imported or through their accredited marketing organization of repute. If to be imported through the accredited Marketing Organisation, Please state the name of such Marketing Organisation and please enclose the relevant documents with the Tender Offer regarding accreditation of the said Marketing Organisation by the manufacturer of the HIB core material.
b. Grade, Trade Name and Thickness of the core material, to be imported
c. Name of the core-cutting vendor and whether the said vendor has got In-House CNC Machine facility for cutting of core materials and whether the said vendor has been accredited by ISO
d. Whether, the Bidder has past experience towards direct import of core materials. If ‘YES’, the copies of recent past Import documents to be furnished with the Tender Offer (Please state, whether the said import documents are enclosed with the Tender Offer)
e. Whether the Bidder is agreed to follow the procedures, as stipulated at Cl.No.5.4.8 (o), (p) &(q)(1), (2), (3), (4), (5),(6) & (7) of this Technical Specification, as applicable for those, who have got no In-House core-cutting facility.
75 75. Please confirm that the facility for partial discharge test
4.23 GUARENTEED TEHNICAL PARTICULAR FOR 420kV Shunt Reactor
Sl. No Description As Per BSPTCL's Specification To be quoted by bidder
1 Name of the Manufacturer
1.1 Rated Voltage, Ur (1p.u)
1.2 Rated Capacity at 420 kV
1.4 Connection (3 Phase)
1.5 Cooling System
1.7 No of Phases
1.9 System Fault Level
1.1 Permissible current unbalance among different phases
1.11 Crest value of Third Harmonic content in phase current at rated voltage with sinusoidal wave form
1.12 Range of constant Impedance (However, complete saturation characteristics of the Reactors up to 2.5 p.u. Voltage shall be furnished)
1.13 Tolerance on current
1.14 Ratio of zero sequence reactance
1.15 Temperature rise over 50 deg C Ambient Temp at rated voltage
a Top oil measured by thermometer
b Average winding measured by resistance method
1.16 Max. design Ambient temp
a) Lightning Impulse withstand Voltage
b) Switching Impulse withstand Voltage
c) Power Frequency withstand Voltage
d) Tan delta of windings
a) Rated voltage
b) Rated current (Min.)
c) Lightning Impulse withstand Voltage
d) Switching Impulse withstand Voltage
e) Power Frequency withstand Voltage
f) Minimum total creepage distances
g) Tan delta of bushings
h) Max Partial discharge level at Ur
1.19 Maximum Partial discharge level at1.58 Ur / √3
1.2 Vibration and Tank stress level at rated voltage and frequency
1.21 Maximum Noise level at rated voltage and frequency
1.22 Maximum Permissible Losses of Reactor at rated Voltage, Frequency and at 75O C (kW)
a) 125MVAR, 420kV 3-Ph Reactor
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.1 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Station HMI
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.2 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Redundant Station HMI (in Hot-stand by mode)
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.3 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Bay level units along with bay mimic
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.4 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Bay Level Unit for Auxiliary system
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.5 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Disturbance Recorder Work Station
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.6 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Colour Laser Printer (For Reports & Disturbance records)
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.7 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Dot matrix printers ( For Alarms and log sheets)
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.8 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For All interface equipment for gateway to RCC and RSCC
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.9 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Communication infrastructure between Bay level units, Station HMI, Printers, gateways, redundant LAN etc.
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.10 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Remote workstation including HMI and along with one printer
Name of the tendering company
Sl.No Description As per Tenderer
BIHAR STATE POWER TRANSMISSION COMPANY: PATNA
4.24.11 SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS For Modems
Name of the tendering company
Sl.No Description As per Tenderer
SCHEDULE FOR GUARANTEED TECHNICAL PARTICULARS FOR XLPE (Cu) POWER CABLES
Name of the tendering company
Sl.No. Description As per Tenderer
3 Standard Applicable
a) Voltage Grade
b) Suitable for Service Voltage and System of Earthing.
4 Maximum Conductor temperature
5 Conductor(Copper)
b) Form of Conductor
c) Number of Cores
d) Number of diameter (Stranded/Solid) of wire per core.
a) Material Insulation
c) Average Dielectric Strength
d) Dielectric Constant
7 Suitability with regard to temperature moisture ozone, acid and alkaline surroundings
8 Thickness of sheath over conductor, if any………..mm.
9 Material of sheath over cable
10 Thickness of sheath over cable………mm.
11 Electrical Performance
a) Conductor resistance at 20°C per KM
b) Maximum conductor temperature
c) Under full load
d) Under transient condition
e) Maximum operation Voltage……..Volts
f) Insulation resistance of 1 Km of cable at 20°C Mega Ohms
g) Power afactor or loss angle.
h) Tan delta of dielectric materials
I) Dielectric loss per km at rated voltage.
j) Power frequency with stand voltage KV rms.
k) Current loading data for the cable for specified operating temperature.
12) Type of Cable : Single core or stranded
a) In air in cable trays
b) In cable channels
c) In cleode ducts
d) In cable conduits and Pipes
13) Derating factors for
a) Ambient temperature
b) Grouping of 3 or 4 cables in air.in trays, channels for different spacing between cable and in closed ducts in touching position.
14) Allowable short circuit current for 3 Sec.
15) D.C.Withstand voltage
16) A.C. 50 Cycles/ second impedance.
17) A.C. 50 Cycles/ second impedance.
MECHANICAL DATA
18) Weight of Cable
a) Wt. Of conductor per Km.
b) Wt. Of PVC compound per Km.
c) Complete wt. Per Km.
d) Wt. Of Armour
19) Overall diameter
20) Maximum length per drum
21) Drum dimensions
22) Gross weight of cable drum
23) Maximum Pulling tension
24) Minimum bending radius
25) I.S.I. Certification No.
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF GENERAL PARTICULARS
(TO BE FURNISHED IN PART - I)
1 Name of Bidder:
2 Address of bidder:
3 Telegraphic address of the Bidder.:
4 Name and designation of the officer of the Bidder to whom all reference shall be made for expeditious technical co-ordinationn.
5 Place of manufacture: (Item wise)
6 Services or facilities available:
7 Availability of spare parts.:
8 Bidder's proposal number & date:
9 Offer is valid upto
10 i) Earnest money deposited or not
ii) If deposited, indicate amount and details
11 Whether terms of taking over, guarantee, Insurance are acceptable or not
12 Whether the delivery & execution schedule indicated in the specification acceptable
13 Whether liquidated damage for delay in delivery and Execution as indicated in the specification is acceptable
14 Whether latest copy of income tax clearance certificate and sales tax certificate enclosed with the bid or not.
15 Whether terms of payment indicated in the specification acceptable.
16 Whether terms as stipulated under security deposit /CONTRACT PERFORMANCE GUARANTEEEis acceptable.
17 Whether bank guarantees as stipulated under advance payment, Security deposit and performance guarantee clause of the Specification will be submitted
18 Whether agreeable to enter into a contract (As per the Performa enclosed) in the event of an order.
19 I) Are the prices quoted in price bid FIRM(only firm prices are acceptable)
II) Whether unit FOR destination prices have been quoted in the price bid.
20 Whether prices quoted are also applicable On reduced quantity or not? Rebate, on any account, if any may be mentioned.
21 Whether a statement showing deviations for General conditions enclosed.
22 Whether a statement showing deviations from Technical specificationn enclosed.
23 Whether the bidder is agreeable to execute the Contract in case deviation stipulated by him are not acceptable to BSPTCL
24 a) Whether excise duty is leviable? (for the items to be supplied by the contractor directly to the BSPTCL.)
b) If included, Indicate actual amount
25 a) Whether sales tax is chargeable? (for the items to be supplied by the contractor directly to the BSPTCL.)
b) If included, Indicate actual amount(item wise)
26 Whether certificate of past performance enclosed or not
27 Annual details of similar works executed for Past 5 years.
28 Whether unit FOR destination price (landed) of all individual items quoted in the price bid or not?
29 Whether all commercial terms are accepted or not
30 Whether all technical specifications accepted or not
31 Whether prices are quoted for all works including Design, Engineering, drawing, supply of materials / Equipments, erection and commissioning of complete Substation and .s (all works involved.)
32 Power of Attorney authorizing the signatories of the tenderer to fill up & sign the tender is furnished in the tender or not.
33 Whether certificates granted by bankers regarding credit limit allowed to the Contractor and Bankers assessment of their Solvency submitted
34 Whether Audited balance sheets of last five years submitted or not
35 Furnish MAAT for last five financial years i.e.
37 Confirm that the total price for the complete project including design & drawing has been furnished and no extra claims shall be made for any other work required for completion of the project
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
BIHAR STATE POWER TRANSMISSION COMPANY LTD
SUPPLEMENT TO SCHEDULE-B TO BE FURNISHED BY TENDERER
(THIS MUST BE FURNISHED IN PART - I OF TENDERER)
SL. NO. POINTS TO BE CONFIRMED OR CLARIFIED BY THE BIDDER CLARIFICATION & CONFIRMATION
1 Offer must be made complete in all respects as per Technical specification
2 Prices of spares and tools and plants shall be furnished separately by the bidder on FOR site basis inclusive of all taxes etc. BSPTCL reserves the right to vary the quantity of spares during order.
3 All distribution Boards shall be fully enclosed, cabined type, fabricated from CRCA sheet steel minimum thickness as Specified in specification suitable for either wall/column/floor mounting. Indoor panels shall be dust and vermin prof. Outdoor panels shall be weather proof with canopy.
4 Though in the Specification for some equipments, particular make and type have not been mentioned, Equipments of make and types which are being used satisfactorily in BSPTCL, will be preferred. However, in case of equipments of makes, not supplied earlier to BSPTCL the credentials and updated performance reports regarding supplies made to other central and state Power utilities should be furnished. BSPTCL reserves the right to opt for the make and type.
5 Only type tested equipments and materials shall be supplied by the contractor
6 All street light poles must have independent LILO junction box, isolating switches and fuses.
7 For inside Control Room area and separate switchyard area tenderer shall have to arrange independent cable trays/racks for entire scheme with separate arrangement for D.C. cables.
8 Tenderer shall note and confirm that their scope of work shall fully comply with the requirement as detailed in BSPTCL's Specn.
9 The Insurance covering Transit Risk, Transportation Risk, handling (during loading and unloading), risk during storage, erection, commissioning, theft and fire shall be done and borne by the Tenderer for all the equipment/items devices pertaining to the sub-stn under turnkey package till the installation is handed over to BSPTCL authorities.
10 Tenderer to note and confirm that the freight charges including handling charges during loading and unloading shall be borne by the bidder. All the materials sent by the Tenderer to site by road transportation shall be suitably packed. No separate freight charges shall be paid by BSPTCL.
11 Tenderer to note and confirm that storing of all materials under this contract shall be within the Tenderer's scope of work and adequate security arrangement for the stores as well as in the areas of erection till the date of handling over, shall be tenderer's responsibility.
Tenderer to arrange their own suitable storage at their cost for lmaterials. Bidder also to construct temporary store as well as Site office at Bidders cost.
12 Tenderer to note and confirm that the BSPTCL and his duly authorised representative shall have an access to the contractor's premises, manufacturer's work for all tests of the equipment, cable etc. as listed in the schedule of tender. Inspection and testing shall be carried out as per tender specification.
13 All plants/equipment and materials to be supplied for the project shall be guaranteed as per BSPTCL specifications.
14 Tenderer to note and confirm that all the supplies shall conform to relevant ISS, IEC, I.E. RULES and BSPTCLspecifications. No material will be accepted unless covered by relevant ISS, IEC on any other relevant approved specification as required.
15 Tenderer to note and confirm that the installation shall be complete in all respects for efficient and trouble free service For this purpose any part or parts required whether specifically mentioned or not shall be deemed to be within tenderer's Scope.
Any additional quantity which may be required over and above the quantiy as per approved bill of materials based on BSPTCL approved drawing to meet the site layout requirements and to achieve the best performance level as specified to BSPTCL shall be supplied and installed at no extra cost of BSPTCL During installation of equipments at site any minor modification of civil work like chipping, grouting, make chase or holes on the walls, floors etc. including materials such as sand, steel, cement as may be required at no extra cost to BSPTCL.
16 Tenderer to note that erection tools and tackles as may be required to complete installation work shall be arranged by you at no extra cost to BSPTCL. All per commissioning checks and commissioning tools and istruments shall have to be arranged by the bidder at no extra cost to BSPTCL.
17 Tenderer to note and confirm that connectors, hardwares required for substation shall be quoted in lump sum basis which will be utilised in switchyard and shall be as per the approved drawing. These should be type tested.
18 Tenderer to note and confirm that without the written consent of BSPTCL they will not assign or sublet the total contract or any part there of other than for any part of the work for which the maker are named in the contract. Such contract if given shall not relieve him from any obligation, duty or responsibility as per the terms and conditions of the specification and the contract.
19 Tenderer to note and confirm that all the cable trays/racks/ladders/cable end boxes/conduties/electrical equipment (such as switchboard, panels, junction boxes etc shall be effectively grounded with 50x6 Flat.)
20 Tenderer to note and confirm the following for the civil work required to complete foundation under the scope of vendor on turnkey basis.
Tenderer to note and confirm that relevant data those may be required for the above work and the survey work will be undertaken immediately on receipt of confirmed order.
Tenderer also to note that all supply of consumable materials including cement and steel shall be arranged by the contractor. No separate charges for design and preparation of detailed drawing will be entertained by BSPTCL.
22 Tenderer to note and confirm the following drawings and details in quadruplicate shall be furnished as per tender specifications
a) Tentative scheme for exension of control building as per specification. Complete schedule to be furnished.
b) Tentative scheme for drainage.
c) Tentative lighting scheme both indoor and outdoor with design calculation with the light fittings used.
d) Tentative scheme for grounding along with calculations.
e) Plan, elevation and other detailed drawing for extension of control building for extension works as and where specified.
f) Detailed drawing for all connectors, hardwares and insulators.
g) Detailed plan, elevation of extension portion of 220/132/33 KV switchyard mentioning all parameter as per CBIP, ISS, I.E Rules etc.
23 Tenderer to note and confirm that the minimum illumination level of various area shall be as under (data to be used for reference purpose) which shall also conform to the latest CBIP & ISS.
EMERGENCY GENERAL EMERGENCY
Control room 300
carrier room & Engineer Room 200
other rooms 150 10 (For store room & misc. Board room only)
Corridor & Stair Case 75
Outside control building 20 _
Switchyard and roads within it 20 _
Approach Road & Boundary Wall 10 _
The tenderer shall furnish supporting design calculation for illumination at different areas mentioned above along with manufacturer's leaflets for light fittings used.
24 Tenderer to note and confirm that AC/DC change over BSPTCL Indoor type suitable for mounting complete with AC/DC conductor, auxiliary conductor, timer, test push button, DC Voltmeter, DC feeder shall have to be included in your price.
25 Tenderer to note and confirm that the lighting switch boards flash type with 5 A switch and 5A socket including space for fixing electronic hand regulator shall be used.
26 Tenderer to note and confirm that any additional requirement for AC/DC changeover board, lighting junction boxes and lighting board are required to fulfill the entire installation, depending on the requirement, shall be within the scope of work with no extra cost to BSPTCL.
27 Tenderer to note and confirm the following for the civil work required to complete foundation under the scope of vendor.
Preparation of design and detailed working drawing and construction of foundation for equipment and structure to be supplied by tenderer as per approved drawing.
a) Preparation of design and detailed working drawing for construction of control room building and execution of the same as per approved drawing.
b) Construction of RCC cover for cable trench as per approved drawing
c) Tenderer also to note that supply of all consumable materials including cement and steel shall be arranged by the contractor. No separate charges for design and preparation of detailed drawing will be entertained by BSPTCL
All the equipments provided shall also comply with the latest revision of Indian Electricity Act and Indian Electricity Rules and any another applicable statutory provisions, rules and regulations. All equipments provided under the specification shall generally conform to the latest issue of the ISS and BSPTCL specifications.
30 Tenderer to confirm that they will furnish following documents:
i) Bank Guarantee towards security deposit/contract performance, guarantee before execution of the contract Agreement.
ii) Bank Guarantee for advance payment
iii) Pert CPM/Barchart/Execution schedule for completion of the project before execution of the agreement
iv) Indemnity Bond for the equipments delivered and handed over to the contractor.
v) Bank Guarantee against performance guarantee.
vi) Power of Attorney by all the partners in case of Joint Venture for authorising the lead partner
vii) Copy of Agreement executed by the members of Joint Ventures.
31 Sales tax on Works contract, Turnover Tax on any other similar taxes under the Sales Tax, Act, as applicable, are included in the Bid/tendered price and BSPTCL/Purchaser shall not bear any expenditure/liability on this account. Entry tax, if any shall be extra.
This is also hereby confirmed that the award of two contracts will not in any way absolve the contractor of any responsibility and obligation as per the terms and conditions of the tender specification for succesful completion of the complete work as per the tender specifications and both the contract will have a cross fall breach Clause i.e., a breach in one contract will automatically be considered as breech of the other contract which will conform the BSPTCL/Purchaser/ Employer the right to terminate the other contract at th contractor's risk and cost.
34 It is hereby confirmed that if any income-tax, surcharge on income tax or any other corporate tax is applicable/payble under the law, the same shall be paid by the contractor.
35 It is confirmed that the contract shall be executed strictly in accordance with the specifications and documents except for the variations and deviations, all of which have been detailed out exhaustively in the following schedules irrespective of what soever has been stated to the contrary any where else in the tender/offer/bid.
i) Schedule of deviations against technical specifications Schedule "C"
ii) Schedule of deviations against general conditions of the contract. Schedule "D"
iii) Schedule of revision of prices against deviations as detatiled under schedule "C" and "D" Schedule "J"
36 Confirm that the following clauses as specified in the tender specifications are accepted unconditionally and no deviations/exceptions are taken on any account whatsoever.:
ii) Security Deposit
iii) Earnest Money
iv) Liquidated damage for delay,stage penalty, incentives.
vi) Terms of payment
vii) Performance guarantee
viii) Taking over
xii) Time for execution of the contract
37 Confirm that additional conditions, deviations, if any, found in the proposal documents other than those stated in the deviation schedules, save the pretaining to any rebate, offered, shall stand with drawn.
38 Unit rates of items/equipments/works as and where required have been furnished
39 The details of equipments/materials proposed to be supplied as bought out items have been furnished in a separate schedule.
40 The required documents related to the pre-qualification of he tenderers as detailed in the tender specifications has been furnished in the tender. The documents for the fulfillment of the requirement of the tender specifications have been furnished.
41 Confirm that if the offer is submitted against the tender is accepted by the BSPTCL, the contractor agree to submit engineering data, provide services and complete the entire work in accordance with schedule indicated in the tender/offer. It has been clearly understood that the time for completion of the project is the essence of the contract and hence the execution schedule shall be strictly adhered to the execution schedule has been furnished with the offer.
42 Separate schedule for each item for which L.S. price have been quoted should be furnished with part I of the tender.
43 Confirm that all equipments and materials confirming strictly to the tender specification only shall be offered to be delivered in case the order is placed on the bidder. In case of any deviations in the technical specification or make of offered materials/equipments, the BSPTCL shall not be responsibble for any delay even if it is approved.proved.
44 Confirm that no extra claim shall be entertained by the BSPTCL for the specified scope of work
46 To confirm whether 10% BG would be furnished by that contractor towards employing vendor support if any during guarantee period of SAS as per Cl. 1.3.39.1 of Vol. I of tender specification. Please specify clearly whether support of vendor would be obtained for SAS system or the contractor itself is capable for design, manufacture, supply and installation of SAS system.
47 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'P-III'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF DEVIATIONS AGAINST TENCHINCAL SPECIFICATIONS.
(TO BE FILLED IN BY THE TENDERER)
We/I have carefully gone through the Technical specifications and We/I have satisfied our-seleves/myself and hereby confirm that our/my offer strictly conforms to the requirements of the technical specifications except for the deviation which are given below. The amount by which the tendered price will increase or decrease has been indicated in the schedule 'J' of the specification.
Sl. No. Description (Clause/ Page) Stipulations in specification Deviation offered Remarks
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'C'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF DEVIATIONS AGAINST GENERAL CONDITIONS OF THE CONTRACT
(TO BE FILLED IN BY THE TENDERER)
We/I have carefully gone through the general conditions of contract and We/I have satisfied our-seleves/myself and hereby confirm that our/my offer strictly conforms to the requirements of the general conditions of contract except for the deviation which are given below. The amount by which the tendered price will increase or decrease has been indicated in the schedule 'J' of the specification.
Sl. No. Description (Clause/Page) Stipulations in specification Deviation offered Remarks
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'C'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF ERECTION & MAINTENANCE TOOLS
(TO BE FILLED IN BY THE TENDERER)
The tenderer shall furnish below a list of special tools, accessories and equipments required for installation testing and maintenance including their prices.
Sl. No. Description Number recommended Unit Prices inclusive of all taxes & duties Unit Prices inclusive of all taxes & duties Unit Prices inclusive of all taxes & duties Purpose of use
F.O.R. Works F.O.R. Site Total
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'E'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF SPARES.
(TO BE FILLED IN BY THE TENDERER)
The tenderer shall furnish below a list of spare parts which he recommends for five years operation other than those mentioned in specification.
Items No Description Number recommended Unit Prices inclusive of all taxes & duties Unit Prices inclusive of all taxes & duties Unit Prices inclusive of all taxes & duties Purpose of use
F.O.R. Works F.O.R. Site Total
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'F'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF DRAWINGS
(TO BE FILLED IN BY THE TENDERER)
The tenderer shall furnish below a list of drawings which shall be furnished by them
Sl. No. Name of drawing When to be submitted (to be given in days) after issue of letter of intent.
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'G'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF PAST EXPERIENCE
(TO BE FILLED IN BY THE TENDERER)
(A) FOR SUB STATION WORKS
(i) Works Already Executed
Sl. No. Details of works Name of customer for whom work has been executed. Date of commissioning Value of the works Remarks.
(ii) Works under Execution
Sl. No. Details of works Name of customer for whom work has been executed. Date of commissioning contractual Value of the works Remarks.
21 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'H'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF DELIVERY/EXECUTION PERIOD
(TO BE FILLED IN BY THE TENDERER)
Guaranteed delivery/completion period counted from the date of issue of Purchase Order/Work order.
Sl. No. Name of equipments & works Commencement period in month Time period of supply erection and commissioning per month Total completion period in month
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'I'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
SCHEDULE OF REVISION OF PRICES
(TO BE FILLED IN BY THE TENDERER)
Against each and every deviation from the specification's conditions as enumerated in the Technical deviation schedule 'C' and Deviations in the General condition Schedule 'D' enclosed, the Amount by which the tendered price will be increased or decreased be indicated clause by clause in this schedule. In case the amount is not mentioned in this schedule against any of the deviations mentioned in deviation sheet (Schedule 'C' & 'D') it will be taken for granted that the same does not involve any change in the tendered price.
Name of the Contractor / Bidder
Clause No. Deviation if any Amount by which the tendered Price will change Amount by which the tendered Price will change
1 Increase Decrease
2 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'J'
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
PROFORMA FOR QUALIFICATION
1 We have noted that to be qualified for award, tenderers shall provide evidence satisfactory to the BSPTCL of their capability and adequacy of resources to carry out the contract effectively. The following information/ documents are furnished/submitted along with our bid :
a Copies of original documents defining the constitution of legal status, place of registration and principal place of business; written power of attorney of the signatory of the bid to commit the bidder.
b The audited balance sheets for the last five years.
2 Other details in support of Qualifying Requirement have been filled in formats given at the subsequent pages of this Schedule. All individual firms and each Partner of a Joint Venture bidding for the package are requested to complete the information in the form. The requisite information to be provided for all firms (individual sole bidders as well as partner of Joint Venture bidder).
a Joint Venture Summary : If bidder is a joint Venture of two or more Partners.
Name of the Bidder
Name of all Partners of joint Venture
Name of Partner No. 1
Name of Partner No. 2
Name of Partner No. 3
Name of Partner No. 4
Details of J V Agreement. The tenderers should submit details in the following format --- The Joint Venture Agreement as per specified format is enclosed at ___________ __________________M/s ________________________is nominated as lead Partner and Power of Attorney authorising M/s ________________as lead Partner, signed by legally authorised signatories of all Partners is enclosed at _____________________.
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
3.(b) (i). The following is the list of orders executed by us for 220 KV and above voltage Sub-Station and ., the details of which are furnished in the support of Qualifying Requirements.
Name of the Contractor / Bidder
Sl. No Customer Order Ref. & Date Order Value (Lakhs) (Rs.) Sub Stn. or Line Voltage (KV) Total Line Length (Km) or Sub Stn Capacity Scope of work in case of Transmission line Scope of work in case of Sub Stn. Scope of work in case of Sub Stn. Scope of work in case of Sub Stn. Date of Commissioning of Sub-Stn.
Length of Transmission line No of 220 KV or above line Bays No of220/ 132/33 KV or above Transformer Bays Transformer Capacity
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-2'
4. (B) (ii). Our Annual Turnover for the last five years are as follows :
Sl. No. Financial Year (Specify) Annual Turnover
(in Rs. Crores)
Average Annual Turnover for best three years out of last five financial years is Rs. ___________ Crores.
5. We hereby confirm that the liquid assets (current assets minimum inventories) And/or evidence of excess to or availability of credit facilities of our company, i.e. ___________________as on _______________(date) in Rs. ________ Crores
6 In accordance with the tender documents, Certificate(s) from Banker issued on ____________ (date) as per requisite format, various fund based/non-fund based limits sanctioned to the Bidder or each member of the Joint Venture and the extent of utilisation as on date is/are enclosed at _________________________.
7 The monthly cash flow projection for execution of the Contract is as follows :
Sl No. Month Anticipated Cash Flow Source
8 Details of Bidder's Banks :
Name of Banker Address of Banker Telephone Contract Name and Title
9 Details of Litigation History
Year Award for or against Applicant Name of Client, cause of litigation and matter in dispute Disputed amont (current value in Indian Rupees)
10.0 Certify that the above informations furnished by me are true and correct to the best of my knowledge.
11 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-4'
FORMAT FOR DETAIL ABOUT BOUGHT OUT ITEMS
We hereby furnish the details of the items/equipments, which we proposed to buy for the purpose of supply for the project with construction.
Sl. No. Item Description Source of supply
BIHAR STATE POWER TRANSMISSION COMPANY LTD: PATNA
FORMAT FOR WORK COMPLETION SCHEDULE FOR SUBSTATION WORK
We hereby declare that the following work completion schedule shall be followed by us in supply and erection of the equipments for Sub station & . works. The period indicated below from the date of order of the contract to us :
Name of the Contractor / Bidder
Sl. No. Description of Work Period of Months
1 Finalisation of Sub - Vendors
2 Completion of detailed engineering
3 Procurement of raw materials / bought out items
i) Commencement
4 Manufacturing
ii) Commencement
5 Type testing (if required)
i) Commencement
6 Despatch and receipt at site
i) Commencement
7 Soil investigation
i) Commencement
8 Establishment of site office
9 Erection in during civil / works
i) Commencement
10 Testing & Commissioning
i) Commencement
11 Commissioning & issuance of taking over
12 Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-VI'
CHECK LIST TO BE SIGNED BY TENDERER AND TO BE FURNISHED ALONGWITH THE TECHNICAL PART OR THE TENDER.
NAME OF THE BIDDER
Sl. No. Description Furnished (Yes or No) Page no of the offer
(I) SCHEDULE "A" OF PRICE - P-I
(II) SCHEDULE "B" OF GENERAL PARTICULARS -PII & III
(III) SCHEDULE "C" OF DEVIATIONS FOR SUPPLY AND DELIVERY AGAINST TECHNICAL SPECIFICATION -PIV
(IV) SCHEDULE "D" OF DEVIATIONS AGAINST GENERAL CONDITIONS OF THE CONTRACT - PV
(V) SCHEDULE "E" OF ERECTION AND MAINTENANCE TOOLS. - PVI
(VI) SCHEDULE "F" OF SPARES - PVII
(VII) SCHEDULE "G" OF DRAWINGS - PV III
(VIII) SCHEDULE "H" OF PAST EXPERIENCE - PIX
(IX) SCHEDULE "I" OF DELIVERY - PX
(X) SCHEDULE "J" REVISION OF PRICES - PXI
(XI) COPY OF ELECTRICAL CONTRACTOR’S LICENCE.
(XII) AUTHORITY OF SEEK REFERENCES FROM THE TENDERER’S BANKERS.
(XIII) FOR LETTER OF UNDERTAKINGS - PXV
(XIV) BALANCE SHEET FOR LAST 5 YEARS i.e, PROFIT & LOSS STATEMENT. (FURNISH MAAT VALUE)
(XV) POWER OF ATTORNEY IN RESPECT OF TENDERERS SIGNATURE - PXVIII
(XVI) ATTORNEY IN RESPECT OF JOINT VENTURES-PXIX
(XVII) FOR QUALIFICATION REQUIREMENT - PXX
(XVIII) FOR TENDER TECHNICAL BID - PXXI
(XIX) FOR TENDER PRICE BID - PXXII
(XX) DETAILS OF LIQUID ASSETS.
(XXI) FOR EVIDENCE OF ACCESS TO OR AVAILABILITY OF CREDIT FACILITIES - PXXIV
(XXII) FOR DETAILS ABOUT BOUGHT OUT ITEMS-PXXV
(XXIII) WORK COMPLETION SCHEDULE FOR SUB STATION WORK AND TRANSMISSION LINE -PXXVI
(XXIV) WORK COMPLETION SCHEDULE FOR WORK -PXXVII
(XXV) EMD- PXXVIII
(XXVII) AN AFFIADEVIT CONFORMING THAT ALL THE DETAILS AND DOCUMENTS FURNISHED ALONG WITH THE TENDER ARE CORRECT AND TRUE COPIES OF ORIGINALS
(XXVIII) Copies of original documents defining the constitution or legal status, place of registration and principal place of business, written power of attorney of the authorized signatory of the bid to commit the tender.
(XXIX) Total annual turnover in construction work of a similar nature performed by the tenderer in his own name (not by any other company whose name has subsequently been changed so as to form the current tenderer) in each of the last five years.
(XXX) Experience in executing similar projects (Nature & Volumes) for each of the last 5 (five) years, and details of work in hand and contractual commitments, clients who may be contacted for further information on those contracts. The copy of performance certificate issued by end users/utilities may be furnished.
(XXXI) Qualifications and experience of key site management and technical person proposed for the contract.
(XXXII) A certificate from a bank or reputable firm of accountants conforming the liquidity (liquid asset and credit facilities) of the tenderer at a date one month prior to the last date for submission of tenders.
(XXXIII) Solvency Certificate to be furnished.
(XXXIV) Evidence of adequacy of working capital for this contract i.e. evidence of access of line (s) of credit and availability of other financial resources.
(XXXV) Authority to seek references from the tenderers bankers.
(XXXVI) Information regarding any current litigation in which the tenderer is involved, the parties concerned and disputed amount.
(XXXVII) Statement of safety policy and safety statistics for the last 5 years.
(XXXVIII) Copy of QA Certification and associated documentation.
Note:- Please note that the non submission of any document and confirmation of the above matters shall lead to out right rejection of the tenders/ offers/ bids without any further correspondence.
Bihar State Power Transmission Company Limited
Work as detailed in SBD
Evaluation Sheet for Technical Proposal
NIT No. 15/PR/BSPTCL/2026
GENERAL INFORMATION
1 NAME OF BIDDING FIRM
Tel No. Fax No. Email Id
3 MODE OF APPLICATION(Single/JV)
4 APPLIACANT INFORMATION Individual or Lead Applicant II Aplicant:
Country of Incorporation: Year of Incorporation: Country of Incorporation: Year of Incorporation:
III Applicant: IV Applicant:
Country of Incorporation: Year of Incorporation: Country of Incorporation: Year of Incorporation:
(General and Management Information)
5 CONTACT PERSON Name Post
6 AUTH. SIGNATORY Name Post
Bihar State Power Transmission Company Limited
Work as detailed in SBD
Evaluation Sheet for Technical Proposal
NIT No. 15/PR/BSPTCL/2026
Name of Bidder(s)
Individual or Lead Applicant
A= Maximum annual turnover in any one year during last 5 years (Updated to the price level of last year @ 8% a year. i.e. Indexed at present value of last year taking 8% as indexing rate) taking into account the completed as well as works in progress. (In crore) N= No. of years prescribed for completion of works for which bids are invited. (considering the project completion period of 24 months, N=2, for 18 months N=1.5, For 15 Months N=1.25) M =3 B= Value, at the current Price level of existing commitments and ongoing works (Electrical and other) to be completed during the period of completion of work for which bids are invited (to be submitted by the bidder) Bid Capacity (AxMxN - B) In Crore
A= Maximum annual turnover in any one year during last 5 years (Updated to the price level of last year @ 8% a year. i.e. Indexed at present value of last year taking 8% as indexing rate) taking into account the completed as well as works in progress. (In crore) N= No. of years prescribed for completion of works for which bids are invited. (considering the project completion period of 24 months, N=2, for 18 months N=1.5) M =3 B= Value, at the current Price level of existing commitments and ongoing works (Electrical and other) to be completed during the period of completion of work for which bids are invited (to be submitted by the bidder) Bid Capacity (AxMxN - B) In Crore
BIHAR STATE POWER TRANSMISSION COMPANY Ltd, PATNA
SUMMARY OF PRICE
Price Break up for Construction of 10 nos. of 132 KV AIS Line Bays for 2nd source connectivity of GSS Ramnagar, Sherghati and Piro and residential quarter at GSS Ramnagar on Turnkey Basis
NIT No. 15/PR/BSPTCL/2026
NAME AND ADDRESS OF THE BIDDER
SL NO. Description Price (Rs.)
1 Total Price for Supply of all materials and equipments including GST. 0.00
2 Total Price for Freight Charges including GST. 0.00
3 Total Price for Insurance Charges including GST. 0.00
4 Total Price for Erection, Testing & Commissioning Charges including GST. 0.00
5 Total Price for Civil works including GST. 0.00
6 Total Price of the Project (in Figure) 0.00
7 Total Price of the Project (in words)
(Tenderer shall quote prices for the following mentioned items. Prices of all accessories, assemblies, components, parts etc. associated with these items are included in tenderer's quoted prices for these items).
Price Break up for Construction of 10 nos. of 132 KV AIS Line Bays for 2nd source connectivity of GSS Ramnagar, Sherghati and Piro and residential quarter at GSS Ramnagar on Turnkey Basis
Name of Bidder & Address
Sl. No. Item Description HSN Code Unit GSS Sherghati (02 Nos. line bay) GSS Chandauti (New) (02 Nos. line bay) GSS Piro (02 Nos. line bay) GSS Ramnagar (02 Nos. line bay) GSS Raxaul (New) (02 Nos. line bay) Total Qty. Unit Ex Works Price(Rs Total Ex Works Price(Rs) SGST (in %) CGST (in %) IGST (in %) Unit GST (Rs.) Total GST (Rs.) Unit Supply Price incl. of GST (Rs.) Total Supply Price incl. of GST (Rs.)
A 132 kV EQUIPMENT
1 Circuit breaker (3 phase)
i) 1600 A, 40 kA SF6 CB C2-M2-E2 class with support structure, marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) ( Spring- Spring mechanism). Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
2 ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm 0 0.00 0.00 0.00 0.00 0.00
i) 1600 A, 40 kA with one earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
ii) 1600 A, 40 kA without earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
iii) 1600 A, 40 kA without earth switch (Double break Isolator)(Tandem arrangement) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
iv) 2500 A, 40 kA without earth switch (Double break high level beam mounted Isolator) Nos. 1 1 2 2 2 8 0.00 0.00 0.00 0.00 0.00
3 Current Transformers 5 core (1 phase) (the winding of CT shall be of copper only) 0 0.00 0.00 0.00 0.00 0.00
i) 1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,31.5 kA with 120% extended current rating with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
4 8800 pF CVTs (1 phase) with marshalling boxes, terminal connectors etc . (The winding of CVT shall be of copper only) Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
5 120 kV Surge arresters class-IV (SH Class) ( 1 phase) with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
6 Portable Discharge Rod Nos. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
B ERECTION HARDWARE (132 kV) 0 0.00 0.00 0.00 0.00 0.00
1.1 Insulator (Porcelain long rod insulators-120kN), antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, connectors suitable for twin moose & quad moose (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.) 0 0.00 0.00 0.00 0.00 0.00
132 KV, Main Bus & Transfer Bus complete work including all items 0 0.00 0.00 0.00 0.00 0.00
1.2 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 20 20 16 20 14 90 0.00 0.00 0.00 0.00 0.00
1.4 Bus extension for two bays Set 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
C LT Switchgear 0 0.00 0.00 0.00 0.00 0.00
1.1 415 V ACDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 3 (three)sources of AC Power from 2 SST's & Diesel Generator(DG). Also provisions to be made for use of either source of power from SST & DG or both sources of power from SST at a time with provision of electro-mechanical interlock. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
1.4 220 V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel shall be done individually for each CRP. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
1.5 48V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel/ Communication Panels shall be done individually for each CRP/ Communication Panels. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
D CONTROL & RELAY PANELS 0 0.00 0.00 0.00 0.00 0.00
Control, Relay & Protection Panel for all indicating meters and multi function meters shall be communicable types with 0.5 class accuracy. 1 bay control unit with bay mimic to be provide separately in control panel. 0 0.00 0.00 0.00 0.00 0.00
a) 132 KV line (with A/R) with numerical distance protection relays (with the features of load blender and PRP) and earth fault / overcurrent relays complying to IEC 61850 Protocal with optical fiber ports sufficient DI/DO for scheme with additional 6 DI/DO for spare with under frequency Relay. All indicating meters/ multifunctions meters shall be communicable tpe with 0.5 class accuracy and 0.2 S class ABT energy meter (with modem) to be provided. (relay shall have feature of PRP and load blinder) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
b) Provision for Supply and extension of Bus Bar protection scheme for 02 nos. new bays and integration with existing bus bar protection panel. The scheme should be compatible with make and type (Centralised/distributed) of existing bus bar protection scheme at GSS (Bus Bar protection should be low impedence and will have 04 zones with numerical type of relays complying IEC 61850 (edition 2) protocol as where applicable with complete cabling works. Sets. 0 1 0 0 1 2 0.00 0.00 0.00 0.00 0.00
c) Digital Protection Coupler suitable for integration and operation through OPGW System with required cables, complete in all respect i.e connectivity and matching with remote end. Work for remote end comprising dismantelling, shifting, erection & commissioningis in the scope of bidder. Sets. 4 4 4 4 4 20 0.00 0.00 0.00 0.00 0.00
G FIRE PROTECTION SYSTEM 0 0.00 0.00 0.00 0.00 0.00
1.1 Portable Fire Extinguishers 0 0.00 0.00 0.00 0.00 0.00
d 12 Fire buckets with covered stands Nos. 2 2 2 2 4 12 0.00 0.00 0.00 0.00 0.00
a Heavy duty PVC conduits as of 20/25/32 mm size complete with all accessories for point wiring for Light points, Fans power points 5/15 amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and 1.5 mm2 copper earth wire PVC insulated in green color including wiring for submains i.e. wiring from Lighting panel to switch board. LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
b Wiring from lighting panel to switch boards, from switchboard to junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as per technical specification, complete in all respect. 1.5 mm2 copper wire (green) will be used for earthing inside conduits LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
I Telephone sockets 0 0.00 0.00 0.00 0.00 0.00
a Single socket outlet comprising RJ-11 socket Nos. 5 5 5 5 5 25 0.00 0.00 0.00 0.00 0.00
b Dual socket outlet comprising RJ-45 socket Nos. 3 3 3 3 3 15 0.00 0.00 0.00 0.00 0.00
J ILLUMINATION SYSTEM (The quantities mentioned below is tentative for tendering purposes and the final quantities will be decided during detailed engineering based upon lux level calculations) 0 0.00 0.00 0.00 0.00 0.00
1.a Lighting Panel (Outdoor) Type ACP-2 Nos. 1 1 1 1 2 6 0.00 0.00 0.00 0.00 0.00
1.a Lighting Panel (Outdoor) Type ACP-3 Nos. 1 1 1 1 2 6 0.00 0.00 0.00 0.00 0.00
2 LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements) 0 0.00 0.00 0.00 0.00 0.00
b Supply of Complete fitting of LED Flood Lighting Luminairs (<250 Watt) having minimum System Lumen Output of 23000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00
c Supply of Complete fitting of LED Flood Lighting Luminairs (<530 Watt) having minimum System Lumen Output of 60000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00
d Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear Nos. 4 4 2 1 4 15 0.00 0.00 0.00 0.00 0.00
e Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
f Lighting fixture Type-MP: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
g Lighting fixture Type- SC: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
h 15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
i 63A, 415V: Interlocked switch socket outdoor receptacles (Type RP) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
j Lighting Poles Type A1 Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
k Lighting Poles Type E1 Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
K Cables alongwith associated accessories like clamps, glands, lugs and straight joints, Feruls, Tagging etc. 0 0.00 0.00 0.00 0.00 0.00
i Any other size as per requirement KM 0 0.00 0.00 0.00 0.00 0.00
L Earthing mat with GI flats of following sizes for risers with spikes as per design including all materials for comlete earthing of the substation suitable for 40KA for 1 sec short time current rating 0 0.00 0.00 0.00 0.00 0.00
1.1 40 mm MS rod for main earth mat(To be procured directly from SAIL/RINL/TATA or from their stockyard) MT 30 30 8 3 2 73 0.00 0.00 0.00 0.00 0.00
1.2 75x12 mm G.I Flats for risers for equipments, columns and structures MT 10 10 6 3 2 31 0.00 0.00 0.00 0.00 0.00
1.3 50x6 mm G.I flats for risers for all other equipments etc. MT 5 5 1.5 2 1 14.5 0.00 0.00 0.00 0.00 0.00
1.4 Material for earthing pits with supply of all materials including base plate LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
i Treated earthpit set 2 2 6 4 4 18 0.00 0.00 0.00 0.00 0.00
ii Untreated earthpit set 8 8 6 8 8 38 0.00 0.00 0.00 0.00 0.00
M Sub- Station galvanized Steel structure (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design):- 0 0.00 0.00 0.00 0.00 0.00
1.1 Lattice structure with fasteners etc. (for Gantry ,tower,Beam) MT 30 30 12 12 7 91 0.00 0.00 0.00 0.00 0.00
1.2 Standard structure for equipment support (other than CB ) MT 35 35 10 10 12 102 0.00 0.00 0.00 0.00 0.00
N Pipe Type structure (as per matching with existing System) MT 4 4 12 4 4 28 0.00 0.00 0.00 0.00 0.00
P Overhead shielding 0 0.00 0.00 0.00 0.00 0.00
i. Overhead shielding against lightning by galvanized steel wires and fittings as per requirement and design (matching with the GSS) (excluding lighting cum lightning mast) LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
ii. Lightning cum Lighting masts with structure Sets. 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
R Sub- Station automation system (Suitable and integarted with existing system) comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) where ever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). Note :- Integration of SAS with SLDC patna/ERLDC with existing SCADA system in bidder scope in co-ordination with the AMC vendor of SCADA. 0.00 0.00 0.00 0.00 0.00
S Air conditioning for switchyard panel room (SPR) - 9m length with High wall type 5 star dual Invertor Split Air conditioner (BEE Complied) Units of 2 TR capacity with 5KVA stablizer and required accessories i.e. Power plug, socket, MCB, wires etc. (The quantity mentioned is tentative, which will be decided during detailed engineering based on heat load calculation) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
T Mandatory spares (L.S items break up of spares furnished separately as annexure) 0 0.00 0.00 0.00 0.00 0.00
1 132 KV CT, 1200 A, 120% extended current rating Nos. 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00
Note: (i) Where the tender quantity is shown above as ‘’LS’’ (Lump sum) or ‘’set’’, the corresponding break-up quantity is to be assessed by the bidder and indicated. (ii) Prices are firm and in any case price variation will not be considered.
(Tenderer shall quote prices for the following mentioned items. Prices of all accessories, assemblies, components, parts etc. associated with these items are included in tenderer's quoted prices for these items).
Price Break up for Construction of 10 nos. of 132 KV AIS Line Bays for 2nd source connectivity of GSS Ramnagar, Sherghati and Piro and residential quarter at GSS Ramnagar on Turnkey Basis
Name of Bidder & Address
Sl. No. Item Description HSN Code Unit GSS Sherghati (02 Nos. line bay) GSS Chandauti (New) (02 Nos. line bay) GSS Piro (02 Nos. line bay) GSS Ramnagar (02 Nos. line bay) GSS Raxaul (New) (02 Nos. line bay) Total Qty. Unit Freight (Rs) Total Freight (Rs) SGST (in %) CGST (in %) IGST (in %) Unit GST (Rs.) Total GST (Rs.) Unit Freight incl. of GST(Rs.) Total Freight incl. of GST (Rs.) Unit Insurance (Rs) Total Insurance (Rs) SGST (in %) CGST (in %) IGST (in %) Unit GST (Rs.) Total GST (Rs.) Unit Insurance incl. of GST(Rs.) Total Insurance incl. of GST (Rs.)
A 132 kV EQUIPMENT
1 Circuit breaker (3 phase)
i) 1600 A, 40 kA SF6 CB C2-M2-E2 class with support structure, marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) ( Spring- Spring mechanism). Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0 0.00 0.00 0.00 0.00
2 ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
i) 1600 A, 40 kA with one earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ii) 1600 A, 40 kA without earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
iii) 1600 A, 40 kA without earth switch (Double break Isolator)(Tandem arrangement) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
iv) 2500 A, 40 kA without earth switch (Double break high level beam mounted Isolator) Nos. 1 1 2 2 2 8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
3 Current Transformers 5 core (1 phase) (the winding of CT shall be of copper only) 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
i) 1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,31.5 kA with 120% extended current rating with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
4 8800 pF CVTs (1 phase) with marshalling boxes, terminal connectors etc . (The winding of CVT shall be of copper only) Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
5 120 kV Surge arresters class-IV (SH Class) ( 1 phase) with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.1 Insulator (Porcelain long rod insulators-120kN), antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, connectors suitable for twin moose & quad moose (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.) 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
132 KV, Main Bus & Transfer Bus complete work including all items 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.2 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 20 20 16 20 14 90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.1 415 V ACDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 3 (three)sources of AC Power from 2 SST's & Diesel Generator(DG). Also provisions to be made for use of either source of power from SST & DG or both sources of power from SST at a time with provision of electro-mechanical interlock. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.4 220 V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel shall be done individually for each CRP. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.5 48V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel/ Communication Panels shall be done individually for each CRP/ Communication Panels. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Control, Relay & Protection Panel for all indicating meters and multi function meters shall be communicable types with 0.5 class accuracy. 1 bay control unit with bay mimic to be provide separately in control panel. 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
a) 132 KV line (with A/R) with numerical distance protection relays (with the features of load blender and PRP) and earth fault / overcurrent relays complying to IEC 61850 Protocal with optical fiber ports sufficient DI/DO for scheme with additional 6 DI/DO for spare with under frequency Relay. All indicating meters/ multifunctions meters shall be communicable tpe with 0.5 class accuracy and 0.2 S class ABT energy meter (with modem) to be provided. (relay shall have feature of PRP and load blinder) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
b) Provision for Supply and extension of Bus Bar protection scheme for 02 nos. new bays and integration with existing bus bar protection panel. The scheme should be compatible with make and type (Centralised/distributed) of existing bus bar protection scheme at GSS (Bus Bar protection should be low impedence and will have 04 zones with numerical type of relays complying IEC 61850 (edition 2) protocol as where applicable with complete cabling works. Sets. 0 1 0 0 1 2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
c) Digital Protection Coupler suitable for integration and operation through OPGW System with required cables, complete in all respect i.e connectivity and matching with remote end. Work for remote end comprising dismantelling, shifting, erection & commissioningis in the scope of bidder. Sets. 4 4 4 4 4 20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.1 Portable Fire Extinguishers 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
d 12 Fire buckets with covered stands Nos. 2 2 2 2 4 12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
a Heavy duty PVC conduits as of 20/25/32 mm size complete with all accessories for point wiring for Light points, Fans power points 5/15 amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and 1.5 mm2 copper earth wire PVC insulated in green color including wiring for submains i.e. wiring from Lighting panel to switch board. LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
b Wiring from lighting panel to switch boards, from switchboard to junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as per technical specification, complete in all respect. 1.5 mm2 copper wire (green) will be used for earthing inside conduits LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
a Single socket outlet comprising RJ-11 socket Nos. 5 5 5 5 5 25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
b Dual socket outlet comprising RJ-45 socket Nos. 3 3 3 3 3 15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
J ILLUMINATION SYSTEM (The quantities mentioned below is tentative for tendering purposes and the final quantities will be decided during detailed engineering based upon lux level calculations) 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements) 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
b Supply of Complete fitting of LED Flood Lighting Luminairs (<250 Watt) having minimum System Lumen Output of 23000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
c Supply of Complete fitting of LED Flood Lighting Luminairs (<530 Watt) having minimum System Lumen Output of 60000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
d Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear Nos. 4 4 2 1 4 15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
e Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
f Lighting fixture Type-MP: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
g Lighting fixture Type- SC: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
h 15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
i 63A, 415V: Interlocked switch socket outdoor receptacles (Type RP) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
K Cables alongwith associated accessories like clamps, glands, lugs and straight joints, Feruls, Tagging etc. 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
i Any other size as per requirement KM 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
L Earthing mat with GI flats of following sizes for risers with spikes as per design including all materials for comlete earthing of the substation suitable for 40KA for 1 sec short time current rating 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.1 40 mm MS rod for main earth mat(To be procured directly from SAIL/RINL/TATA or from their stockyard) MT 30 30 8 3 2 73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.2 75x12 mm G.I Flats for risers for equipments, columns and structures MT 10 10 6 3 2 31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.3 50x6 mm G.I flats for risers for all other equipments etc. MT 5 5 1.5 2 1 14.5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.4 Material for earthing pits with supply of all materials including base plate LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
M Sub- Station galvanized Steel structure (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design):- 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.1 Lattice structure with fasteners etc. (for Gantry ,tower,Beam) MT 30 30 12 12 7 91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
1.2 Standard structure for equipment support (other than CB ) MT 35 35 10 10 12 102 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
N Pipe Type structure (as per matching with existing System) MT 4 4 12 4 4 28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
i. Overhead shielding against lightning by galvanized steel wires and fittings as per requirement and design (matching with the GSS) (excluding lighting cum lightning mast) LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ii. Lightning cum Lighting masts with structure Sets. 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
R Sub- Station automation system (Suitable and integarted with existing system) comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) where ever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). Note :- Integration of SAS with SLDC patna/ERLDC with existing SCADA system in bidder scope in co-ordination with the AMC vendor of SCADA. 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
S Air conditioning for switchyard panel room (SPR) - 9m length with High wall type 5 star dual Invertor Split Air conditioner (BEE Complied) Units of 2 TR capacity with 5KVA stablizer and required accessories i.e. Power plug, socket, MCB, wires etc. (The quantity mentioned is tentative, which will be decided during detailed engineering based on heat load calculation) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
T Mandatory spares (L.S items break up of spares furnished separately as annexure) 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Note: (i) Where the tender quantity is shown above as ‘’LS’’ (Lump sum) or ‘’set’’, the corresponding break-up quantity is to be assessed by the bidder and indicated. (ii) Prices are firm and in any case price variation will not be considered.
(Tenderer shall quote prices for the following mentioned items. Prices of all accessories, assemblies, components, parts etc. associated with these items are included in tenderer's quoted prices for these items).
Price Break up for Construction of 10 nos. of 132 KV AIS Line Bays for 2nd source connectivity of GSS Ramnagar, Sherghati and Piro and residential quarter at GSS Ramnagar on Turnkey Basis
Name of Bidder & Address
Sl. No. Item Description SAC (Service Accounting Codes) Unit GSS Sherghati (02 Nos. line bay) GSS Chandauti (New) (02 Nos. line bay) GSS Piro (02 Nos. line bay) GSS Ramnagar (02 Nos. line bay) GSS Raxaul (New) (02 Nos. line bay) Total Qty. Unit Rate for Erection, Testing and Commissioning Charges (in Rs.) Total Price for Erection, Testing and Commissioning Charges (in Rs.) SGST (in %) CGST (in %) IGST (in %) Unit GST (Rs.) Total GST (Rs.) Unit Rate for Erection, Testing and Commissioning Charges including GST (in Rs.) Total Price for Erection, Testing and Commissioning Chargesincluding GST (in Rs.)
A 132 kV EQUIPMENT
1 Circuit breaker (3 phase)
i) 1600 A, 40 kA SF6 CB C2-M2-E2 class with support structure, marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) ( Spring- Spring mechanism). Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
2 ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm 0 0.00 0.00 0.00 0.00 0.00
i) 1600 A, 40 kA with one earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
ii) 1600 A, 40 kA without earth switch (Double break Isolator) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
iii) 1600 A, 40 kA without earth switch (Double break Isolator)(Tandem arrangement) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
iv) 2500 A, 40 kA without earth switch (Double break high level beam mounted Isolator) Nos. 1 1 2 2 2 8 0.00 0.00 0.00 0.00 0.00
3 Current Transformers 5 core (1 phase) (the winding of CT shall be of copper only) 0 0.00 0.00 0.00 0.00 0.00
i) 1200 -600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,31.5 kA with 120% extended current rating with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
4 8800 pF CVTs (1 phase) with marshalling boxes, terminal connectors etc . (The winding of CVT shall be of copper only) Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
5 120 kV Surge arresters class-IV (SH Class) ( 1 phase) with marshalling boxes, terminal connectors etc. Nos. 6 6 6 6 6 30 0.00 0.00 0.00 0.00 0.00
6 Portable Discharge Rod Nos. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
B ERECTION HARDWARE (132 kV) 0 0.00 0.00 0.00 0.00 0.00
1.1 Insulator (Porcelain long rod insulators-120kN), antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, connectors suitable for twin moose & quad moose (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.) 0 0.00 0.00 0.00 0.00 0.00
132 KV, Main Bus & Transfer Bus complete work including all items 0 0.00 0.00 0.00 0.00 0.00
1.2 132 kV Solid Core, Bus post Insulators for erection hardware Nos. 20 20 16 20 14 90 0.00 0.00 0.00 0.00 0.00
1.4 Bus extension for two bays Set 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
C LT Switchgear 0 0.00 0.00 0.00 0.00 0.00
1.1 415 V ACDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 3 (three)sources of AC Power from 2 SST's & Diesel Generator(DG). Also provisions to be made for use of either source of power from SST & DG or both sources of power from SST at a time with provision of electro-mechanical interlock. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
1.4 220 V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel shall be done individually for each CRP. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
1.5 48V DCDB (no of feeders shall be as per the requirement of the project plus 50% extra feeders) shall be suitable for 2 sources of DC Power from Battery Banks/chargers and provisions to be made for use of either source of power or both sources of power at a time with provision of electro-mechanical interlock. Wiring from DCDB to CR Panel/ Communication Panels shall be done individually for each CRP/ Communication Panels. Set 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
D CONTROL & RELAY PANELS 0 0.00 0.00 0.00 0.00 0.00
Control, Relay & Protection Panel for all indicating meters and multi function meters shall be communicable types with 0.5 class accuracy. 1 bay control unit with bay mimic to be provide separately in control panel. 0 0.00 0.00 0.00 0.00 0.00
a) 132 KV line (with A/R) with numerical distance protection relays (with the features of load blender and PRP) and earth fault / overcurrent relays complying to IEC 61850 Protocal with optical fiber ports sufficient DI/DO for scheme with additional 6 DI/DO for spare with under frequency Relay. All indicating meters/ multifunctions meters shall be communicable tpe with 0.5 class accuracy and 0.2 S class ABT energy meter (with modem) to be provided. (relay shall have feature of PRP and load blinder) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
b) Provision for Supply and extension of Bus Bar protection scheme for 02 nos. new bays and integration with existing bus bar protection panel. The scheme should be compatible with make and type (Centralised/distributed) of existing bus bar protection scheme at GSS (Bus Bar protection should be low impedence and will have 04 zones with numerical type of relays complying IEC 61850 (edition 2) protocol as where applicable with complete cabling works. Sets. 0 1 0 0 1 2 0.00 0.00 0.00 0.00 0.00
c) Digital Protection Coupler suitable for integration and operation through OPGW System with required cables, complete in all respect i.e connectivity and matching with remote end. Work for remote end comprising dismantelling, shifting, erection & commissioningis in the scope of bidder. Sets. 4 4 4 4 4 20 0.00 0.00 0.00 0.00 0.00
G FIRE PROTECTION SYSTEM 0 0.00 0.00 0.00 0.00 0.00
1.1 Portable Fire Extinguishers 0 0.00 0.00 0.00 0.00 0.00
d 12 Fire buckets with covered stands Nos. 2 2 2 2 4 12 0.00 0.00 0.00 0.00 0.00
a Heavy duty PVC conduits as of 20/25/32 mm size complete with all accessories for point wiring for Light points, Fans power points 5/15 amps. With 2.5 sq.mm/4 mm2/6.0 mm2 copper for circuit wiring and 1.5 mm2 copper earth wire PVC insulated in green color including wiring for submains i.e. wiring from Lighting panel to switch board. LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
b Wiring from lighting panel to switch boards, from switchboard to junction boxes for light points with 2.5/4.0/6.0 mm2 copper wire as per technical specification, complete in all respect. 1.5 mm2 copper wire (green) will be used for earthing inside conduits LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
I Telephone sockets 0 0.00 0.00 0.00 0.00 0.00
a Single socket outlet comprising RJ-11 socket Nos. 5 5 5 5 5 25 0.00 0.00 0.00 0.00 0.00
b Dual socket outlet comprising RJ-45 socket Nos. 3 3 3 3 3 15 0.00 0.00 0.00 0.00 0.00
J ILLUMINATION SYSTEM (The quantities mentioned below is tentative for tendering purposes and the final quantities will be decided during detailed engineering based upon lux level calculations) 0 0.00 0.00 0.00 0.00 0.00
1.a Lighting Panel (Outdoor) Type ACP-2 Nos. 1 1 1 1 2 6 0.00 0.00 0.00 0.00 0.00
1.a Lighting Panel (Outdoor) Type ACP-3 Nos. 1 1 1 1 2 6 0.00 0.00 0.00 0.00 0.00
2 LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements) 0 0.00 0.00 0.00 0.00 0.00
b Supply of Complete fitting of LED Flood Lighting Luminairs (<250 Watt) having minimum System Lumen Output of 23000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00
c Supply of Complete fitting of LED Flood Lighting Luminairs (<530 Watt) having minimum System Lumen Output of 60000 with all accessories Conforming to IP:65 Nos. 1 1 2 4 4 12 0.00 0.00 0.00 0.00 0.00
d Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear Nos. 4 4 2 1 4 15 0.00 0.00 0.00 0.00 0.00
e Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
f Lighting fixture Type-MP: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
g Lighting fixture Type- SC: as per Tech. Specification Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
h 15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
i 63A, 415V: Interlocked switch socket outdoor receptacles (Type RP) Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
j Lighting Poles Type A1 Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
k Lighting Poles Type E1 Nos. 0 0 2 2 2 6 0.00 0.00 0.00 0.00 0.00
K Cables alongwith associated accessories like clamps, glands, lugs and straight joints, Feruls, Tagging etc. 0 0.00 0.00 0.00 0.00 0.00
i Any other size as per requirement KM 0 0.00 0.00 0.00 0.00 0.00
L Earthing mat with GI flats of following sizes for risers with spikes as per design including all materials for comlete earthing of the substation suitable for 40KA for 1 sec short time current rating 0 0.00 0.00 0.00 0.00 0.00
1.1 40 mm MS rod for main earth mat(To be procured directly from SAIL/RINL/TATA or from their stockyard) MT 30 30 8 3 2 73 0.00 0.00 0.00 0.00 0.00
1.2 75x12 mm G.I Flats for risers for equipments, columns and structures MT 10 10 6 3 2 31 0.00 0.00 0.00 0.00 0.00
1.3 50x6 mm G.I flats for risers for all other equipments etc. MT 5 5 1.5 2 1 14.5 0.00 0.00 0.00 0.00 0.00
1.4 Material for earthing pits with supply of all materials including base plate LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
i Treated earthpit set 2 2 6 4 4 18 0.00 0.00 0.00 0.00 0.00
ii Untreated earthpit set 8 8 6 8 8 38 0.00 0.00 0.00 0.00 0.00
M Sub- Station galvanized Steel structure (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design):- 0 0.00 0.00 0.00 0.00 0.00
1.1 Lattice structure with fasteners etc. (for Gantry ,tower,Beam) MT 30 30 12 12 7 91 0.00 0.00 0.00 0.00 0.00
1.2 Standard structure for equipment support (other than CB ) MT 35 35 10 10 12 102 0.00 0.00 0.00 0.00 0.00
N Pipe Type structure (as per matching with existing System) MT 4 4 12 4 4 28 0.00 0.00 0.00 0.00 0.00
P Overhead shielding 0 0.00 0.00 0.00 0.00 0.00
i. Overhead shielding against lightning by galvanized steel wires and fittings as per requirement and design (matching with the GSS) (excluding lighting cum lightning mast) LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
ii. Lightning cum Lighting masts with structure Sets. 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
Q Integration of the newly constructed line bay in the existing RTU and control centres (Main, back up) including supply, installation and commissioning of required quantity of MFM, cables, CMR & all required accessories hardware in cordination with concerned OEM of RTU LS 1 1 1 1 1 5 0.00 0.00 0.00 0.00 0.00
R Sub- Station automation system (Suitable and integarted with existing system) comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) where ever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). Note :- Integration of SAS with SLDC patna/ERLDC with existing SCADA system in bidder scope in co-ordination with the AMC vendor of SCADA. 0 0.00 0.00 0.00 0.00 0.00
T Air conditioning for switchyard panel room (SPR) - 9m length with High wall type 5 star dual Invertor Split Air conditioner (BEE Complied) Units of 2 TR capacity with 5KVA stablizer and required accessories i.e. Power plug, socket, MCB, wires etc. (The quantity mentioned is tentative, which will be decided during detailed engineering based on heat load calculation) Nos. 2 2 2 2 2 10 0.00 0.00 0.00 0.00 0.00
Note: (i) Where the tender quantity is shown above as ‘’LS’’ (Lump sum) or ‘’set’’, the corresponding break-up quantity is to be assessed by the bidder and indicated. (ii) Prices are firm and in any case price variation will not be considered.
(Tenderer shall quote prices for the following mentioned items. Prices of all accessories, assemblies, components, parts etc. associated with these items are included in tenderer's quoted prices for these items).
Price Break up for Construction of 10 nos. of 132 KV AIS Line Bays for 2nd source connectivity of GSS Ramnagar, Sherghati and Piro and residential quarter at GSS Ramnagar on Turnkey Basis
Name of Bidder & Address
Sl. No. Item Description SAC (Service Accounting Codes) Unit GSS Sherghati (02 Nos. line bay) GSS Chandauti (New) (02 Nos. line bay) GSS Piro (02 Nos. line bay) GSS Ramnagar (02 Nos. line bay) including Residential quarter GSS Raxaul (New) (02 Nos. line bay) Total Qty. Unit Price without GST (in Rs.) Total Price without GST(in Rs.) SGST (in %) CGST (in %) IGST (in %) Unit GST (Rs.) Total GST (Rs.) Unit Price including GST (in Rs.) Total Price including GST (in Rs.)
1 Supplying and Filling in plinth with local sand and under floors including,watering, ramming consolidating and dressing complete. cum 142.6125 12.67875 14.4 121.0125 0 290.70375 0.00 0.00 0.00 0.00 0.00
2 Demolishing cement concrete including disposal of material-1:3:6 or richer mix cum 0 0 28.12 0 0 28.12 0.00 0.00 0.00 0.00 0.00
3 Demolishing cement concrete including disposal of material 1:4:8 or leaner mix Dismentling of BBCC cum 0 0 0 0 38.365 38.365 0.00 0.00 0.00 0.00 0.00
4 Dismantling expanded metal or R.R.C. fabrics with necessarybattens and beading including stacking the serviceable material within 50 metres lead. sqm 0 0 180 0 0 180 0.00 0.00 0.00 0.00 0.00
5 Boring, Providing and installing cast in situ single under reamed piles of specified diameter and lengthbelow pile cap in M-25 ementconcrete, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and the length of the pile to be embedded in pile cap etc. all complete. (Length of pile for payment shall be measured upto to the bottom of pile cap) 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
6 Demolishing R.C.C. work including stacking of steel bars and disposal of unserviceable material withing 50 metres lead: m3 0 0 18.75 0 0 18.75 0.00 0.00 0.00 0.00 0.00
7 Earth work in excavation for all depth & size and neatly dressed : all kinds of soil sqm 3167.27 1375.59 1064.82 2745.45 905.1 9258.23 0.00 0.00 0.00 0.00 0.00
8 Excavating, supplying and filling of local earth (including royalty butexcluding cairriage cost) by mechanical transport including ramming and watering of the earth in layers not exceeding 20 cm in trenches, plinth, sides of foundation etc. complete. cum 0 4069.14075 396 0 0 4465.14075 0.00 0.00 0.00 0.00 0.00
9 Providing and laying in position cement concrete of specified grade exluding the cost of centring and shuttering-all work upto plinth level. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i 1.2.4 (1 Cement :2 coarse sand :4 graded stone agregate 20 mm nominal size) m3 20.739125 23 3.37 0 0 47.109125 0.00 0.00 0.00 0.00 0.00
ii 1.3.6 (1 Cement :3 coarse sand :6 graded stone agregate 20 mm nominal size) m3 0 0 69.81 25.47225 23.4325 118.71475 0.00 0.00 0.00 0.00 0.00
iii 1.4.8 (1 Cement :4 coarse sand :8 graded stone agregate 40 mm nominal size) m3 187.0875 40.8935625 132 193.15 0 553.1310625 0.00 0.00 0.00 0.00 0.00
iv 1.1.5.3 (1 Cement :1.5 coarse sand :3 graded stone agregate 20 mm nominal size) m3 0 0 0 0.26875 0.386 0.65475 0.00 0.00 0.00 0.00 0.00
10 Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
ii Thermo-Mechanically Treated bars TMTC-500 - 10mm dia. Kg 46119.288 3260.46 4764.35 27067.786 453.2448 81665.1288 0.00 0.00 0.00 0.00 0.00
iii Thermo-Mechanically Treated bars TMTC-500 - 12mm dia. Kg 39486.494 4143.3372 1595.38 16843.054 4768.72 66836.9852 0.00 0.00 0.00 0.00 0.00
iv Thermo-Mechanically Treated bars TMT Fe-500-16mrn dia. Kg 2013.552 2141.11048 180.5 66884.69 0 71219.85248 0.00 0.00 0.00 0.00 0.00
vi Thermo-Mechanically Treated bars TMT Fe-500-25mrn dia. Kg 0 0 2256.7104 2463.134 332.5168 5052.3612 0.00 0.00 0.00 0.00 0.00
12 filled with a grout of 12 mm thick cement mortar 1:3 (1 Cement : 3 coarse sand) and jointed with Cement mortar 1:2 (1 cement : 2 stone dust), including rubbing and polishing complete. (To be secured to the backing and the sides by means of cramps and pins which shall be paid for separately) 25 mm thick sqm 0 0 35.165 0 0 35.165 0.00 0.00 0.00 0.00 0.00
13 Centring and shuttering including strutting,propping etc. and removal of form for. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i Foundations, footings, bases of columns etc. for mass concrete. m2 5091.12 811.43 150.28 375.73 144.6 6573.16 0.00 0.00 0.00 0.00 0.00
ii Columns,Pillars, Piers, Abutments, Posts and Struts m2 311.6 623.12 571.93 1881.68 629.6 4017.93 0.00 0.00 0.00 0.00 0.00
iii Walls (any thickness) including attached pilasters. Butteresses, plinth and string courses etc. m2 0 0 100.8 260.6 73.5 434.9 0.00 0.00 0.00 0.00 0.00
iv Suspended floors, roofs, landings, balconies and access platform with water proofply 12 mm thick. m2 0 31.3 24 2537.62 0 2592.92 0.00 0.00 0.00 0.00 0.00
v Lintels, beams, plinth bams, griders, bressumers and contilevers. m2 0 43.11 45 2414.02 0 2502.13 0.00 0.00 0.00 0.00 0.00
vi Weather shade,Chajjas, corbels etc. including edges m2 0 0 0 65.75 0 65.75 0.00 0.00 0.00 0.00 0.00
vii Stairs,(excluding landings) except spiral-staircaces. m2 0 0 0 10.5 0 10.5 0.00 0.00 0.00 0.00 0.00
14 Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring,shuttering,finishing and reinforcement-All work upto plinth level 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i 1:1:2(1 cement: 1 coarse sand:2 graded stone aggregate 20 mm nominal size) m3 0 0 133.42 0 0 133.42 0.00 0.00 0.00 0.00 0.00
ii 1:1:5:3(1 cement: 1.5 coarse sand:3 graded stone aggregate 20 mm nominal size) m3 1205.8375 223.55175 53.56 128.873 161.5875 1773.40975 0.00 0.00 0.00 0.00 0.00
15 Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cementcontent as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and including retard setting of concrete, improve workability without impairing strength andadmixtures in recommended proportions as per IS: 9103 to accelerate, reinforcement,durability as per direction of Engineer-in charge. Note:- Cement content considered in this item is @ 330 kg/ cum. Excess or less cement used as per design mix is payable or recoverable separately (Upto plinth level). m3 0 0 0 458.29 0 458.29 0.00 0.00 0.00 0.00 0.00
16 Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix,including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and including retard setting of concrete, improve workability without impairing strength and admixtures in recommended proportions as per IS: 9103 to accelerate,reinforcement,durability as per direction of Engineer-incharge.Note:- Cement content considered in this item is @ 340 kg/cum. Excess or less cement used as per design mix is payable or recoverable separately (Above Plinth level). m3 0 0 0 630.26 0 630.26 0.00 0.00 0.00 0.00 0.00
17 Reinforced cement concrete work in wall (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts, etc. upt floor five level excluding cost of centring, shuttering, finishin and reinforcement.1:1:5:3(1 cement: 1.5 coarse sand:3 graded stone aggregate 20mm nominal size) cum 0 1.84 0 3.63 0 5.47 0.00 0.00 0.00 0.00 0.00
18 Reinforced cement conrete work in beams,suspended floors, roofs having slope upto 15, landings,balconiec, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto floor five level excludingthe cost of centring, shuttering, finishing and reinforement with 1:1.5:3(1 cement:1.5 coarse sand:3 graded stone aggregate 20 mm nominal size). cum 0 4.92 0 0 0 4.92 0.00 0.00 0.00 0.00 0.00
19 Supplying and fixing of MS Angle ( 50 X 50 X 6 ) mm in proper shape is required as per direction of E/I Kg 0 0 422.15 2685.56 162 3269.71 0.00 0.00 0.00 0.00 0.00
20 Supplying and fixing of MS Flate upto 10mm Thickness in proper shape is required as per direction of E/I Kg 0 0 0 566.664 28.776 595.44 0.00 0.00 0.00 0.00 0.00
21 MS flats (75*6) mm with welding in proper shape as required as per direction of E/I Kg 0 0 0 0 77.704 77.704 0.00 0.00 0.00 0.00 0.00
22 Labour for cutting of M.S. angle iron post to required length, one end splitted as fish tailed in a length of 150mm complete as per building specification and direction of E/l. Each 0 0 31 196 0 227 0.00 0.00 0.00 0.00 0.00
23 Welding by electric plant including of transportation of electric welding at site etc complete as per direction of E/I cm 0 0 0 1960 0 1960 0.00 0.00 0.00 0.00 0.00
24 Applying priming coat:With ready mixed zinc chromate yellow primer of approved brand and manufacture on steel galvanized iron/steel works m2 0 0 0 251.98 0 251.98 0.00 0.00 0.00 0.00 0.00
25 Painting with ready mixed paint of approved brand and manufacture in all shades to give an even shade:New steel work (two or more coats) m2 137.24685 595.3128 0 251.98 0 984.53965 0.00 0.00 0.00 0.00 0.00
26 Providing 250mm wide brick drain in cement mortar (1:6) with av. 150mm. Clear depth and 250mm apron including cost of E/W. involved with 75mm cement concrete (1:4:8) over one brick designation 100-A flat soling in proper grade and slope at the base.the drain duly. plastered in CM. (1:3) with punning over exposed surface all complete as per building specification and direction of E/l, m 0 0 90 0 0 90 0.00 0.00 0.00 0.00 0.00
27 Providing and laying damp-proof Course 50 mm thick with cement concrete 1:2:4(1cement:2:2 coarse sand :4 graded stone aggregate 20mm nominal size) m2 0 4.5 0 0 0 4.5 0.00 0.00 0.00 0.00 0.00
28 Cement plaster in course sand: 12 mm cement plaster of mix 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
29 20 mm cement plaster of mix1:6(1 cement: 6 coarse sand) m2 0 0 1500 0 0 1500 0.00 0.00 0.00 0.00 0.00
30 15 mm cement plaster on rough side of single or half brick wall of mix.1:6 (1 cement: 6 coarse sand) m2 0 0 0 4259.54 0 4259.54 0.00 0.00 0.00 0.00 0.00
31 6 mm cement plaster to ceiling of mix1:4(1 cement: 4 coarse sand) m2 0 31.38 0 2502.18 0 2533.56 0.00 0.00 0.00 0.00 0.00
32 18 mm cement plaster in two coat under layer 12 mm thick cement plaster 1:5 (1 cement: 5 course sand) and a top layer 6mm thick cement plaster 1:3(1 cement: 3 coarse sand finiished rough with sponge m3 0 67.56 0 0 0 67.56 0.00 0.00 0.00 0.00 0.00
33 Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. m2 0 73.44 0 10179.84 0 10253.28 0.00 0.00 0.00 0.00 0.00
34 Applying one coat of cement primer of approved brand and manufacture on wall surface:Cement primer m2 0 0 0 162 0 162 0.00 0.00 0.00 0.00 0.00
35 Finishing walls with water proofing cement paint of approved brand and manufacture and of required shade to give an even shade.New work (three or more coats) m2 0 88.4 0 162 0 250.4 0.00 0.00 0.00 0.00 0.00
36 Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications.Two or more coats applied on walls @ 1.25 ltr/10 sqm over and including one coat of special primer applied @ 0.75 ltr /10 sqm. m2 0 52.92 0 0 0 52.92 0.00 0.00 0.00 0.00 0.00
37 Distempering with 1st quality acrylic distemper, having VOC (Volatile Organic Compound ) content less than 50 grams/ litre, of approved brand and manufacture,including applying additional coats wherever required, to achieve even shade and colour.- 2 coats including Applying one coat of distemper primer of approved brand and manufacture on wall surface: m2 0 0 0 7846.3 0 7846.3 0.00 0.00 0.00 0.00 0.00
38 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade :New work (Two or more coat applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) m2 0 67.56 0 2333 0 2400.56 0.00 0.00 0.00 0.00 0.00
39 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture m2 0 0 0 456.12 0 456.12 0.00 0.00 0.00 0.00 0.00
40 Ready mixed pink or grey primer of approved brand and manufacture on wood work (hard and softwood) m2 0 0 0 456.12 0 456.12 0.00 0.00 0.00 0.00 0.00
41 Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C. kitchen and the like consisting of: (i) 1st course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming tc IS 2645 in recommended proportions.(ii) 11 nd course of 20 mm cement plaster 1:3 (1 cement:3 coarse sand)mixed with water proofing compound in recommended proportion, (iii) Illrd course of applying blown or/residual bitumen aplied hot at 1.7 kg. per sqm of area, (iv) Ivth course of 400 micron thick PVC sheet.(Overlaps at joints of PVC shet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/sqni). m2 0 0 0 124.42 0 124.42 0.00 0.00 0.00 0.00 0.00
42 Providing and laying integral cement based water proofing treatment including prepatation of surface as required for treatment of roofs,balconies , terraces etc, consisting of following operations. (a) Applying and grouting a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with proprietary water -proofing compound cleaning the surface before treatment, (b) Laying cement concrete using broken bricks / brick bats 25 mm to 100 mm size with 50 % of cement mortar 1:5 (1 cement: 5 coarse sand ) admixed with proprietary water proofing compound conforming to IS : 2645 over 20 mm thick layer of cement mortar of mix 1:5 (1 cement: 5 coarse sand ) admixed with proprietary water froofing compound conforming to IS 2545 to reuired slope and treating similary the adjoining walls upto 300 mm height including rounding of junctions, or walls ad slabs. (c) After two days of proper curing applying a secoung coat of cement slurry admixed with proprietary water proofing compound conforming to IS : 2645. (d)Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement: 4 coarse sand ) admixed with proprietary water proofing compound conforming to IS : 2645 and finally finishing the surface with trowel with neat cement slurry and making of 300 x 300 mm square. (e)The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test, All above operations to be done in order and as directed and specifed by the Engineer-in-Charge.With average thickness of 120 mm and minimum thickness at khurras point to be 65 m2 0 0 0 792.25 0 792.25 0.00 0.00 0.00 0.00 0.00
43 Providing and laying Vitrified tiles in floor in different sizes {thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only.Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily.Size of Tile 600 x 600 mm m2 0 10.35 0 0 0 10.35 0.00 0.00 0.00 0.00 0.00
44 Providing and laying Vitrified tiles in floor, size of Tile 600 x 600 mm.(thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622 , of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). m2 0 0 0 1370.16 0 1370.16 0.00 0.00 0.00 0.00 0.00
45 Providing and laying Ceramic glazed floor tiles 300x300 mm (thickness sqm 799.40 to be specified by the manufacturer) of ist quality conforming to IS :15622 of approved make in colours such as white , Ivory , Grey , Fume Red , Brown, laid on 20 mm thick Cement motar 1:4 (1 cement: 4 coarse sand) including pointing the joints with white cement and matching pigment etc., complete. m2 0 0 0 103.29 0 103.29 0.00 0.00 0.00 0.00 0.00
46 Providing and fixing 1st quality ceramic glazed wall tiles conforming to IS : 15622 (Thickness to be specified by the manufacture) of approved make in all colours, shades except burgundy , bottle green , black of any size as approved by Engineer-in-charge in skirting , risers of steps and dados over 12 mm thick bed of cement Motar 1:3(1 cement: 3 coarse sand ) and jointing with grey cement slurry @ 3.3 kg per sqm including pointing in white cement mixed with pigment of matching shade complete. m2 0 0 0 565.92 0 565.92 0.00 0.00 0.00 0.00 0.00
47 Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size,approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4coarse sand), joints treated with white cement,mixed with matching pigment, epoxy touch ups,including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. m2 0 0 0 202.44 0 202.44 0.00 0.00 0.00 0.00 0.00
48 Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M -30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.. m2 0 0 0 213.8 0 213.8 0.00 0.00 0.00 0.00 0.00
49 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285,For fixed portion 21.1.1.1 Anodised aluminium (anodised transparent or dyed to required shade accordingto IS: 1868, Minimum anodic coating of grade AC 15) Kg 0 7.01 0 0 0 7.01 0.00 0.00 0.00 0.00 0.00
50 For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) 21.1.2.1 Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15) Kg 0 9.38 0 0 0 9.38 0.00 0.00 0.00 0.00 0.00
51 Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length ( hold fast lugs or dash fastener shall be paid for separately). cum 0 0 0 2.167 0 2.167 0.00 0.00 0.00 0.00 0.00
52 Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1 st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces ofshutters. 35 mm thick including stainless steel butt hinges with necessary screws including Providing & Fixing decorative high pressure laminated sheet of plain / wood grain in gloss / matt / suede finish with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. 1 mm thick. Shutter for Main door & External doors sqm 0 0 0 138.99 0 138.99 0.00 0.00 0.00 0.00 0.00
53 Providing and fixing factory made uPVC white colour casement/ casement cum fixed glazed windows comprising of uPVC multichambered frame, sash and mullion (where ever required) extruded profiles duly reinforced with 1.60 ± 0.2 mm thick galvanized mild steel section made from roll forming process of required length (shape & size according to uPVC profile), uPVC extruded glazing beads of appropriate dimension, EPDM gasket, stainless steel (SS 304 grade) friction hinges, zinc alloy (white powder coated) casement handles, G.I fasteners 100 x 8 mm size for fixing frame to finished wall, plastic packers, plastic caps and necessary stainless steel screws etc. Profileof frame & sash shall be mitred cut and fusion welded at all corners, mullion (if required) shall be also fusion welded including drilling of holes for fixing hardware's and drainage of water etc. After fixing frame the gap between frame and adjacent finished wall shall be filled with weather proof silicon sealant over backer rod of required size and of approved quality, all complete as per approved drawing & direction of Engineer-in-Charge. (Single / double glass panes and silicon sealant shall be paid separately) Note: For uPVC frame, sash and mullion extruded profiles minus 5% tolerance. Casement window double panels with S.S. friction hinges (300 x 19 x 1.9 mm) made of (small series) frame 47 x 50 mm, sash 47 x 68 mm & mullion 47 x 68 mm all having wall thickness of 1.9 ± 0.2 mm and single glazing bead of appropriate dimension. (Area of window above 0.75 sqm upto 1.50 sqm). sqm 0 0 0 114.745 0 114.745 0.00 0.00 0.00 0.00 0.00
54 30 mm thick factory made Polyvinyl Chloride (PVC) door shutter made of styles and rails of a uPVC hollow section of size 60x30 mm and wall thickness 2 mm (± 0.2 mm),with inbuilt decorative moulding edging on one side. The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 25x20 mm and 1 mm (± 0.1 mm) wall thickness. The lock rail made up of ‘H’ section, a uPVC hollow section of size 100x30 mm and 2 mm (± 0.2 mm) wall thickness fixed to the shutter styles by means of plastic/ galvanised M.S. ‘U’ cleats. The shutter frame filled with a uPVC multi-chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (± 0.1 mm) wall thickness .The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer’s specification and direction of Engineer-incharge. sqm 0 0 0 48.805 0 48.805 0.00 0.00 0.00 0.00 0.00
55 Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete Fixed to openings/ wooden frames with rawl plugs screws etc. Kg 0 0 0 1695 0 1695 0.00 0.00 0.00 0.00 0.00
56 Providing and fixing 900mm high S.S.304 Grade Stainless steel railing with 40mm diameter and 1.5mm thick at top,40mm diameter and 1.5mm thick vertical supports spaced at 1.5m center to center and 8mm thick toughened glass including fabricating ,fixtures, errecting , necessary welding , grinding , finishing, buffing to stainless steel pipe etc. complete.** Spec. No.: As directed by Engineer Incharge Kg 0 0 0 2398 0 2398 0.00 0.00 0.00 0.00 0.00
57 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes,having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.Concealed work, including cutting chases and making good the walls etc. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
58 Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by Municipal Board complete with bolts,nuts,rubber insertions etc. (The tail pieces if required will be paid separately) : each 0 0 0 2 0 2 0.00 0.00 0.00 0.00 0.00
59 Providing and fixing brass bib cock of approved quality 15 mm nominal bore each 0 0 0 36 0 36 0.00 0.00 0.00 0.00 0.00
60 Providing and fixing brass stop cock of approved quality 15 mm nominal bore each 0 0 0 103 0 103 0.00 0.00 0.00 0.00 0.00
61 Providing and fixing 25mm dia gun metal gate valve with C.I. wheel of approved quality (screwed end) : each 0 0 0 27 0 27 0.00 0.00 0.00 0.00 0.00
62 Providing and fixing 50mm dia gun metal gate valve with C.I. wheel of approved quality (screwed end) : each 0 0 0 6 0 6 0.00 0.00 0.00 0.00 0.00
63 Providing and fixing 15mm dia ball valve (brass) of approved quality, High or low pressure, with plastic floats complete : each 0 0 0 95 0 95 0.00 0.00 0.00 0.00 0.00
64 Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I.brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete,including painting of fittings and brackets, cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid each 0 0 0 15 0 15 0.00 0.00 0.00 0.00 0.00
65 Providing and fixing water closet squatting pan (Indian type W.C.pan) with 100 mm sand cast Iron P or S trap, 10 litre low fixtures complete, including cutting and making good the walls andlevel white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and floors wherever required :White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests each 0 0 15 0 15 0.00 0.00 0.00 0.00 0.00
66 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require White Vitreous China Wash basin size 550x400 mm with a pair of 15 mm C.P. brass pillar taps each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
67 Providing and fixing square-mouth S.W. gully trap class SP-1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300 x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design :150 x 100 mm size P type With sewer bricks conforming to IS : 4885 each 0 0 0 6 0 6 0.00 0.00 0.00 0.00 0.00
68 Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors :100 mm inlet and 75 mm outlet Sand Cast Iron S&S as per IS- 1729 each 0 0 0 103 0 103 0.00 0.00 0.00 0.00 0.00
69 Constructing brick masonry chamber for underground C.I.inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg),R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design :With common burnt clay F.P.S. (non modular) bricks of class designation 7.5 Inside dimensions 600x 850 mm and 45 cm deep for pipe line with three or more inlets : each 0 0 0 49 0 49 0.00 0.00 0.00 0.00 0.00
70 Providing and fixing soil, waste and vent pipes :Sand cast iron S&S pipe as per IS: 1729 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
71 Providing and fixing on wall face unplastidsed-75mm dia PVC(working pressure 4 kgf per sqm) rain water pipes conforming to IS :4985 including jointing with seal ring conforming to IS: 5382 leaving 10 mm gap for thermal expansion. m 0 0 0 185 0 185 0.00 0.00 0.00 0.00 0.00
72 Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet :100 mm dia each 0 0 0 55 0 55 0.00 0.00 0.00 0.00 0.00
73 Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per IS : 13983 with C.I. brackets and stainless steel plug 40 mm,including painting of fittings and brackets, cutting and making good the walls wherever required :Kitchen sink with drain board 510x1040 mm bowl depth 250 mm each 0 0 0 17 0 17 0.00 0.00 0.00 0.00 0.00
74 Providing and fixing C.P. brass long body bib cock 15mm nominal boreof approved quality conforming to IS standards and weighing not less than 690 gms. each 0 0 0 18 0 18 0.00 0.00 0.00 0.00 0.00
75 Providing and fixing gun metal non- return valve of approved quality (screwed end) : 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i Horizontal type each 0 0 0 4 0 4 0.00 0.00 0.00 0.00 0.00
ii Vertical type each 0 0 0 4 0 4 0.00 0.00 0.00 0.00 0.00
76 Providing and fixing C.P. brass angle valve 15mm nominal bore for basin mixer and geyser points of approved quality conforming to IS:8931 a) 15 mm nominal bore each 0 0 0 154 0 154 0.00 0.00 0.00 0.00 0.00
77 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. Litre 0 0 0 15000 0 15000 0.00 0.00 0.00 0.00 0.00
78 S/F/F 1 H.P. Cromption or any other apprioved make Motor and ISI make automatic starter mounted on a common wooden board etc. all complete job. each 0 0 0 3 0 3 0.00 0.00 0.00 0.00 0.00
79 Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications,drawings and direction of Engineer-in-charge complete. sqm 0 3.36 0 0 0 3.36 0.00 0.00 0.00 0.00 0.00
80 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors,embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete asper the direction of Engineer-in-charge.With stainless steel cover plate minimum 1.25 mm thickness Each 0 2 0 0 0 2 0.00 0.00 0.00 0.00 0.00
81 Providing and fixing aluminium tubular handle bar 32 mm outer dia,3.0 mm thick & 2100 mm long with SS screws etc .complete as per direction of Engineer-in-Charge.Anodized (AC 15 ) aluminium tubular handle bar Each 0 4 0 0 0 4 0.00 0.00 0.00 0.00 0.00
82 Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete. Each 0 4 0 0 0 4 0.00 0.00 0.00 0.00 0.00
83 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness(weight not less than 10kg/sqm) sqm 0 4.68 0 0 0 4.68 0.00 0.00 0.00 0.00 0.00
84 Providing and fixing on wall face UPVC (working pressure 4 kgf per sqm) rain water pipes confirming to IS:4985 including jointing with seal…………etc.(a) 110mm dia Meter 0 12 0 0 0 12 0.00 0.00 0.00 0.00 0.00
85 Providing and fixing on wall face UPVC moulded fittings/accessories for UPVC rain water pipes confirming to IS:4985 including jointing with seal…………etc.(a) 110mm dia Bend Each 0 4 0 0 0 4 0.00 0.00 0.00 0.00 0.00
86 Providing and fixing on wall face UPVC moulded fittings/accessories for UPVC rain water pipes confirming to IS:4985 including jointing with seal…………etc(b) 110mm dia Shoe Each 0 4 0 0 0 4 0.00 0.00 0.00 0.00 0.00
87 Surface dressing of the ground including removing vegetation and inequalities not exceeding 15 cm deep and disposal of rubbish with all lifts and leads.All kinds of soil Sqm 1398.61 0 1500 1312 0 4210.61 0.00 0.00 0.00 0.00 0.00
88 Antiweeds treatment in switch yard area as per building specification and direction of E/I m2 0 0 1500 0 0 1500 0.00 0.00 0.00 0.00 0.00
89 Providing designation 100 A one brick flat soling joints filled with local sand including cost of watering, taxes, royalty all complete as per building specification and direction of E/l sqm 0 27.3 108.648 786.2958 0 922.2438 0.00 0.00 0.00 0.00 0.00
90 Providing designation 100 A one brick on edge soling joints filled with local sand including cost of watering, taxes, royalty all complete as per building specification and direction of E/l, sqm 0 0 96 0 0 96 0.00 0.00 0.00 0.00 0.00
91 Brick work with fly ash bricks as per IS 12894(2002) & IS 3495 in foundations and plinth in Cement mortar 1.:4 (1 cement: 4 coarse sand ) cum 0 0 0 116.721 0 116.721 0.00 0.00 0.00 0.00 0.00
92 Brick work with fly ash bricks as per IS 12894(2002) & IS 3495tor Brick work in superstructure above plinth level upto floor V in Cement mortar 1.:4 (1 cement: 4 coarse sand ) cum 0 0 0 525.664 0 525.664 0.00 0.00 0.00 0.00 0.00
93 Brick work with bricks of class designation 100A in foundations and plinth in : Cement mortar 1 .:6 (1 cement: 6 coarse sand ) cum 0 34.79 6.17 8.0625 0 49.0225 0.00 0.00 0.00 0.00 0.00
94 Extra for Brick work in superstructure above plinth level upto floor V cum 0 27.89 0 0 0 27.89 0.00 0.00 0.00 0.00 0.00
95 Providing and laying in position cement concrete of specified grade exluding the cost of centring and shuttering-all work upto plinth level.BCC- 1:5:10 (1 Cement: 5 coarse sand : 10 brick aggregate 40 mm nominal size)(100mm Thk) including neat cement slurry on top. m3 139.861 174 150 131.2 30.6065 625.6675 0.00 0.00 0.00 0.00 0.00
96 Stone aggregate (single size) 40 mm turn nominal size m3 139.861 175.74 225 131.2 0 671.801 0.00 0.00 0.00 0.00 0.00
97 Grading- I (Using Screening Crushable type such as Moorum or Gravel) Using Screening Crushable type such as Moorum or Gravel (with Vibratory Roller) cum 0 0 30 0 0 30 0.00 0.00 0.00 0.00 0.00
98 Grading- II (Using Screening Crushable type such as Moorum or Gravel) Using Screening Crushable type such as Moorum or Gravel (with Vibratory Roller) cum 0 0 60 0 0 60 0.00 0.00 0.00 0.00 0.00
99 mild steel expanded metal 20x60 mm strands sqm 0 0 0 196 0 196 0.00 0.00 0.00 0.00 0.00
101 Providing and fixing 24 mm dia. bolts and nuts of 925 mm in length providing and fixing bolts above 300 mm in length Kg 0 0 2106.3 0 0 2106.3 0.00 0.00 0.00 0.00 0.00
102 Steel work welded in built up sections/framed worK including cuttinghoisting, rixing in position and applying a priming coat of approvedsteel primer using structural steel, etc. as requiredIn gratings, frames, guard bar, ladders, railings, brackts. gates & similar works kg 4037.8455 10282.104 0 0 0 14319.9495 0.00 0.00 0.00 0.00 0.00
104 Structural steel work in single section fixed without connecting plate including cutting.hoisting.fixing in position and applying a priming coat of approved steel primer all complete. kg 0 1051.07 0 0 0 1051.07 0.00 0.00 0.00 0.00 0.00
105 Chain link fencing mesh of size 25x25 mm made of g.i. wire of dia. 3 mm. sqm 0 181.425 180 0 0 361.425 0.00 0.00 0.00 0.00 0.00
106 Labour cost of Stone Metal spreading in swich yard area all as per direction of E/I Each 118.5262712 148 265 111 170 812.5262712 0.00 0.00 0.00 0.00 0.00
107 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i Batten Holder Point 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
viii Ceiling Fan Point 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
108 Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Meter 0 0 0 125 0 125 0.00 0.00 0.00 0.00 0.00
109 Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit alongwith 2 Nos 4.0 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required. Meter 0 0 0 125 0 125 0.00 0.00 0.00 0.00 0.00
110 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. Each 0 0 0 75 0 75 0.00 0.00 0.00 0.00 0.00
111 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. Each 0 0 0 60 0 60 0.00 0.00 0.00 0.00 0.00
112 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (for CKT) Meter 0 0 0 1500 0 1500 0.00 0.00 0.00 0.00 0.00
ii 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire (For Street Light) Meter 0 0 0 150 0 150 0.00 0.00 0.00 0.00 0.00
iii 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire (For Computer + Multi Socket) Meter 0 0 0 1000 0 1000 0.00 0.00 0.00 0.00 0.00
iv 2 X 4 sq. mm + 1 X 4 sq. mm earth wire (For AC Point) Meter 0 0 0 550 0 550 0.00 0.00 0.00 0.00 0.00
v 4 X 10 sq. mm + 2 X 10 sq. mm earth wire (For TPN DB) Meter 0 0 0 475 0 475 0.00 0.00 0.00 0.00 0.00
113 Supplying and fixing 2 pin, 6 amp ceiling rose on the existing junction box/ wooden block including connection etc as required. Each 0 0 0 75 0 75 0.00 0.00 0.00 0.00 0.00
114 Supplying and fixing batten/ angle holder including connection etc. as required. Each 0 0 0 75 0 75 0.00 0.00 0.00 0.00 0.00
115 Supplying and fixing stepped type electronic fan regulator on the existing modular plate/ switch box including connections but excluding modular plate etc. as required. Each 0 0 0 75 0 75 0.00 0.00 0.00 0.00 0.00
116 Supplying and fixing electronic musical call suitable for single phase, 230 volts complete bell as required. Each 0 0 0 15 0 15 0.00 0.00 0.00 0.00 0.00
117 Supplying and fixing suitable size G.I. box with modular plate and cover in front on surface or in recess including providing and fixing 4 nos. 3 pin, 5/6 amps modular socket outlet and 4 nos. 5/6 amps modular switch, connection etc as required. ( Used for computer point ) Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
118 Supplying and fixing suitable size G.I. box with modular plate and cover in front on surface or in recess including providing and fixing 2 nos. 3 pin, 5/6 amps modular socket outlet and 2 nos. 5/6 amps modular switch, connection etc as required. ( Used for Multi point ) Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
119 Supplying and fixing modular type 25 amps A.C. unit box with ON/OFF MCB on surface or in recess complete with connections, testing and commissioning etc as required. Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
120 Supplying and fixing single wall mounted 18/22 watt LED type batten fitting complete with electronic driver and LED tube etc directly on wall/ ceiling including connections with 1.5 sq.mm FR PVC insulated copper conductor and earthing the body etc. as required. Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
121 Supplying and fixing of following types lamp in the existing electrical fitting/ fixtures etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
122 Supplying and fixing indoor recess mounting 36 watt LED flat panel luminaire suitable for armstrong / grid ceiling and complete with electronic driver etc. directly on false ceiling including connection with 1.5 sq.mm FR PVC insulated copper conductor cable and earthing the body etc. as required. Each 0 0 0 15 0 15 0.00 0.00 0.00 0.00 0.00
123 Supplying and fixing recess/surface mounted 23/24 (1ft X 1ft) watt LED downlighter complete with integrated electronic driver & LED directly on ceiling/false ceiling including connection with 1.5 sq.mm FR PVC insulated copper conductor cable and earthing the body etc. as required. Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
124 Supplying and fixing Surface mounted 15/18 watt LED downlighter complete with integrated electronic driver & LED directly on ceiling including connection with 1.5 sq.mm FR PVC insulated copper conductor cable and earthing the body etc. as required. Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
125 Supply and installation of regular/standard model A.C. ceiling fan of 1200 mm sweep including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated copper conductor etc as required. Each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
126 Supply and installation of 300 mm, 230 v A.C. exhaust fan in the existing opening including making good the damage, connection testing, commissioning etc as required. Each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
127 Supply and installation of 400 mm, 230 v A.C. wall/cabin fan including fixing the bracket, making connection, testing, commissioning etc as required. Each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
128 Supplying and fixing following way, horizontal type three pole & neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus - bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i 4 way ( 4 + 12 ), double door, horizontal type Each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
ii 6 way ( 4 + 18 ), double door, horizontal type Each 0 0 0 32 0 32 0.00 0.00 0.00 0.00 0.00
129 Supplying and fixing following rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
ii 40 amps, Tripole pole and neutral Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
iii 50/63 amps, Tripole pole and neutral Each 0 0 0 45 0 45 0.00 0.00 0.00 0.00 0.00
130 Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i 300 mm width X 50 mm depth X 1.6 mm thickness Each 0 0 0 125 0 125 0.00 0.00 0.00 0.00 0.00
131 SITC of Following size of ’G’ frame Loadbank Panel Board System is a power distribution board with MCCBs as incoming and outgoing switching-cum-protective devices, for distribution of power to various loads as per the requirements of the system.The modular construction of load bank renders the customary panel building redundant by virtue of compactness, reduced cost and short delivery time coupled with reliability of the various modular units. All units are fabricated using sheet steel of 1.6mm and are epoxy powder coated to give a superior finish. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
132 Providing and fixing following rating and breaking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
iii S/F of Double door Cable Alley I/C 400 A/630 A,O/G 4P GF 8Way Each 0 0 0 11 0 11 0.00 0.00 0.00 0.00 0.00
iv S/F of Meter Module - Digital Each 0 0 0 11 0 11 0.00 0.00 0.00 0.00 0.00
v S/F of Terminal for G Frame Outgoing (Per Pole) Each 0 0 0 125 0 125 0.00 0.00 0.00 0.00 0.00
vi S/F of Spreader Terminal 200 A~400 A Each 0 0 0 15 0 15 0.00 0.00 0.00 0.00 0.00
133 Supply of following sizes and core PVC/XLPE insulated, PVC sheathed armoured electrical cable with aluminium conductor for working voltage upto 1.1 KV etc as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
134 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
i Above 185 sq. mm and upto 400 sq. mm Metre 0 0 0 175 0 175 0.00 0.00 0.00 0.00 0.00
135 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonary enclosure with cover plate having locking arrangement and watering pipe 2.7 metre long etc. with charcoal/ coke and salt as required. Set 0 0 0 5 0 5 0.00 0.00 0.00 0.00 0.00
136 Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing etc. as required. Metre 0 0 0 65 0 65 0.00 0.00 0.00 0.00 0.00
137 Supplying and fixing 90 watt LED type street light with die cast aluminium housing for ingress protection of IP65 and complete with all accessories etc, on pole/building including connection with FR PVC insulated copper conductor cable and earthing the body etc. as required. Each 0 0 0 22 0 22 0.00 0.00 0.00 0.00 0.00
138 Supplying and embedding following dia G.I. pipe (medium class) in pole collar/ foundation (during casting) for cable entry including bending the pipe to the required shape complete as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
139 Supplying and fixing wall/floor mounted cubical panel board, fabricated with 16 gauge iron sheet, suitable for panel mounted switch disconnector, including bus-bar chamber, insulator and painting etc. as required. (but without busbar copper strip) Sq.ft 0 0 0 63 0 63 0.00 0.00 0.00 0.00 0.00
140 S/F copper Strip 50 mm X 5 mm sizes for bus-bar including interconnection etc. as reqd. P/Kg 0 0 0 84 0 84 0.00 0.00 0.00 0.00 0.00
141 Supply of Pilot lamp for indicator Each 0 0 0 21 0 21 0.00 0.00 0.00 0.00 0.00
142 Supply and fixing digital voltmeter, three phase in the existing cubical panel board including drilling holes in the panel board, making connection etc as required. Each 0 0 0 4 0 4 0.00 0.00 0.00 0.00 0.00
143 Supply and fixing digital Ammeter, three phase in the existing cubical panel board including drilling holes in the panel board, making connection etc as required. Each 0 0 0 4 0 4 0.00 0.00 0.00 0.00 0.00
144 Providing and fixing following rating and breaking capacity MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
145 Providing and fixing following capacity four pole ON-load/ panel mounted changeover switches inside the existing cubical panel board including drilling holes in cubicle panel, making connections etc. as required. 0 0 0 0 0 0 0.00 0.00 0.00 0.00 0.00
Note:- 1.Prices are firm and in any case price variation will not be considered. 2.Seigniorage fee corresponding to mining items such as Coarse sand, Local sand, Stone aggregate etc. as per prevelent rules of Mining Dept., GoB shall be borne by the bidders. 3. Rates shall be quoted inclusive of all transportation cost, duties, fixing cost and all applicale taxes.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT No. 15_PR_BSPTCL_2026.PDF
NIT • 0.35 MB
36085_BankDetails.pdf
NIT • 0.09 MB
36967_00852_VOL3(Tender Specification for GSS).pdf
NIT • 0.50 MB
37125_16814_TSTS-Insulator.pdf
NIT • 0.43 MB
37703_23015_Battery.pdf
NIT • 0.17 MB
37710_30014_Dual Float cum Boost Charger_Chandi.pdf
NIT • 0.34 MB
38198_TECHNICALSHEET-BAY.xls
NIT • 0.57 MB
38593_29429_Circuit Breaker.pdf
NIT • 0.53 MB
39111_23075_ABT Meter.pdf
NIT • 0.42 MB
39263_32821_Isolator.pdf
NIT • 0.28 MB
39858_43253_VMS.pdf
NIT • 0.37 MB
40930_40239_Power & Control Cables.pdf
NIT • 0.58 MB
41835_36571_Fire Protection System.pdf
NIT • 0.58 MB
46795_30238_Control & Protection Panel.pdf
NIT • 0.76 MB
48518_TS-CIVIL.pdf
NIT • 4.00 MB
50726_MoP order-Cyber testing at CPRI.pdf
NIT • 6.61 MB
51134_00589_spec for FO Cable (1).pdf
NIT • 0.65 MB
51197_39941_Porcelain Long Rod Insulator.pdf
NIT • 0.72 MB
51744_08184_TS - VOLUME-2A.pdf
NIT • 3.93 MB
51896_34280_EPAX & EPABX.pdf
NIT • 0.74 MB
52026_91120_TS_Surge arrester.pdf
NIT • 0.42 MB
53254_95951_Measuring and Testing Equipments.pdf
NIT • 0.95 MB
56214_16164_TS-CommunicationEquipment.pdf
NIT • 1.23 MB
58041_PLCC.pdf
NIT • 0.95 MB
59988_MoP_PPP_MII_Order_dated_16th_Nov_2021.pdf
NIT • 8.35 MB
60029_12273_TS - VOLUME-2B.pdf
NIT • 1.97 MB
68547_TECHNOCOMMERCIALSHEET.xls
NIT • 0.14 MB
75899_34667_VOL-2A.pdf
NIT • 4.48 MB
Debarment.pdf
NIT • 2.30 MB
SBD nit 15.pdf
NIT • 3.32 MB
58403_Pricesheet-NIT 15.xlsx
NIT • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .